Product catalog summary
Overview: This document provides detailed instructions for the installation of pit frames for dock levellers, specifically focusing on the Frame Fixing 8 (F8) model. It includes specifications, installation procedures, and recommendations for ensuring proper setup and maintenance.
Specifications:
  • Dock leveller dimensions are provided in millimeters, including length (Le), width (Wd), construction height (h), and diagonal (d).
  • Types of pit configurations include Type A (Closed Pit), Type B (Open Pit), and Type C (Pit with compartment for unloading lip’s passing).
  • The permissible tolerance for pit dimensions is ±10 mm, and measurements must be set at right angles.
Installation Procedures:
  • The pit frame is constructed from steel profiles (80x80x8) and must be positioned and fixed into dedicated pits.
  • Reinforcement steels are used to secure the frame, with specifications for materials and dimensions provided.
  • The frame must be plumb, level, and installed at a 90˚ angle, then welded or anchored to the cement or chain-link fence.
Forces Acting on the System:
  • Various forces such as front wheel force (F1), moving lift truck force (F2), and vertical/horizontal forces in hinges and cylinders (F3-F7) are outlined for consideration in reinforced concrete planning.
Recommendations:
  • Type B pit is recommended for easier maintenance access.
  • The cable passing tube should be positioned to allow the worker to observe all dock leveller movements.
  • Ensure the frame ends frontally with the loading bay to avoid inclusion issues.
Warnings:
  • In cases of existing dock levellers with hollow passing, the standard cable length of 7.5 m may be insufficient.
  • Position the cable passing tube on the fuse box side to ensure visibility of dock leveller movements.
See more

Catalog excerpts

Dock levellers - Frame fixing 8-1

Frame fixing 8 FRAME_F8 INSTALLATION PIT EDGE FIXING F8 Qjjj (+39)-011. 71760.19 ■ytfU'U http://www.arnioweb.com

 Open the catalog to page 1
Dock levellers - Frame fixing 8-2

Frame fixing 8 TYPE - Measures in mm In frontal section the tip can have a shape at choice between the types A, B and C as listed below: The Type B pit is the one we suggest you because enables the access under the dock leveller, in order to perform ordinary and/or extraordinary maintenance. NB - The permissible tolerance on the length and width’s quotes of the pit is ± 10 mm. We remind you that the mentioned measures must be set at right angles to each other.

 Open the catalog to page 2
Dock levellers - Frame fixing 8-3

Frame fixing 8 Pit frame - scheme of the forcesacting The building works are never made by us. So, hereafter, we show you the forcesacting on the system; they must be used in the reinforced concrete’s planning. Front wheel force Moving lift truck on closed dock leveller force Horizontal force in the hinge with under braking cart Vertical force in the hinge Horizontal force in the cylinder Vertical force in the cylinder Vertical force on the back side of the fram Pit frame - frontal section WARNING: The cable passing tube 08O shall be placed on the fuse box side. The position shown in the adjacent...

 Open the catalog to page 3
Dock levellers - Frame fixing 8-4

Frame fixing 8 PIT FRAME INSTALLATION The first operation consists in the installation of the pit frames, which are special frames made of steel, suitable for the following fitting of the dock levellers. This frame is made by profiles 80x80x8, already tailor-made cut and welded, to be positioned and fixed into the dedicated pits of the cements loading bays. Pit frame - detail The pit frame is composed by angle bar, plate and reinforcement steel Below is shown, as example, the table with the measurements for a frame suitable for a 2C dock leveller. fa. WARNING! The angle bars are positioned before...

 Open the catalog to page 4
Dock levellers - Frame fixing 8-5

The reinforcement steels can be made of folded, tubular metal sheets, “16” steel round components with a distance between them ranging from 300 and 350 mm.

 Open the catalog to page 5
Dock levellers - Frame fixing 8-6

Frame fixing 8 The frame has to be plumb and level, installed at 90˚ by its diagonal beams and has to be placed already assembled. It must be then welded and/or anchored to the round elements soaked in the cement or to the chainlink fence. The frame frontally MUST end with the loading bay frontal to avoid problems of dock leveller’s inclusion. This is the smallest frame (at dimensional level) required as surface to install a dock leveller. Optionally, you can also choose bigger dimensions (ex. angle bar 80x120mm) or you can use formworks to prepare the pit. Calculations relating the cement’s...

 Open the catalog to page 6