protection

protection
1 / 24 PagesView full catalog

protection

Product catalog summary
Overview: The document outlines technical specifications and installation guidelines for lightning current and overvoltage arresters used in low-voltage distributions. These devices are crucial for protecting against damage from lightning strikes and overvoltage.
Specifications:
  • Nominal Voltage: 230V AC
  • Maximum Operating Voltage: Up to 275V AC or 350V DC
  • Lightning Impulse Current: 12.5kA to 100kA
  • Nominal Discharge Current: 20kA to 30kA
  • Max Discharge Current: 40kA to 100kA
  • Voltage Protection Level: 0.9kV to 1.5kV
  • Response Time: 25ns to 100ns
  • Protection Degree: IP 20
  • Operating Temperature Range: -40°C to +80°C
Installation and Features:
  • Devices are mounted on a 35 mm DIN rail.
  • Equipped with visual and optional remote fault signaling.
  • Conforms to EN 61643-11 + A11 standards.
Models and Configurations:
  • Available in single-pole and multipolar configurations with remote signaling options.
  • Replacement cartridges available for maintenance.
Compliance: All products are EU RoHS compliant, meeting environmental and safety standards.
Product Categories:
  • ENErpro T3: Surge arresters for low-voltage systems, modular and miniaturized, compliant with EN 61643-11 + A11 T2 standards.
  • soLArpro T2: For photovoltaic systems, compliant with EN 50539-11:2011.
  • DATApro T2+T3: For ISDN telecommunication lines, available with RJ12 or terminal connections.
  • DATApro T3: For Ethernet ports, suitable for CAT.5 or CAT.6 connections.
  • DATApro: For TV or satellite lines, offering first and second-level protection.
  • LEDpro: For LED lighting systems, protecting against overvoltage.
Key Parameters:
  • Nominal Discharge Current: Varies by product, including 3kA, 20kA, and 2.5kA.
  • Voltage Protection Level: 1.2kV to 4.0kV.
  • Response Time: 1ns to 100ns.
Compliance: Products meet European standards EN 61643-11, EN 50539-11:2011, and EN 61643-21.
See more

Catalog excerpts

protection-1

Scaricatori di corrente da fulmine e sovratensione ad alta prestazione da installare nella parte iniziale di distribuzioni a bassa tensione, per prevenire gli effetti derivanti da fenomeni atmosferici. Gli scaricatori sono dotati di: • Segnalazione di guasto visiva • Le versioni [F] hanno i contatti per la segnalazione di guasto a distanza High performance lightning current and overvoltage arresters, to be installed at the start of low-voltage distributions, to prevent overvoltage effects induced during lightning strikes. • Visual fault signalling • [F] versions with contacts for remote fault signalling Articolo Poli Per reti Telesegnalamento Moduli occupati Item Poles For networks Remote signalling Modules 2440 Cartuccia di ricambio - Replacement cartridge

 Open the catalog to page 1
protection-2

I dati sono per singolo polo - Data are for single pole Tensione nominale - Nominal voltage Tensione massima operativa - Maximum operating voltage Corrente impulsiva di fulmine - Lightning impulse current - (10/350 µs) Corrente massima di scarica - Max discharge current - (8/20 µs) Livello di protezione voltaggio - Voltage protection level Tempo di risposta - Response time Corrente susseguente - Following current Corrente nominale di scarica - Nominal discharge current - (8/20 µs) Protezione massima da sovracorrente - Maximun overcurrent protection Protezione massima da sovracorrente (serie)...

 Open the catalog to page 2
protection-3

Scaricatori di corrente da fulmine e sovratensione da installare nella parte iniziale di distribuzioni a bassa tensione, per prevenire gli effetti derivanti da fenomeni atmosferici. Gli scaricatori sono dotati di: • Segnalazione di guasto visiva • Le versioni [F] hanno i contatti per la segnalazione di guasto a distanza Lightning current and overvoltage arresters, to be installed at the start of low-voltage distributions, to prevent overvoltage effects induced during lightning strikes. • Visual fault signalling • [F] versions with contacts for remote fault signalling Articolo Poli Per reti Telesegnalamento...

