Catalog excerpts
V-DATA SHEET BDTM957 - FIVE VALVE MANIFOLD Badotherm manifold model BDTM957 is a five valve manifold that can be used for isolation, bleeding, calibration, and testing of differential pressure instruments. The BDTM957 manifold has the process connections on the bottom side and the instrument connections on the top side. All Badotherm manifolds are standard stainless steel and optional available in exotic materials. This valve is available with a rotatable conical tip to ensure perfect alignment for a bubble tight shut-off. MATERIAL SPECIFICATIONS BODY STEM TIP BONNET SPINDLE GASKET TECHNICAL SPECIFICATIONS BDTM957 flow diagram product features Process connection l/2"NPT-f VENT. INST. VENT. non-rotating spindle tip Instrument connection flanged - IEC 61518 & y- bonnet locking pins Vent connection l/4"NPT-f H><!>-+H>l5>-4--l>fcH safety back seating T-bar Maximum pressure 413 bar (6.000 psi) at 38°C 4i ty 2x isolation valves (blue) Maximum temperature 240 °C A A 2x vent valves (red) PRQQ equalizing valve (green) EXOTIC SPINDLE CONFIGURATIONS AND BODY MATERIALS stem_tip_code_ body material Super Duplex 2507_Stellite 6B SD-6b Super Duplex 2507 Titanium Gr. 2 Stellite 6B T2 - 6b Titanium Gr. 2 SPINDLE GASKET material operating temperature ■ cleaning for oxygen service (only with Virgin PTFE spindle gasket) ■ anti-tamper spindle to prevent unauthorized use ■ mounting bracket for 2" pipe mounting ■ assembly kit including bolts, gaskets and anti-seizure compound
Open the catalog to page 1V-DATA SHEET BDTM957 - FIVE VALVE MANIFOLD DESIGN INFORMATION AND DRAWINGS DESIGN STANDARD PRESSURE TESTING WEIGHT PRESSURE TEMPERATURE TABLE 1Only applicable in combination with Flexible Graphite gasket
Open the catalog to page 2Holland – UK – Romania – India – Thailand – Dubai - USA To our knowledge, the information contained herein is accurate as of the date of this document. However neither Badotherm, nor its affiliates makes any warranty, express or limited, or accepts any liability in connection with this information or its use. This information is for technical skilled persons at their own discretion and risk and does not relate to the use of this product in combination with any other product. The user alone finally determines suitability of any information or material in contemplated use, the manner of use...
Open the catalog to page 3All Badotherm Group catalogs and technical brochures
-
DLD Diaphragm Leak Detection
2 Pages
-
TC Temperature Compensator
2 Pages
-
US FH
3 Pages
-
BRC
3 Pages
-
EXT
3 Pages
-
BC
4 Pages
-
Thermowells
14 Pages
Archived catalogs
-
commercial catalogue 2006/07
324 Pages