Product Overview: This document is a product leaflet for dry type transformers, including single-phase, three-single, three-two, and three-phase transformers, with voltage classes ranging from 1.1 kV to 7.2 kV. These transformers are designed for installation in dry, air-conditioned rooms or PTI AUGIER type substations.
Electrical Characteristics:
  • Power Ratings: Single-phase (5-50 kVA), Three-single and Three-two (16-160 kVA), Three-phase (16-630 kVA).
  • Insulation Voltage: 1.1 kV, 3.6 kV, 7.2 kV.
  • Primary and Secondary Voltages: Standard voltages include 230 V, 400 V, 950 V, 3200 V, 5500 V, and 6600 V.
  • Couplings: Standard and specific couplings available, including step-down Dyn11 and step-up YNd1.
Construction and Design:
  • Magnetic circuits made from low-loss crystal sheet metal.
  • Copper or aluminum windings with fungicide varnish impregnation.
  • Cooling via natural air (NA).
  • Designed for use in temperatures ranging from -15°C to +40°C.
Standards and Testing: Conforms to NFC 17200, NFC 52100, and CEI 76 standards. Routine and specific tests are conducted on each transformer.
Accessories and Options:
  • Standard accessories include voltage tapping, earthing terminals, lifting lugs, and rollers for higher power ratings.
  • Optional accessories include painted enclosures, HRC fuses, thermal protection, and tap changers.
Size and Weight: Detailed dimensions and weights are provided for both IP00 frame and IP21 enclosure presentations, varying by power rating.
Notes: Transformers are not reversible, and step-up transformers are designed to limit inrush currents. The manufacturer reserves the right to alter information without prior notice.
See more

Catalog excerpts

Dry transformer-1

PRODUCT LEAFLET DRY TYPE TRANSFORMER Single-phase, three-single, three-two and three-phase transformers 1.1 kV to 7.2 kV classes

 Open the catalog to page 1
Dry transformer-2

Dry Type Transformers Transformers meant to be installed in a dry and air conditioned room or in a PTI AUGIER type substation. ELECTRICAL CHARACTERISTICS : Power rating and type : Single-phase : TMAI : 5 - 7.5 - 10 - 16 - 25 - 32 - 50 kVA Three-single : TTMAI : 16 - 25 - 32 - 50 - 63 - 80 - 100 - 125 - 160 kVA Three-two : TTBAI : 16 - 25 - 32 - 50 - 63 - 80 - 100 - 125 - 160 kVA Three-phase : TTAI : 16 - 25 - 32 - 50 - 63 - 80 - 100 - 125 - 160 - 200 250 - 400 - 500 - 630 kVA Insulation voltage : 1.1 kV - 3.6 kV - 7.2 kV Primary voltage : Every voltage compatible with insulation voltages above....

 Open the catalog to page 2
Dry transformer-3

CONSTRUCTION : Magnetical circuits with crystal made sheet metal, oriented, with low losses. Copper or aluminium windings, impregnated vacuum with a fungicide varnish, class H impregnation. Metallic flanges. Ironed chassis with rollers. Wooden terminals plate bakelised. Cooling Use Color : in natural air : NA. : use in dry, air conditioned rooms, at a room temperature of -15 °C ; + 40°C. : RAL 7035 gray. STANDARDS AND TESTS : Conforms to NFC 17200 - NFC 52100 - CEI 76 standards. Other specifications on request. Routine tests U.T.E made on each transformer, specific tests on request.. Dry type...

 Open the catalog to page 3
Dry transformer-4

Three-phase dry Type Transformers TTAI ELECTRICAL CHARACTERISTICS : Power rating: 16 - 25 - 32 - 50 - 63 - 80 - 100 - 125 - 160 - 200 - 250 - 400 - 500 - 630 kVA Insulation voltage : 1.1 kV - 3.6 kV - 7.2 kV Primary voltage : Every voltage compatible with insulation voltages above. Usually standard voltages are : 230 V - 400 V - 950 V - 3200 V - 5500 V and 6600 V. Secondary load voltage : 400 V - 950 V - 3200 V - 5500 V and 6600 V. Couplings : Step-down Dyn11 - Step-up YNd1, other couplings on request. CONNEXION : Primary and secondary connexions on copper plates, by the upper side of the transformer....

 Open the catalog to page 4
Dry transformer-5

TTAI Dry Transformers SIZES-WEIGHT (mm) - PRESENTATION ON IP00 FRAME - STEP DOWN TRANSFORMER Power rating (kVA) SIZES-WEIGHT (mm) - PRESENTATION WITH IP21 ENCLOSURE - STEP DOWN TRANSFORMER Power rating (kVA)

 Open the catalog to page 5
Dry transformer-6

Single-phase Dry Type Transformers TMAI ELECTRICAL CHARACTERISTICS : Power rating: 5 - 7,5 - 10 - 16 - 25 - 32 - 50 kVA Insulation voltage : 1.1 kV - 3.6 kV - 7.2 kV Primary voltage : Every voltage compatible with insulation voltages above. Usually standard voltages are : 230 V - 400 V - 950 V - 3200 V. Secondary load voltage : 230 V - 950 V - 3200 V. Couplings : Standard : single-phase transformer : Ii0 CONNEXION : Primary and secondary connexions on copper plates, by the upper side of the transformer. STANDARD ACCESSORIES : Voltage tapping adjustable out of voltage : +/- 2,5 % ou +- 5% sorties...

 Open the catalog to page 6
Dry transformer-7

TMAI Dry Transformers SIZES-WEIGHT (mm) - PRESENTATION ON IP00 FRAME Power rating (kVA) SIZES-WEIGHT (mm) - PRESENTATION WITH IP21 ENCLOSURE Power rating(kVA)

 Open the catalog to page 7
Dry transformer-8

A WORLD OF ENERGY UNDER CONTROL UN MONDE D'ENERGIE MAITRISEE

 Open the catalog to page 8

All Augier catalogs and technical brochures

  1. TED TRANSFORMER

    28  Pages

  2. TER TRANSFORMER

    24  Pages

  3. DIAM 4100

    8  Pages

  4. Switch Over

    8  Pages

  5. Marklight

    8  Pages

  6. Sub-stations

    24  Pages

  7. DIAM 3100

    8  Pages

  8. DIAM 4000

    4  Pages

  9. MHV dimmer

    4  Pages

  10. COMPACTO

    12  Pages

  11. OPTIMOFLUX

    8  Pages

  12. Modulobloc

    20  Pages

  13. Augier-Box

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.