µCv 10

µCv 10

µCv 10

Product catalog summary
Specifications:
The document describes a programmable signal conditioner, the µCv 10, which features a universal power supply (20 to 250 Vac and 20 to 250 Vdc) and universal input options including various voltage, current, and sensor types. It has a typical response time of 300ms and provides isolated analog outputs and relay outputs. The device supports digital communications via isolated RS485 Modbus/Jbus and includes features like sensor break detection, self-diagnosis, and mode simulation for configuration validation.
Programming:
Programming can be done using a micro-console with a graphical rear-lit LCD and tactile keyboard or via PC software SlimSET through a USB/µUSB cable. The micro-console displays measured values, analog output values, product tag names, and the status of relay outputs and RS485 communications. The SlimSET software allows for configuration storage, modification, duplication, and loading into converters, as well as file edition and printing.
Inputs and Outputs:
The µCv 10 supports a wide range of inputs including mA, mV, V, thermocouples, Pt100, Ni 100 sensors, resistive sensors, and potentiometers. It offers isolated analog outputs (current or voltage) and relay outputs with configurable setpoints, hysteresis, and time delay. The device ensures galvanic isolation between supply, input, analog output, relay output, and RS485.
Compliance and Safety:
The device complies with various standards including UL 61010-1, CSA C22.2 NO.61010-1-12, EN 61010-1, and ATEX 2014/34/UE. It is designed for installation in environments with pollution degree 2 and voltage surge category II, and features a self-extinguishing case with IP20 protection.
Physical and Environmental Characteristics:
The µCv 10 is designed for mounting in a switchbox with a latching mechanism on a symmetrical DIN rail. It operates within a temperature range of -20 to +60°C and can be stored between -20 to +70°C. The device has a power draw of 2.8 W max. and a dielectric withstanding of 3.0 kV-50Hz-1min.
See more

Catalog excerpts

µCv 10-1

PROGRAMMABLE SIGNAL CONDITIONERS uCv 10 Features Universal power supply: 20 to 250 Vac and 20 to 250 Vdc Universal input: 100mV, 1V, 10V, 270V, 20mA, Pt100, Ni 100 (2, 3 or 4wire), APt100 thermocouple, resistance and potentiometer Typical response time: 300ms Supply for 2-wire sensor Isolated analog output(s) (A/2A) 0-4-20mA current (active/passive) or 0-10V voltage. Relay outputs (R): 2 or 4 change-over relays (8A/250 VAC on resistive load). Digital communications (N) isolated RS485 Modbus/Jbus Sensor break detection and selfdiagnosis. Isolation input / outputs / supply. Mode simulation allowing to validate the configuration or the installation. Programming either with microconsole or by the PC software SlimSET via a standard USB/yUSB cable. Configuration Easy programming on front face with a micro-console or with the PC software SlimSET (via a standard USB/pUSB cable). Programming with the Micro-console The graphical rear-lit LCD with tactile keyboard allows to visualise the following information: - the measured value with its unit, - the value of the analog output, - the product tag name, - the status of the relay outputs and the RS485 communications. • Scrolling message for programming help in various languages • Passcode protected programming Programming by PC : SlimSET Programming software (Windows environment) allowing: The storage of the configurations as files which can be consulted, modified, duplicated or loaded into the converters. The edition and printing of files with or without having a signal conditioner connected. Dimensions numbering of the terminals: A, B, C, D Process Control Equipment E482453 Coding Type I uCvlQ ARN Available versions: (consult with us for different configurations) Order example: For s signal conditioner with universal input + 1 analog output + 2 relays: reference pCv 10 AR • Standard programming cable USB type A male to pUSB B male: reference C1-pUSB CJC terminal (option): reference B1CSF-4

 Open the catalog to page 1
µCv 10-2

Connectings Types of INPUTS Outputs of the pCv 10 A/AR/2AR 0-4/20mA passive external source 30V max. 0-4/20mA passive external source 30V max. (1) Sensor break detection: mA input (if down scale > 3,5mA) Other inputs: a 12pA pulsed current allows the detection of line or sensor break. (2) Wiring possible in 2, 3 and 4 wire Influence of the line resistance (0<Rl<<25Q) included in the announced intrinsic error. (3) CJC efficiency: Internal CJC: ±2°C ±0.03°C/°C from -10°C to +50°C CJC (option terminal) : ±1°C from -10°C to +50°C MR Measure range Thermal drift <150ppm /°C The voltage or current outputs...

 Open the catalog to page 2

All ARDETEM SFERE catalogs and technical brochures

  1. TPIv10

    2  Pages

  2. EVAN3000

    2  Pages

  3. EVA3000

    2  Pages

  4. TPI 41K

    2  Pages

  5. TAIv60

    2  Pages

  6. Series µCs

    4  Pages

  7. Series TPls

    4  Pages

  8. TPIv 20I

    2  Pages

  9. TPIv 10I

    2  Pages

  10. ATIS H

    2  Pages

  11. TMvL3

    2  Pages

  12. TMvL2

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.