 Open the catalog to page 3
protection-4

I dati sono per singolo polo - Data are for single pole Tensione massima operativa - Maximum operating voltage Corrente impulsiva di fulmine - Lightning impulse current - (10/350 µs) Tensione nominale - Nominal voltage Corrente nominale di scarica - Nominal discharge current - (8/20 µs) Corrente massima di scarica - Max discharge current - (8/20 µs) Livello di protezione voltaggio - Voltage protection level Tempo di risposta - Response time Corrente susseguente - Following current Corto circuito con protezione massima - Short-circuit with maximum protection Protezione massima da sovracorrente...

 Open the catalog to page 4
protection-5

Scaricatori di corrente da fulmine e sovratensione da installare nella parte iniziale di distribuzioni a bassa tensione, per prevenire gli effetti derivanti da fenomeni atmosferici. Gli scaricatori sono dotati di: • Segnalazione di guasto visiva • Le versioni [F] hanno i contatti per la segnalazione di guasto a distanza Lightning current and overvoltage arresters, to be installed at the start of low-voltage distributions, to prevent overvoltage effects induced during lightning strikes. • Visual fault signalling • [F] versions with contacts for remote fault signalling Articolo Poli Per reti Telesegnalamento...

 Open the catalog to page 5
protection-6

I dati sono per singolo polo - Data are for single pole Tensione massima operativa - Maximum operating voltage Corrente impulsiva di fulmine - Lightning impulse current - (10/350 µs) Tensione nominale - Nominal voltage Corrente nominale di scarica - Nominal discharge current - (8/20 µs) Corrente massima di scarica - Max discharge current - (8/20 µs) Livello di protezione voltaggio - Voltage protection level Tempo di risposta - Response time Corrente susseguente - Following current Corto circuito con protezione massima - Short-circuit with maximum protection Protezione massima da sovracorrente...

 Open the catalog to page 6
protection-7

Scaricatori di sovratensione unipolari, da installare in quadri secondari di distribuzione a bassa tensione, per prevenire gli effetti derivanti da fenomeni atmosferici. Gli scaricatori sono dotati di: • Segnalazione di guasto visiva • Le versioni (F) hanno i contatti per la segnalazione di guasto a distanza Unipolar overvoltage arresters, to be installed on secondary panel boards of low-voltage distributions, to prevent overvoltage effects induced during lightning strikes. SPD are provided with: • Visual fault signalling • (F) versions with contacts for remote fault signalling Articolo Item...

 Open the catalog to page 7
protection-8

I dati sono per singolo polo - Data are for single pole Tensione nominale - Nominal voltage Tensione massima operativa - Maximum operating voltage Corrente nominale di scarica - Nominal discharge current - (8/20 µs) Corrente massima di scarica - Max discharge current - (8/20 µs) Livello di protezione voltaggio - Voltage protection level - @ I=5 kA (8/20 µs) Livello di protezione voltaggio - Voltage protection level Tempo di risposta - Response time Corrente susseguente - Following current Corto circuito con protezione massima - Short-circuit with maximum protection Protezione massima da sovracorrente...

 Open the catalog to page 8
protection-9

ENERpro T2 Scaricatori di sovratensione multipolari a varistori, da installare in quadri secondari di distribuzione a bassa tensione, per prevenire gli effetti derivanti da fenomeni atmosferici. Gli scaricatori sono dotati di: • Segnalazione di guasto visiva • Le versioni (F) hanno i contatti per la segnalazione di guasto a distanza Multipolar varistors overvoltage arresters, to be installed on secondary panel boards of low-voltage distributions, to prevent overvoltage effects induced during lightning strikes. SPD are provided with: • Visual fault signalling • (F) versions with contacts for remote...

 Open the catalog to page 9
protection-10

I dati sono per singolo polo - Data are for single pole Tensione nominale - Nominal voltage Tensione massima operativa - Maximum operating voltage Corrente nominale di scarica - Nominal discharge current - (8/20 µs) Corrente massima di scarica - Max discharge current - (8/20 µs) Livello di protezione voltaggio - Voltage protection level - @ I=5 kA (8/20 µs) Livello di protezione voltaggio - Voltage protection level Tempo di risposta - Response time Corrente susseguente - Following current Corto circuito con protezione massima - Short-circuit with maximum protection Protezione massima da sovracorrente...

 Open the catalog to page 10
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.