Specifications:
  • Expansion Capability: The MP02 unit can be expanded with up to 2 I/O modules via a side connector and RS485 ports using Modbus I/O modules.
  • Digital Expansion Units: Options include MPD10808, MPD11616, MPD20808, and MPD40808, each with varying input/output configurations.
  • Inputs: The device supports 6 analogue inputs with various voltage and current ranges, 2 universal analogue inputs, and up to 40 digital inputs with expansion.
  • Outputs: It offers up to 4 analogue outputs and 40 digital outputs with expansion, featuring protection against reverse polarity and short circuits.
  • Functional Features: Equipped with an ARM 32-bit processor, 16 MB RAM, and supports multiple programming languages compliant with IEC61131-3 standards.
  • General Characteristics: Operates on a 24 Vdc power supply, with dimensions of 152 x 110 mm and a weight of approximately 460 g. It is designed for DIN rail mounting with an IP20 protection rating.
Procedures and Recommendations:
  • Ordering Information: The document provides a guide on composing part numbers based on various options for inputs, outputs, communication ports, and accessories.
  • Accessories: Includes cables, power adaptors, filters, and plugs, with specific part numbers for ordering.
Key Data from Diagrams: The document includes dimensional diagrams with measurements in millimeters, illustrating the physical layout of the MP02 unit.
See more

Catalog excerpts

MP02-1

• COMPACT PROGRAMMABLE CONTROLLER (MICROPAC) + ON BOARD I/O AND EXPANSION CAPABILITY • 8 A/I + 8 D/I • 4 A/O + 8 D/O FEATURES INPUTS MP02 6x 0...10V, 0/1...5V, 0...1V - 0/4...20mA Resolution: 16 bit Accuracy: 0.1% of span Input impedance >100kΩ (V); 300Ω (mA) Insulation 800 V between power supply and logic ±15 mV, ± 35mV, ±50 mV, ±100 mV, ±300 mV, ±1.25 V, TC (L, J, T, K, S, R, N), Pt100, Pt1000 and potentiometer (0.1... 10kΩ) Resolution: 16 bit Accuracy: 0.1% of span Input impedance >10 MΩ (V) Insulation 800 V between power supply and logic 40 Vpp between the channels (differential inputs) 8 + 32 (with expansion units) 24 Vdc (ON: 5...30V, OFF: 0..3V) or 8 + 8/16 max. 120 Vac Counter input 80 Hz max. frequency Sink type Protection: Reverse polarity and overvoltage Insulation 800 V between power supply and logic 8+32 Digital FUNCTIONAL Processor Memory Programming languages Standard Real time clock Execution cycle Minimum time Serial ports Protocols GENERAL Power supply Power consumption Dimensions / Weight Mounting Front protection degree Operating / storage temperature Operating humidity ±10 V (±25 mA max.), 0/4... 20 mA Resolution: 13 bit Accuracy: 0.1% of span Insulation 800 V between power supply and logic 8 + 32 (with expansion units) 24Vdc, 0.5 A or 8 + 8/16 relays (2A, 240 Vac, NA) Source type (PNP) Protection: Reverse polarity and short circuit Insulation 800V between channels and power supply ARM 32 bit 16 MB of RAM system, application memory max. 2 MB internal, 64 kB redundant FLASH memory IL, ST, FBD, LD, SFC, CFC IEC61131-3 on board ≥5ms (10ms tipical) Ethernet + RS485 + RS232/485 Modbus RTU (Master/Slave), Modbus TCP Server, ASCII 24 Vdc (-15... +25%) / 50/60 Hz 13 VA (+3.5 VA with both expansion units) 152 x 110 mm, depth 66 mm / 460 g approx. On OMEGA DIN A rail IP 20 0… 50°C (32… 122°F) / -40…+70°C (-40… 158°F) 5… 95 RH% without condensation Note: MP02 unit can be expanded up to 2 I/O modules through the side connector and via one of the RS485 ports by using the Modbus I/O modules. Digital expansion units: MPD10808 (8 inputs 24 Vdc + 8 outputs 24 Vdc, 0.5A) MPD11616 (16 inputs 24 Vdc + 16 outputs 24 Vdc, 0.5A) MPD20808 (8inputs 24 Vdc + 8 relays outputs 2A) MPD40808 (8 inputs

 Open the catalog to page 1
MP02-2

INDUSTRIAL CONTROLLERS ADVANCED PROGRAMMER CONTROLLERS internet cloud CELL PHONES THERMOSTATS ANALOGUE CONTROLLERS REMOTE SUPERVISOR PREPROGRAMMED SYSTEMS RS232 CABLE 2M, CONFIG. CU, PC-DB9F/CU-RJ45 ETHERNET CABLE 2M, PROGRAMM. CU, PC-RJ45/CU-RJ45 POWER ADAPTOR 3.2 A POWER ADAPTOR 5 A FERRITES + FILTERS PLUG WITH 11 POLE CLAMP TERMINALS PLUG WITH 14 POLE SCREW TERMINALS PLUG WITH 11 POLE CLAMP TERMINALS PLUG WITH 14 POLE SCREW TERMINALS TIMERS COUNTERS POWER LIMITERS COMBUSTION CONTROL SPECIAL CONTROLLERS AND “CUSTOM” To compose the part number, pls. choose one of the option for each variable...

 Open the catalog to page 2

All ASCON TECNOLOGIC catalogs and technical brochures

  1. NP4

    2  Pages

  2. KR1E

    4  Pages

  3. at on cloud

    8  Pages

  4. TCPDE M

    2  Pages

  5. opmt

    2  Pages

  6. IO-CB series

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.