COMTRAXX® CP9…-I series Condition monitor with display and an integrated gateway

Open the catalog to page 1
COMTRAXX® CP9...-I Serie - 2

Condition monitor with display and an integrated gateway Product description The COMTRAXX® CP9…-I series features a condition monitor with web interface and a display, which is available in different sizes. All Bender devices can be connected via the integrated interfaces. In addition, third-party devices can also be integrated into the system. The measured values, parameters and all other data can be checked and parameterised via the web interface or the display. There is a wide range of options for indicating and visualising alarms. Due to the robust surface and design, there are no...

Open the catalog to page 2
COMTRAXX® CP9...-I Serie - 3

• Quick and easy-to-create visualisation of the system. Integrated editor provides access to a variety of widgets and functions. – Display on up to 50 overview pages, where e.g. room plans can be stored. It is possible to navigate within these pages – Access to all measured values that are available in the system – Buttons and sliders can be used to send BMS test and reset commands, as well as to control external devices via Modbus TCP • 100 virtual devices with 16 channels each can be created. There, for example, calculations of several measured values can be carried out and the result can...

Open the catalog to page 3
COMTRAXX® CP9...-I Serie - 4

Technical data Insulation coordination acc. to IEC 60664-1 CP907-I Rated voltage Overvoltage category Pollution degree Rated impulse voltage CP915-I Rated voltage Overvoltage category Pollution degree Rated impulse voltage Supply CP907-I via plug-in terminal (A1/+;A2/-) Nominal voltage DC 24 V SELV/PELV Nominal voltage tolerance ±20 % Typical power consumption at DC 24 V < 15 W Connection plug-in terminal (A1/+;A2/-) Maximum cable length when supplied via B95061210 (24-V DC power supply unit 1.75 A): 0.28 mm² 75 m 0.5 mm² 130 m 0.75 mm² 200 m 1.5 mm² 400 m 2.5 mm² 650 m CP907-I via...

Open the catalog to page 4
COMTRAXX® CP9...-I Serie - 5

Device connections DNS (UDP/TCP) DHCP (UDP) HTTP (TCP) NTP (UDP) SNMP (UDP) SNMP TRAPS (UDP) HTTPS (TCP) MODBUS (TCP) OPCUA (TCP) MDNS (UDP) BCOM (UDP) Digital inputs (1-12) Number12 Galvanic separation yes Operating mode selectable for each input: active-high or active-low Factory setting active-high Voltage range (high) AC/DC 10…30 V Voltage range (low) AC/DC 0…2 V Max. current per channel (at AC/DC 30 V) 8 mA Connection push-in terminal (1-1) (2-2) (3-3) … (12-12) Maximum cable length < 1000 m Switching elements Number 1 relay Operating mode N/C operation or N/O operation Function...

Open the catalog to page 5
COMTRAXX® CP9...-I Serie - 6

Application example Integrated functions E-Mail notification Backups Documentations Parameter Data transfer … Additional hardware necessary Solution for BACnet Solution for OPC … Bender GmbH & Co. KG Londorfer Straße 65 • 35305 Grünberg • Germany Tel.: +49 6401 807-0 • info@bender.de • www.bender.de BENDER Group CP9xx-I_D00418_04_D_XXEN / 02.2022 / © Bender GmbH & Co. KG, Germany – subject to change! The specified standards take into account the edition valid until 02.2022 unless otherwise indicated.

Open the catalog to page 6

All BENDER catalogs and technical brochures

  1. CTBC17

    2 Pages

  2. POWERSCOUT®

    8 Pages

  3. Energy meter

    6 Pages

  4. RDC121

    7 Pages

  5. RCMB123

    7 Pages

  6. RCMB 121-2

    7 Pages

  7. RCMB121-1

    7 Pages

  8. RDC104-4

    6 Pages

  9. 300ST

    4 Pages

  10. 400ST

    4 Pages

  11. USC710D4

    6 Pages

  12. DI-1DL

    4 Pages

  13. DI-2

    4 Pages