Power factor correction catalogue
36Pages

{{requestButtons}}

Catalog excerpts

Power factor correction catalogue - 1

Onduleurs • Redresseurs • Batteries

Open the catalog to page 1
Power factor correction catalogue - 3

Page How to choose compensation battery tor the reactive power -1,2 Selection table for protections and cables - 3 Selection table for current transformers (T.l) of capacitor / banks - 3 Energy saving: increasing energy efficiency - 4 Compensation: improving power factor - 5 Automatic capacitor banks - general- 6 Automatic capacitor banks B25 series - 7,8 Automatic capacitor banks B35 series - 9,10 Automatic capacitor banks B50 series - 11,12 Automatic capacitor banks AR180 series - 13,14 Automatic capacitor banks AR140 series - 15,16 Static capacitor banks AST series - 17,18 Fixed...

Open the catalog to page 3
Power factor correction catalogue - 4

Ooduleurs • Redresseurs • Batteries Capacitor bank without regulation known as fixed compensation • Used when reactive power to compensate is constant and when the load is working 24h / 24h. • Used when reactive power is to compensate for low power. Also standardized by the coefficient QC (Compensation to install in KVAR) / SN (Transformer power in KVA) is generally <15%. This threshold of 15% is indicative and we recommend it to avoid to overcompensate the charge power vacuum. • Used to directly compensate the asynchronous motor, load losses of the line head transformer. Table of the...

Open the catalog to page 4
Power factor correction catalogue - 5

Onduleurs • Redresseurs • Batteries Capacitor banks with regulation also called automatic compensation • Used when the load changes on the installation and the need to compensate the reactive power is enabled through switched capacitor modules in or out sen/ice by the digital power factor controller Aunilec type RAUNI96 or RAUNI144 • Used for main switchboard (Low Voltage General Table) or from main departure of the factory • The power varying more or less rapidly can play an important role in choosing the automatic capacitor bank. - Either by electromechanical contactors if the rate of...

Open the catalog to page 5
Power factor correction catalogue - 6

Selection table for protections and cables for three phase capacitors - Voltage 400V Selection table for current transformers (Tl) for three phase capacitors - Voltage 400V * With EPR insulation, temperature 30°C (unit mm2) ui www.aunilec.com We recommend to install an opening Tl in order to save time for the implementation and therefore reduce installation costs. Available with opening of 20 * 30 to 80 * 160mm.

Open the catalog to page 6
Power factor correction catalogue - 7

Onduleurs • Redresseurs • Batteries Industrial plants where the load varies greatly throughout normal operation will require automatic power factor controller in order to connect the necessary capacitive power. Why power factor should be improved? The benefits are the following: • Reduce utility charges • Increase system capacity • Improve voltage • Reduce circuit losses Reduce utility charges Thermal capacity considerations force the Utilities to overbuild its distribution system in order to serve a facility with low power factor. The Utilities force the customer to install capacitors...

Open the catalog to page 7
Power factor correction catalogue - 8

Ooduleurs • Redresseurs • Batteries Operating conditions Nominal voltage The nominal voltage of the capacitor bank is the voltage at which the product was designed and to which the test voltages refer. For safe conditions, the operating voltage must not exceed the rated capacitor banks voltage. Working temperature Working temperature is a fundamental parameter for the safe functioning of Power Factor Correction Equipment. Consequently, it is very important to have sufficient heat dissipation inside the Power Factor Correction Equipment cubicle. Ventilation should be adequate to prevent that...

Open the catalog to page 8
Power factor correction catalogue - 9

Power Factor correction in presence of harmonics In recent years. Power Factor Correction has evolved greatly due to the presence of generated harmonics by the loads. These loads produce harmonic currents and voltage which distorts the network waveforms. The main sources of harmonics are generated by AC/DC static converters and UPS systems. For these reasons it is essential that any installation of Power Factor Correction equipment must be carefully evaluated. The possible presence ot harmonic currents in the network could create conditions of parallel resonance between the inductance...

Open the catalog to page 9
Power factor correction catalogue - 10

Ooduleurs • Redresseurs • Batteries Automatic capacitor banks B25 series Automatic capacitor banks ; Serie B25 THDi < 25% Technical characteristics Rated voltage: 400Vac Rated frequency: 50Hz (60Hz on request) Voltage of auxiliary circuits: 1lOVac Working temperature range: -10°C/+50°C Cubicle: 20/1 Omm sheet steel, protected against corrosion by a phosphating treatment. Epoxy powder painted, RAL 7035 color (other colors on request) External Protection Degree: IP30 (type S-M), IP40 (Type L) Locking system: by screw for cubicle type S and type M type by key for cubicle type...

Open the catalog to page 10
Power factor correction catalogue - 11

Network: 400Vac 50Hz THDi <10% Resonance non allowed Capacitors: 440Vac 50Hz, THDi <25% , Automatic capacitor banks Serie B25THDi<25%

Open the catalog to page 11
Power factor correction catalogue - 12

Ooduleurs • Redresseurs • Batteries Automatic capacitor banks B35 series Automatic capacitor banks Serie B35 THDi < 35% Technical characteristics Rated voltage: 400Vac Rated frequency: 50Hz (60Hz on request) Voltage of auxiliary circuits: 1lOVac Working temperature range: -10°C/+50°C Cubicle: 20/1 Omm sheet steel, protected against corrosion by a phosphating treatment. Epoxy powder painted, RAL 7035 color (other colors on request) External Protection Degree: IP30 (type S-M), IP40 (Type L) Locking system: by screw for cubicle type S and type M by key for cubicle type...

Open the catalog to page 12
Power factor correction catalogue - 13

'Ai/tilec" Onduleurs • Redresseurs • Batteries 11 I Types) (Type M) (Type L] (Type L) Network: 400Vac 50HzTHDi <15%. Resonance non allowed Capacitors: 500Vac 50Hz, THDi <35%

Open the catalog to page 13
Power factor correction catalogue - 14

Ooduleurs • Redresseurs • Batteries Automatic capacitor banks Serie B50 THDi < 50% Technical characteristics Rated voltage: 400Vac Rated frequency: 50Hz (60Hz on request) Voltage of auxiliary circuits: 1lOVac Working temperature range: -10°C/+50°C Cubicle: 20/10mm sheet steel, protected against corrosion by a phosphating treatment. Epoxy powder painted, RAL 7035 color (other colors on request) External Protection Degree: IP30 (type S-M), IP40 (Type L) Locking system: by screw for cubicle type S and type M by key for cubicle type L Ventilation: Forced Isolating switch: Three-pole with door...

Open the catalog to page 14