ISOMETER® IR123P - 1

ISOMETER® IR123P Insulation monitoring device for mobile generators Preliminary datasheet

Open the catalog to page 1
ISOMETER® IR123P - 2

Device features • Insulation monitoring for unearthed DC systems (IT systems) 100...300 V • Automatic adaptation to the existing system leakage capacitance • Optimised measurement technique for low-frequency control processes • Electrically isolated PWM output for the kQ measuring value • Optocoupler output for signalling the device status • Automatic device self test _ Zh BENDER Insulation monitoring device for mobile generators Product description The ISOMETER'* IR123P monitors the insulation resistance /?p of an unearthed AC system of 100...300 V against earth, that is supplied by a...

Open the catalog to page 2
ISOMETER® IR123P - 3

1 - Input for reset button "R" (N/O contact) 6 - igital output optocoupler "OK+": Alarm 2; D Connect external operating voltage UB: max. +24 V 2 - Input for test button "T" (N/O contact) 7 - ulse-width-modulated output optocoupler "M+": measured value P Connect external operating voltage UB: max. +24 V 3 - Common input for test and reset button "T/R" 4 - Connect the leads E and KE separately to PE 8 - Common reference point -UB "OK-, M-" for OK+ and M+ 5 - Supply voltage US = Un Connection to the IT system to be monitored 9 - Alarm relay "K1" 10 - Alarm relay "K2" Application example with...

Open the catalog to page 3
ISOMETER® IR123P - 4

Technical data Interfaces Rated insulation voltage 250 V Rated impulse voltage/pollution degree 2.5 kV/3 Protective separation (reinforced insulation) between: Optocoupler, alarm UCE 24 V, IC 10 mA Optocoupler, measured value UCE ≤ DC 24 V, IC ≤ 10 mA PWM signal, duty cycle 0 % = ∞ kΩ PWM signal, duty cycle 50 % = 120 kΩ PWM signal, duty cycle 100 % = 0 kΩ Contact data acc. to IEC 60947-5-1: Rated operational voltage AC 230 V 230 V Utilisation category AC AC 13 AC 14 Rated operational current AC 5 A 3A Rated operational voltage DC 220 V 110 V 24 V Utilisation category DC DC 12 DC 12 DC 12...

Open the catalog to page 4

All BENDER catalogs and technical brochures

  1. CTBC17

    2 Pages

  2. POWERSCOUT®

    8 Pages

  3. Energy meter

    6 Pages

  4. RDC121

    7 Pages

  5. RCMB123

    7 Pages

  6. RCMB 121-2

    7 Pages

  7. RCMB121-1

    7 Pages

  8. RDC104-4

    6 Pages

  9. 300ST

    4 Pages

  10. 400ST

    4 Pages

  11. USC710D4

    6 Pages

  12. DI-1DL

    4 Pages

  13. DI-2

    4 Pages