data sheet Peritact2000

data sheet Peritact2000

data sheet Peritact2000

Product catalog summary
Overview: The document provides detailed technical specifications and features of the Peritact 2000 series low pressure transmitters by Arthur Grillo GmbH. These devices are designed for measuring pressure, under pressure, or differential pressure of non-aggressive gases, with applications in air flow measurement.
Performance: The devices offer a performance range up to 10 times the measuring range with a maximum pressure of 0.2 bar.
Technical Specifications:
  • Measuring Mode: Suitable for air or non-aggressive gases using a diaphragm measuring system.
  • Measuring Range: Various ranges from 0...50 Pa to 0...10000 Pa, with customer-specific presetting available.
  • Temperature Range: Operating temperature from -10 to +50 °C and storage temperature from -25 to +60 °C.
  • Output: Analogue output options include 0...10 V and 0/4...20 mA, with supply voltage options of 230 Vac, 24 Vac, or 24 Vdc.
  • Display: Digital LCD display with 3 1/2 digits or illuminated LCD with 4 lines of 20 characters.
  • Protection Class: IP65 according to EN 60529.
Accuracy and Error Limits: The devices have a zero drift of ± 0.75%, a sum of linearity and hysteresis of ± 1% of the measuring range, and temperature drift specifications of ± 0.3% / 10 K for zero point and ± 0.2% / 10 K for the measuring range.
Conformity: The devices conform to EN 61000-6-2, EN 61000-6-3, and the RoHS directive 2011/65/EU.
Accessories and Options: Available accessories include mounting sets, assembly frames, and test certificates. Special measuring ranges are available for a surcharge.
Models: The document details several models including Peritact 2000, Peritact 2000-2L, Peritact 2000-K, and Peritact 2000-K10, each with specific features and output configurations.
See more

Catalog excerpts

data sheet Peritact2000-1

LOW PRESSURE TRANSMITTER PERITACT 2000 □ Diaphragm element □ Smallest measuring range 0...50 Pa □ Digital display 3 1/2 digits □ Analogue output 0...10 V and 4...20 mA □ Supply voltage 230 Vac, 24 Vac or 24 Vdc □ Protection class IP 65 □ Also available as two-wire-transmitter (PERITACT 2000-2L) Manometer with diaphragm element for indication of pressure, under pressure or differential pressure of non aggressive gas. Overload protection: Static pressure: Zero drift: Sum of linearity and hysteresis: Temperature drift zero point: Temperature drift measuring range: Operating mode: Measuring medium: Measuring principle: Measuring unit: Smallest measuring range: Largest measuring range: Measuring range: Date: 13.02.17 PRESSURE Measuring range selection: Damping: Ambient temperature: Storage temperature: Setpoint setting: Contact load: Housing: Dimensions: Weight: Protection class: Display: Scaling: Pressure connections: Power supply: Output: EMC: RoHS: PERFORMANCE: min. up to 10-times the measuring range max. 0.2 bar ACCURACY/ ERROR LIMIT: ± 0.75 % ± 1% of measuring range ± 0.3 % / 10 K ± 0.2 % / 10 K TECHNICAL SPECIFICATIONS: Measuring mode Air or non-aggressive gases diaphragm measuring system Pa 0...50 Pa (0.5 mbar) 0...10000 Pa (60 mbar) 0.50 Pa (0.5 mbar), 0.100 Pa (1 mbar), 0...200 Pa (2 mbar), 0.400 Pa (4 mbar), 0.500 Pa (5 mbar), 0...1000 Pa (10 mbar), 0...2000 Pa (20 mbar), 0.4000 Pa (40 mbar), 0.5000 Pa (50 mbar), 0.6000 Pa (60 mbar), 0.10000 Pa (100 mbar) factory preset adjustable in 3 steps -10 +50 °C Connection diagram -25...+60 °C 2 Setpoint pointer adjustable over the full scale range, per limit value 1 Output relay with potential-free change-over contact 250 Vac, 6A, induction-free load PHYSICALLY: Ultramid/ABS, black / grey 122 x 120 x 85 mm (wxhxd) approx. 900 g lP65 according EN 60529 3 1/2-digit digital LCD display, digit height 13 mm Screw terminals, cable entry: 2 x M16 x 1.5 Hose connections 8 mm 0 ELECTRONIC: 230 Vac, 24 Vac or 24 Vdc 0...10 V and 0...20 mA via DIP switch switchable to 4...20 mA CONFORMITY: EN 61000-6-2, EN 61000-6-3, CE-mark according RoHS-directive 2011/65/EU Low pressure transmitter Peritact 2000 Measurement range & signal output: Customer-specific presetting required! Output: 0...10 V, 0/4...20 mA, supply voltage: 230 Vac, 24 Vac or 24 Vdc 2-wire transmitter Peritact 2000-2L Measurement range: Customer-specific presetting required! Output: 4...20 mA, supply voltage 13...30 Vdc Mounting set with screws, plastic-pressure taps, 2 m plastic hose (7 x 1.5 mm) Assembly frame for panel mounting incl. all mounting hardware Test certificate Special measuring range e.g. -20...0...+80 Pa Arthur Grillo GmbH • Am Sandbach 7 • 40878 Ratingen • phone 0 21 02 - 47 10 22 • fax 0 21 02 - 47 58 82 www.grillo-messgeraete.de/en • Email: [email protected] • web shop: www.sensor-store.de

 Open the catalog to page 1
data sheet Peritact2000-2

□ Diaphragm element □ Smallest measuring range 0...50 Pa □ Backlit LCD display with 4 lines of 20 characters □ Analogue output 0...10 V and 4...20 mA □ 2 switching output signals potential free □ Switching function min. or max. □ Supply voltage 230 Vac, 24 Vac or 24 Vdc □ Protection class IP 65 Manometer with diaphragm element for indication of pressure, under pressure or differential pressure of non aggressive gas. Also for air flow measurement according to the Differential Pressure or dynamic pressure method with square-root characteristic. Overload protection: Static pressure: Zero drift: Sum...

 Open the catalog to page 2
data sheet Peritact2000-3

LOW PRESSURE TRANSMITTER PERITACT 2000-KI0 □ Dynamic micro flow sensor □ Smallest measuring range 0...10 Pa □ Analogue output 0...10 V and 0/4...20 mA □ 2 outputs with change-over contacts 250V, 8A □ Characteristic linear or square-rooted □ LCD-Display with 4 lines of 20 characters □ Contact function min. or max. □ Supply voltage 230 Vac, 24 Vac or 24 Vdc □ Protection class IP 65 Manometer with diaphragm element for indication of pressure, under pressure or differential pressure of non aggressive gas. Thanks to the measuring principle, the device is irrespective of position and has an extremely...

 Open the catalog to page 3

All Arthur Grillo GmbH catalogs and technical brochures

  1. SPECIAL

    18  Pages

  2. TEMPERATURE

    20  Pages

  3. Display

    14  Pages

  4. HUMIDITY

    21  Pages

  5. PRESSURE

    35  Pages

  6. WR 200-F

    2  Pages

  7. SHT11/15

    1  Page

  8. Orifice plate

    3  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.