AT9000 Advanced Transmitter for Differential Pressure
24Pages

{{requestButtons}}

Catalog excerpts

AT9000 Advanced Transmitter for Differential Pressure - 1

No. SS2-GTX00D-0500 (Rev.3) AT9000 Advanced Transmitter Differential Pressure Transmitters OVERVIEW AT9000 Advanced Transmitter is a microprocessor-based smart transmitter that features high performance and excellent stability. Capable of measuring gas, liquid, vapor, and liquid levels, it transmits 4 to 20 mA DC analog and digital signals according to the measured differential pressure. It can also execute two-way communications between the Smart Communicator or HART® 375 communicator, thus facilitating self-diagnosis, range resetting, and automatic zero adjustment. FEATURES High performance and stability • Unique characterization and composite semiconductor sensors realize high accuracy up to 0.04% F.S. • Our proven sensor technology enables Longterm stability up to 0.1% of URL per 10-year. Wide measuring range (range ability) • A wide measuring range is available from a single model. This feature is highly effective in taking measurement over a wide range and reducing the need for inventory. • Model GTX30D/31D/32D: 2 to 400 inH2O (0.5 to 100 kPa) (range ability: 200 to 1) A diverse lineup • A wide range of models is available to meet user requirements. They include draft range differential pressure, standard differential pressure, high differential pressure, standard differential pressure/high static pressure, and high differential pressure/high static pressure models. Specifications are subject to change without notice. • A wide variety of corrosion-resistant materials for wetted parts is also available. Remote communication • Two-way communication using digital output facilitates self-diagnosis, range resetting, automatic zero adjustment, and other operations. • HART® protocol communication is available. (Option) China RoHS This device is used in the Oil & Gas, Petrochemical, Chemical, Pulp & Paper, Food & Beverage, Machinery, Steel/Metal & Mining, and Automobile industries and therefore does not fall under the China RoHS Legislation. If this device is used in semiconductor manufacturing equipment, labeling on the device and documents for the China RoHS may be required. If such documents are required, consult a Yamatake representative. HART® is a registered trademark of the HART Communication Foundation. -1- “This product is designed for general industrial use.”

Open the catalog to page 1
AT9000 Advanced Transmitter for Differential Pressure - 2

Yamatake Corporation FUNCTIONAL SPECIFICATIONS FM Explosionproof and Dust Approvals Explosionproof for Class I, Division 1, Groups A, B, C Dust-Ignitionproof for Class II, III, Division 1, Groups E, Hazardous locations Indoor / Outdoor Type 4X, IP67 Factory sealed, conduit seal not required for Division Caution - Use supply wires suitable for 5°C above sur- rounding ambient FM Intrinsically safe Approval Entity Parameters: Vmax(Ui)=30 Volts, Imax(Ii)= 100mA, Nonincendive Field Wiring Parameters: Vmax(Ui)=30 ATEX Flameproof and Dust Certifications Caution - Use supply wires suitable for 5°C...

Open the catalog to page 2
AT9000 Advanced Transmitter for Differential Pressure - 3

Yamatake Corporation No. SS2-GTX00D-0500 (Rev.3) IECEx Intrinsic safety and Dust Certifications (Code E2) Measuring span / Setting range / Working pressure range IECEx KEM 07.0058X Zone 0 Ex ia IIC T4 TPROCESS = 105 °C -30 °C < Tamb < +60 °C IP66 / 67 ELECTRICAL PARAMETERS: Ui = 30 V, Ii = 93 mA, Pi = 1 W, Ci = 5 nF, Li = 0.5 mH Ex iaD 20 IP66 / 67 T105 TPROCESS = 105 °C -30 °C < Tamb < +60 °C Mo Measuring Span Measuring range Working Pressure Range del GTX 0.4 to 8 inH2O 15D (0.1 to 2 kPa) GTX 2 to 400 inH2O 30D (0.5 to 100 kPa) 5.1 to 101 psi -14.5 to 101 psi 5.1 to 101 psi -14.5 to 101...

Open the catalog to page 3
AT9000 Advanced Transmitter for Differential Pressure - 4

No. SS2-GTX00D-0500 (Rev.3) Yamatake Corporation 17.9 to 42V DC. Reverse polarity protection is standard. A load resistance of 250 Ω or more is necessary between loops. See Figure 5. Unusable range 1482 1345 Normal operating range Load resistance (Ω) 14.7 (101.3) 7.7 (53) -40 14 104 0.0219 Operating Range 245 Figure 2 Working pressure and temperature of wetted parts section (for oxygen and chlorine service) 0 12.5 17.9 42 45 Supply voltage (V DC) Figure 5 Supply voltage vs. load resistance characteristics 30.4 (210) 0 Normal operating range Note) Operative limit Operating limit Working...

Open the catalog to page 4
AT9000 Advanced Transmitter for Differential Pressure - 5

Yamatake Corporation -40 to 158°F (-40 to 70°C) for models with digital indi- -13 to 185°F (-25 to 85°C) for models with digital indi- Transportation and storage conditions -58 to 185°F (-50 to 85°C) for general purpose models 5 to 149°F (-15 to 65°C) for general purpose model 5 to 185°F (-15 to 85°C) for general purpose model Temperature ranges of wetted parts Normal operating range -40 to 230°F (-40 to 110°C) for general purpose models 5 to 149°F (-15 to 65°C) for general purpose model (model 5 to 230°F (-15 to 110°C) for general purpose model 14 to 149°F (-15 to 65°C) for oxygen and...

Open the catalog to page 5
AT9000 Advanced Transmitter for Differential Pressure - 6

Yamatake Corporation No. SS2-GTX00D-0500 (Rev.3) Center body 316 SST ƽ Transmitter case Aluminum alloy CAUTION • After installing the transmitter, do not stand on it. Using it as a foothold could cause it to collapse and cause physical injury. • Be careful not to hit the glass indicator with tools etc. This could break the glass and cause injury. • The transmitter is heavy. Wear safety shoes and take care when installing it. • Impact to transmitter can damage sensor module. Meter body cover flange SCS14A (Equivalent to 316 SST) or 316 SST, PVC For Wetted parts Adapter flange (option) SCS14A...

Open the catalog to page 6
AT9000 Advanced Transmitter for Differential Pressure - 7

Yamatake Corporation No. SS2-GTX00D-0500 (Rev.3) PERFORMANCE SPECIFICATIONS Reference accuracy Shown for each item are the percentage ratio for χ (inH2O/psi), which is the greatest value of either the upper range value (URV)*1, the lower range value (LRV)*2 or the span. Model GTX15D (Material of wetted parts: Diaphragm; 316L SST, Others; 316 SST) Reference accuracy (*4) Linear output: 4.0⎞ ⎛ ± ⎝ 0.15 + 0.15 × ------ ⎠ % χ When output is 50 to 100%:same as linear output Square-root output: 50 When output is 7.1 to 50%: linear output × --------------------------------------------------------...

Open the catalog to page 7

All Azbil North America catalogs and technical brochures

  1. NX-D25

    2 Pages

  2. NX-CB2

    1 Pages

  3. RN748A

    1 Pages

  4. HM

    1 Pages

  5. FL2 Series

    6 Pages

  6. LJM-D series

    4 Pages

  7. HP100

    10 Pages

  8. HPX

    10 Pages

  9. HPX-AG

    20 Pages

  10. APT

    2 Pages

  11. APM

    6 Pages

  12. FL7M

    10 Pages

  13. ATT70

    8 Pages

  14. WaterMAG

    8 Pages

Archived catalogs