1. Catalogs
  2. BENDER GmbH & Co KG
  3. ISOMETER® IRDH275BM-7

ISOMETER® IRDH275BM-7
1 /6Pages

ISOMETER® IRDH275BM-7

ISOMETER® IRDH275BM-7
1 /6Pages

Catalog excerpts

ISOMETER® IRDH275BM-7-1

Device combination for insulation monitoring in unearthed AC, AC/DC and DC power systems (IT systems)

 Open the catalog to page 1
ISOMETER® IRDH275BM-7-2

Device combination for insulation monitoring in unearthed AC, AC/DC and DC power systems (IT systems) ISOMETER® IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15 Product description Device features • Insulation monitoring for drives including medium voltage converters up to 15.5 kV • Two separately adjustable response values 100 kfi...10 Mfi • AMPPlus measurement method (European patent: EP 0 654 673 B1) • Automatic adaptation to the system leakage capacitance • Info button to display device settings and the system leakage capacitance • History memory with real-time clock to store alarm...

 Open the catalog to page 2
ISOMETER® IRDH275BM-7-3

AC/DC Operating elements 1 - "INFO" button: to query standard information back (menu function), to confirm parameter change 2 - "TEST" button: to call up the self test. Arrow up button: parameter change, to move up in the menu 3 - Two-line display for standard and menu mode 4 - "RESET" button: to delete stored insulation fault alarms parameter change, to move down in the menu 5 - "MENU" button: to call up the menu system. Enter button: to confirm parameter change insulation fault, first warning level reached. insulation fault, second warning level reached. 8 - System fault LED lights: IRDH275...

 Open the catalog to page 3
ISOMETER® IRDH275BM-7-4

Wiring diagram - mains connection/example for UL and CSA applications, it is mandatory to use 5 A fuses. 2,3 - Terminals L1, L2 are not connected! 4 - Connection to the coupling device AGH675S-7 or the two Connect terminal AK to terminal(s) 5 of the coupling device AGH675S-7 (or the two coupling devices AGH675S-7MV15), Connection with standard low-voltage cable, maximum voltage at terminal 5: 200 V 6 - Separate connection of the terminals 3 and 4 of the 7 - External TEST button (NO contact) 8 - External RESET button (NC contact or wire jumper), when the terminals are open, the fault message will...

 Open the catalog to page 4
ISOMETER® IRDH275BM-7-5

Technical data IRDH275BM-7 Insulation coordination acc. to IEC 60664-1 Rated voltage Rated impulse voltage/pollution degree Voltage ranges Nominal voltage range Un Supply voltage US (also see nameplate) Frequency range US Supply voltage US (also see nameplate) Power consumption Response values Response value Ran1 (Alarm 1) Response value Ran2 (Alarm 2) Relative percentage error 100…500 kΩ Relative percentage error 500 kΩ…10 MΩ Response time tan Hysteresis Measuring circuit Measuring voltage Um Measuring current Im (at RF = 0 Ω) Internal DC resistance Ri Internal impedance Zi, at 50 Hz Permissible...

 Open the catalog to page 5
ISOMETER® IRDH275BM-7-6

Rated insulation voltage AGH675S-7MV15 Rated insulation voltage Type test: Voltage impulse test (basic insulation) AC voltage test (basic insulation) Partial discharge test Voltage impulse test (basic insulation) AC voltage test (basic insulation) Partial discharge test Routine test: Operating temperature (normal operation) - 10...+60 °C AC 7 2 k V Operating temperature (continuous operation with asymetrical earth fault - 10.+ 55 °C Classification of climatic conditions acc. to IEC 60721 AC 15.5 k V Stationary use (IEC 60721-3-3) 3K5 (no condensation, no formation of ice) Classification of mechanical...

 Open the catalog to page 6

All BENDER GmbH & Co KG catalogs and technical brochures

  1. CD25000

    4  Pages

  2. CD14400

    4  Pages

  3. CD1000

    4  Pages

  4. AUR381Z

    4  Pages

  5. AN110

    4  Pages

  6. AGH575S-6

    4  Pages

  7. CD1000-2

    4  Pages

  8. MRCDB300 series

    12  Pages

  9. AN111

    4  Pages

  10. AN450

    4  Pages

  11. AN420

    4  Pages

  12. AN410

    4  Pages

  13. STEP-PS

    8  Pages

  14. CTBC17 series

    8  Pages

  15. IPM1300

    8  Pages

  16. CC613

    6  Pages

  17. ICC1324

    8  Pages

  18. ICC1314

    8  Pages

  19. AGH676S-4

    4  Pages

  20. AGH520S

    4  Pages

  21. AGH204S-4

    4  Pages

  22. AGH150xx

    4  Pages

  23. AT series

    6  Pages

  24. DI-1DL

    4  Pages

  25. SMO482P-12

    4  Pages

  26. DI-2USB

    4  Pages

  27. POWERSCOUT®

    8  Pages

  28. SEB30, SEB60

    8  Pages

  29. VIT-AFSBY

    6  Pages

  30. VIT-A

    6  Pages

  31. RDC125-5S

    12  Pages

  32. RCMB131-01

    4  Pages

  33. RDC121

    7  Pages

  34. RCMB123

    7  Pages

  35. RDC104-4

    6  Pages

  36. RCMB104

    6  Pages

  37. RCMB300-series

    12  Pages

  38. Energy meter

    6  Pages

  39. PEM353

    8  Pages

  40. DS0107

    6  Pages

  41. ESL0107

    4  Pages

  42. ES710

    8  Pages

  43. AGH520S

    4  Pages

  44. RCM410R

    8  Pages

  45. RCMS410

    10  Pages

  46. RCMS425-D

    10  Pages

  47. EDGE500

    12  Pages

  48. Iso415R

    4  Pages

  49. Iso685-x-B

    12  Pages

  50. Iso685-x-P

    14  Pages

  51. Iso685-x

    12  Pages

  52. Data Centers

    16  Pages

  53. RCMB104

    6  Pages

  54. Main Catalogue

    486  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.