Breeze V1 Datasheet

Breeze V1 Datasheet

Breeze V1 Datasheet

Product catalog summary
Description
V1 series motorized valves are designed for use with thermostats in domestic and commercial central heating, hot water, and chilled water systems. They control water flow and are suitable for both heating and cooling applications. The valves feature a forged HPB59-1 brass body, stainless base with aluminum case, and nitrile rubber sealing material. They are driven by a sealed synchro motor with a stainless steel return spring and are available as normally closed 2-way or 3-way diverting valves. The valves are reliable, with a lifespan of 10,000 working cycles, and are easy to install and wire. Actuators and valve bodies are supplied separately for convenience.
Main Parameters
  • Power Supply: AC220V/AC24V±10% 60Hz
  • Power Consumption: 6.5W
  • Pressure Rating: 1.6Mpa
  • Valve Reaction Time: Open Time ≤12 s, Close Time ≤8 s
  • Work Condition: Temperature 5~40℃
  • Working Medium: Cold/Hot water 2~90℃
  • Motor Torque: >800gf.cm
Specification
The valves are available in various models with different power options (220V or 24V) and sizes (1/2”, 3/4”, 1”). Each model has specific Kv values, closing pressures, and dimensions. For example, the V1-W2D15 model is a 220V, 1/2” valve with a Kv of 2.2 and a closing pressure of 0.2 MPa.
Installation
  • Use a pressure reducing valve for high-rise buildings.
  • The actuator should not be placed under the pipe to avoid water infiltration.
  • Ensure the motor cover avoids water infiltration when installed on a vertical pipe.
  • To manually operate, move the hand lever slowly along the arrow direction and press it into the groove for a normally open state. The lever will return to automatic when powered.
  • For actuator installation, align the lever into the groove, press the black button, place the actuator on the valve, and release.
Warning
  • Ensure water quality meets air conditioning system requirements.
  • Power must be off during maintenance to prevent equipment damage and personal injury.
  • Avoid dismounting or touching the circuit when power is on.
See more

Catalog excerpts

Breeze V1 Datasheet-1

V1 Series Motorized Valve V1 series motorized valves work with thermostats are used in domestic and commercial central heating, hot water and chilled water systems to control the flow of water in the system. • Suitable for heating and cooling applications • Forged HPB59-1 Brass Body, Stainless base with aluminum case • Sealing material: nitrile rubber(NBR) • Driven by sealed synchro motor with stainless steel return spring • Valve Type: Normally Closed 2-way or 3-way diverting valve • Proven reliability: 10K working times, Easy installation and wiring • Actuators and valve bodies supplied separately for convenience 4. Valve Reaction time: Open Time: %M2 s, Close Time: ^8 s 5. Work Condition: Temperature around: 5~40°C 6. Working Medium: Cold/Hot water 2~90C

 Open the catalog to page 1
Breeze V1 Datasheet-2

Installation •For high-rise buildings, please use pressure reducing valve on the bottom of branch pipe •The actuator cannot be placed under the pipe when installation since the cover of motor should avoid water infiltration. •The cover of motor must avoid water infiltration when the valve is installed on the vertical pipe. •The manual operating lever: Make the hand lever move slowly along the direction of the arrow, then press it into the groove, the valve will in a normally open state. When current flows through the motorized valve for the first time, the hand lever will be back to automatic...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.