Product catalog summary
Description
  • Standard local authority sanitary regulations require protection of public drinking water networks from backflow of polluted water using approved devices.
  • Features include a controllable check valve, security air gap, and low head loss.
  • Anticorrosion protection with bronze, stainless steel, and ductile iron materials.
  • Maintenance can be performed in situ without dismantling.
  • Conforms to standards EN 12729, NF E 29-305-1, ISO 51752, and EN 1717.
  • NF ANTIPOLLUTION mark certified.
Technical Data
  • Range: DN 150 to 250.
  • Maximal working pressure: PN 10.
  • Temperature range: +10°C to +60°C (up to +90°C for backflow).
  • Flanges: ISO PN10, ISO PN16 on request.
Applications
  • Designed for drinkable water networks to prevent backflow due to pressure drops or back pressure from non-potable networks.
Operation Principle
  • The Discobloc consists of a body with upstream and downstream spring-loaded check valves, creating three pressure zones.
  • In normal operation, the intermediate zone pressure is always at least 1.4mWH less than the upstream pressure, ensuring the discharge remains closed.
  • If pressure differences drop, the discharge opens to maintain the required pressure difference, preventing backflow.
Installation
  • Should be installed at the point of drinking water supply, after the water meter, and in compliance with regulations.
  • Must be checked and maintained annually by an approved specialist.
  • Installation should be horizontal and in an accessible inspection chamber.
Important Remark
  • Before installation, pipes should be flushed with large amounts of water to ensure cleanliness.
See more

Catalog excerpts

DISCOBLOC BA-1

Backflow preventer with reduced pressure zone DISCOBLOC BA - Series H2 10 Designed to protect drinking water networks from backflow of polluted water due to: - a pressure drop in the network - a back pressure from a potentially non potable water network. Description • Standard local authority sanitary regulations (art. 16.1) make it obligatory for owners of installations, which are potentially dangerous, to protect public drinking water network and the internal network from the risk of the backflow of polluted water, this being by means of an approved and regularly maintained device. • Reliability: - Controllable check valve with upstream, downstream and intermediate pressure gauge taps, - Security air gap with discharge valve, in case of upstream pressure drop, - Head loss lower than standard’s requirements. • Anticorrosion protection: - Sub set of valve and seat in bronze, stem and spring made of stainless steel, - Body in ductile iron with epoxy powder coating. • Maintenance in situ without dismantling. - EN 12729 - NF E 29-305-1 and ISO 51752 for face-to-face dimensions. - Global EN 1717. • NF ANTIPOLLUTION mark. Technical data • Range: DN 150 to 250. • Maximal working pressure: PN 10. • Temperatures: +10°C to +60°C (maximum temperatures for backflow +90°C). • Flanges: ISO PN10, ISO PN16 on request. Applications • Drinkable water networks.

 Open the catalog to page 1
DISCOBLOC BA-2

Body DN150 DN200 and 250 Bonnet Bolts (bonnet) Discharge sub set Supporting disc + spring Discharge stem Upper disc Diaphragm Valve holder Lower disc Discharge check valve Seat Diaphragm support Upstream check valve sub set Body Axix Check valve Seat O-rings Downstream check valve sub set Split ring Pressure cocks Discharge funnel sub set Saddle Funnel Bolts Chamber connecting set DN 150 Connection O-rings Upstream pressure sub set DN 200 to 250 Connection Cast iron/EN-GJL 250 Ductile iron/EN-GJS 450-10 Bronze/CuSn5Zn5Pb5 Steel A2 Bronze/CuSn12 PTFE coated stainless steel /X8CrNiS 18-9 + PETP...

 Open the catalog to page 2
DISCOBLOC BA-3

Operation principle Description The Discobloc consists of a body closed by a bonnet, an upstream spring loaded check valve (1) and a downstream spring loaded check valve (2). The whole delimits 3 different pressure zones : upstream zone A, intermediate zone B and downstream zone C. The intermediate zone contains a discharge device (3) in the lower part and is connected by a spindle to the main diaphragm (4) and to the compensating diaphragm (5). This mobile unit is drawn upwards by an external spring (outside water) (6) with a calculated force, calibrated in factory. Diaphragms (4) and (5) enclose...

 Open the catalog to page 3
DISCOBLOC BA-4

Location of backflow preventer • On a drinking water network for protecting water supply points for sanitary use: wash-basins, showers, kitchens, etc. the Discobloc is to be located at the limit of pollution generating zones such as : collective central heating, internal fire-fighting networks with stagnant water under pressure, garden watering systems, specialized workshops handling dangerous products, laboratories, etc • At the point at which the drinking water is supplied, after the water meter, for protecting the public network, in case of installations which are complex, dangerous and difficult...