Product catalog summary
Overview: The document provides technical specifications for a converter designed to adapt various standard signals and supply voltage for two-wire transmitters. It is housed in a plastic casing suitable for mounting on a 35 mm standard rail according to EN50022.
Specifications:
  • Input: Customer-specific presetting required, with a supply voltage of approximately 18 Vdc, non-stabilized.
  • Output: Provides both a voltage output of 0...10 V and a current signal of 0/4...20 mA, with a common negative pole.
  • Supply Voltage Options: 230/115 Vac, 24 Vac, or 24 Vdc.
  • Connections: Screw terminals up to 2.5 mm².
  • Dimensions: 22.5 x 99 x 110 mm (W x H x D).
  • Protection Class: IP 20 according to EN 60529.
  • Ambient Conditions: Operating temperature from -10 to 50 °C, relative humidity 0 ... 85%, no condensation.
  • Weight: Approximately 160 g.
Technical Specifications:
  • Measurement Mode: Adjustable via trimmer, ranges include 0 / 0.2 ... 1V, 0/2 ... 10V, 0/4 ... 20mA.
  • Operating Indicator: Green for normal operation, red for overdrive or sensor break.
  • Accuracy/Error Limit: Tolerance of ± 0.2%, temperature drift of ± 0.2% / 10 K.
  • Power Supply: Options include 230 Vac / 115 Vac via input transformer, 24 Vac, or 24 Vdc.
  • Power Consumption: Approximately 1.5 VA.
  • Voltage Output: 0 ... 10 V, short circuit proof, max. 5 mA.
  • Current Output: 0/4 ... 20 mA, max. load 600 Ω.
  • Test Sockets: 2 mm ø for measuring output current, internal resistance max. 10 Ω.
Conformity:
  • EMC: Complies with EN 61000-6-2, EN 61000-6-3, CE-marked.
  • RoHS: In accordance with RoHS-directive 2011/65/EU.
See more

Catalog excerpts

Supply unit and supply converter ST225-1

SUPPY UNIT and SUPPLY CONVERTER ST225 Converter to adapt various standard signals Supply voltage for two-wire transmitter Plastic housing for mounting on 35 mm standard mounting rail according to EN50022 For conversion of standard signals. Incorporated supply voltage for supply of a two-wire measuring transmitter. Output signals are both a voltage 0...10 V and a current signal 0/4...20 mA. Both output signals are related to their common negative pole. ACCURACY / ERROR LIMIT: Tolerance: ± 0,2 % Temperature drift: ± 0,2 % / 10 K Operating Mode: Entrance: Supply voltage: Settings: TECHNICAL SPECIFICATIONS: Measurement mode 0 / 0.2 ... 1V, 0/2 ... 10V, 0/4 ... 20mA Approx. 18 Vdc, unstabilized, max. 25 mA Measuring range adjustable via trimmer PHYSICAL: Display: Operating indicator green, overdrive or sensor break red Casing: Polyamide gray, for mounting on a 35 mm standard profile rail according to EN 50022 Dimensions: 22.5 x 99 x 110 mm (W x H x D) Protection class: IP 20 according to EN 60529 Connections: Screw terminals up to 2.5 mm² Ambient temperature: -10 to 50 ° C Rel. humidity: 0 ... 85%, no condensation Weight: Approx. 160 g ELECTRONIC: Power supply: 230 Vac / 115 Vac via input. Transformer or 24 Vac or 24 Vdc Power consumption: Approx. 1.5 VA Test sockets: 2 mm ø for measuring the output current, internal resistance of the current meter max. 10 Ω Voltage output: 0 ... 10 V, short circuit proof, max. 5 mA Current output: 0/4 ... 20 mA, max. Load 600 Ω Max. Output current: Approx. 25 mA for overdrive or sensor break, indicated by red LED CONFORMITY: EMC: EN 61000-6-2, EN 61000-6-3, CE-mark RoHS: according RoHS-directive 2011/65/EU Item no. Supply unit and supply converter ST225 Input: Customer-specific presetting required! Supply voltage: approx. 18 Vdc, non-stabilized Output: 0...10 V and 0/4...20 mA Supply voltage: 230/115 Vac, 24 Vac or 24 Vdc Arthur Grillo GmbH • Am Sandbach 7 • 40878 Ratingen • phone 0 21 02 - 47 10 22 • fax 0 21 02 - 47 58 82 www.grillo-messgeraete.de/en • Email: [email protected] • web shop: www.se

 Open the catalog to page 1

All Arthur Grillo GmbH catalogs and technical brochures

  1. SPECIAL

    18  Pages

  2. TEMPERATURE

    20  Pages

  3. Display

    14  Pages

  4. HUMIDITY

    21  Pages

  5. PRESSURE

    35  Pages

  6. WR 200-F

    2  Pages

  7. SHT11/15

    1  Page

  8. Orifice plate

    3  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.