ATICS®-2-63A-ISO ATICS®-2-80A-ISO Automatic transfer switching devices with monitoring functions for unearthed safety power supplies

Open the catalog to page 1
ATICS®-2-63A-ISOATICS®-2-80A-ISO - 2

Automatic transfer switching devices with monitoring functions for unearthed safety power supplies Task Power supplies for sensitive equipment used in group 2 medical locations, for example, must function safely and reliably even in the event of malfunctions. A major contribution to achieve this are redundant supply lines and the design of an unearthed power supply system (IT system). Product description ATICS® transfer switching devices provide all functions for changeover between two indepen dent power supplies and for monitoring unearthed power supplies. The power section and the...

Open the catalog to page 2
ATICS®-2-63A-ISOATICS®-2-80A-ISO - 3

ATICS®-ISO – transfer switching and monitoring devices Standards The transfer switching device conforms to the following standards: Standard-compliant isolating transformer monitoring according to: The standards marked with * were part of the test conducted by TÜV Süd. Rated operational current Ie Rated operational voltage Ue * with connection option for ATICS-ES energy storage device. Dimension diagram Dimensions in mm 234 176 Description Measuring current transformer (load current monitoring IT system), Ie: AC 50 A Measuring current transformer (short-circuit monitoring) for ATICS® < 100...

Open the catalog to page 3
ATICS®-2-63A-ISOATICS®-2-80A-ISO - 4

ATICS®-ISO – transfer switching and monitoring devices Application examples Preferred supply line Second supply line • IR426-D47: Monitoring of the operating theatre light IT system (optional) • K2430/CP9xx: Alarm at at least two points with inM dependent power supplies for functional safety • ATICS-ES: Energy storage (B92057206, B92057207 only) Application example operating theatre • TICS®-2-63A-ISO: Changeover between the A preferred and the redundant line while monitoring the medical IT system with transformer load and temperature monitoring Nurse desk Operating theatre Preferred supply...

Open the catalog to page 4
ATICS®-2-63A-ISOATICS®-2-80A-ISO - 5

ATICS®-ISO – transfer switching and monitoring devices Technical data Insulation coordination acc. to IEC 60664-1/IEC 60664-3 Overvoltage category III Pollution degree outside, inside 2 Rated insulation voltage 250 V Protective separation between line 1 – line 2; line 1, 2, 3 – RS-485 line 1, 2, 3 – digital inputs; line 1, 2, 3 – relay outputs Voltage test according to IEC 61010-1 (basic insulation/protective separation) 2.21 kV/3.54 kV Insulation monitoring Supply voltage Rated operational voltage Ue Supply voltage US Power consumption at 63 A Power consumption at 80 A Current during...

Open the catalog to page 5
ATICS®-2-63A-ISOATICS®-2-80A-ISO - 6

Technical data (continuation) Terminals Digital inputs 1 Galvanic separation yes Control via potential-free contacts Mode of operation active at 0 V (low) or 24 V (high), adjustable Voltage range high/low AC/DC 10…30 V/AC/DC 0…0.5 V Adjustable functionswitching back interlocking function, manual/automatic mode, bypass operation, function test, changeover of the preferred line, alarm input for operating theatre lights, alarm input for other devices Power section Connection directly on ATICS®, for plug connections screw-type terminals rigid (flexible)/conductor sizes 10…70 mm² (6…50 mm²)/8...

Open the catalog to page 6

All BENDER catalogs and technical brochures

  1. CTBC17

    2 Pages

  2. POWERSCOUT®

    8 Pages

  3. Energy meter

    6 Pages

  4. RDC121

    7 Pages

  5. RCMB123

    7 Pages

  6. RCMB 121-2

    7 Pages

  7. RCMB121-1

    7 Pages

  8. RDC104-4

    6 Pages

  9. 300ST

    4 Pages

  10. 400ST

    4 Pages

  11. USC710D4

    6 Pages

  12. DI-1DL

    4 Pages

  13. DI-2

    4 Pages