Overview: The document is a technical leaflet for TTAET Dry Type Transformers, specifically designed for outdoor use in expressway and railway applications. These transformers are available in power ratings of 50, 125, and 160 kVA and are compliant with NFC 52 410 standards.
Specifications:
  • Primary Voltage: 5500 V with an insulation level of 7.2 kV.
  • Secondary No-load Voltage: 410 V with an insulation level of 1.1 kV.
  • Coupling: Dyn 11.
  • Dielectric: Dry type cast resin.
  • Protection Degree: Water-proof treated coils, capable of withstanding short-term water leakage.
Operating Conditions:
  • Water splash protection from all directions with a cover rated at IP25.
  • MV Input: Three-phase terminal with a maximum current of 80 A and cable diameter of 44.5 mm.
  • H.V. Protection: Includes 3 HPC fuses with a breaking capacity of 15 kA.
  • L.V. Output: 4-core single-phase cable with varying cross-sections depending on power rating.
  • L.V. Protection: No direct protection but includes thermal probes for thermal protection.
Dielectric Test:
  • Impulse withstand: 60 kV wave 1/50.
  • Power frequency withstand: 22 kV-50 Hz for 1 minute.
Technical Data:
  • Power Output: 40, 100, and 128 kVA for 50, 125, and 160 kVA transformers respectively.
  • Iron Loss: 300, 520, and 750 W.
  • Copper Loss: 1100, 1550, and 2200 W.
  • Impedance S.C.: 4% for 50 and 125 kVA, 4.5% for 160 kVA.
  • Vector Group: Dyn11 for all models.
Additional Information: The document includes details on the supply of MV terminals, un-sealed plugs, and a terminal assembly instruction manual. The manufacturer reserves the right to modify models without prior notice.
Contact Information: Distributed by AUGIER SA, located in Carros Cedex, France. Contact details include phone and fax numbers, as well as an email address and website.
See more

Catalog excerpts

TTAET Transformer for tunnels-1

Technical leaflet TTAET Dry type Transformers

 Open the catalog to page 1
TTAET Transformer for tunnels-2

TTAET - 50, 125, 160 kVA Type Outdoor three-phase transformer for three-phase network, casted in resin,specially treated against corrosion. It is specially designed for expressway and railway. Protection degree: transformer coils are water-proof treated, it can withstand water leakage for short period. Primary Voltage : 5500 V (1) Primary winding insulation level : 7,2 kV Secondary no-load voltage : 410 V (2) Secondary winding insulation level : 1,1 kV Coupling : Dyn 11 Dielectric : Dry type cast resin Power rating : 50 - 125 - 160 kVA Nominal power according to standard for public lighting :...

 Open the catalog to page 2
TTAET Transformer for tunnels-3

TTAET Technical Data- SO, 125, 1611 kVA Vector group - Magnetic current (%) DYnll Dynll Dynll

 Open the catalog to page 3
TTAET Transformer for tunnels-4

Dans un souci d'améliorations constantes, le fabricant se réserve le droit de modifier ses modèles sans préavis.

 Open the catalog to page 4

All Augier catalogs and technical brochures

  1. TED TRANSFORMER

    28  Pages

  2. TER TRANSFORMER

    24  Pages

  3. DIAM 4100

    8  Pages

  4. Switch Over

    8  Pages

  5. Marklight

    8  Pages

  6. Sub-stations

    24  Pages

  7. DIAM 3100

    8  Pages

  8. DIAM 4000

    4  Pages

  9. MHV dimmer

    4  Pages

  10. COMPACTO

    12  Pages

  11. OPTIMOFLUX

    8  Pages

  12. Modulobloc

    20  Pages

  13. Augier-Box

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.