1. Catalogs
  2. ARDETEM SFERE
  3. TM2F-TN2F-com-EN

TM2F-TN2F-com-EN

TM2F-TN2F-com-EN

TM2F-TN2F-com-EN

Product catalog summary
Overview: The document describes a 2-wire isolated programmable transmitter, detailing its specifications, input types, output features, and compliance with standards.
Specifications:
  • Dimensions: 22.5x75x120 mm
  • Operating Temperature: -20° to 60°C
  • Storage Temperature: -30° to 70°C
  • Weight: 200g (with packaging)
  • Material: Self-extinguishing black UL 94VO ABS
Interface and Configuration:
  • Includes a µconsole with a graphical rear-lit LCD and USB 2.0 connection.
  • Configurable via µconsole or PC using SuperVISION / MCvision software.
  • Programming via DIN plug does not disturb the output loop.
Mounting and Connections:
  • Mounting: Latching on symmetrical DIN rail.
  • Plug-off connectors for screwed connections (2.5mm², flexible or rigid).
Input Types:
  • Universal Input (TM2F/TN2F 10): ±100mV, ±1V, ±10V, ±300V, ±20mA, Pt100 3 wire, Ni 100, thermocouples, resistance, and potentiometer.
  • Process Input (TM2F/TN2F 11): ±100mV, ±1V, ±10V, ±300V, ±20mA.
  • Temperature Input (TM2F/TN2F 12): Pt100 3 wire, Ni100, thermocouples.
  • Pt100 Input (TM2F/TN2F 13): Pt100 3 wire.
  • Thermocouple Input (TM2F/TN2F 14): Various thermocouples including J, K, B, R, S, T, E, N, L, W, W3, WRE5.
Output Features:
  • Analog Output: Passive 4-20mA isolated.
  • Detection of sensor break and isolation between input/output.
  • Self-zero and self-diagnosis capabilities.
Performance and Standards:
  • Disturbance immunity: IEC 61000-6-2, IEC 61000-4-3 level 3, IEC 61000-4-4 level 4, IEC 61000-4-6 level 3.
  • Emitted disturbances: EN55011 class A.
  • Vibration withstand: EN60068-2-6 +/-150µm from 10 to 57Hz and +/-2g peak from 57 to 500Hz.
Power Supply and Load:
  • Powered by the output loop.
  • Max Load: LR≤ (Usupply-10)/0.022 in Ω.
Response Time:
  • Input mA/mV/V/resistance: 500ms to 6.5s.
  • Temperature and potentiometer inputs: 700ms to 6.5s.
Additional Features:
  • Galvanic partition: 2.5kV - 50Hz - 1mn between inputs and output.
  • Special linearisation programming up to 20 points.
  • Thermal drift: < 0.015% of the MR /°C.
  • Influence of supply voltage variation: < 0.005% of the EEC /Volt.
See more

Catalog excerpts

TM2F-TN2F-com-EN-1

2-WIRE ISOLATED PROGRAMMABLE TRANSMITTER ARDETEM • Universal input (TM2F/TN2F 10): ±100mV, ±1V, ±10V, ±300V, ±20mA, Pt100 3 wire, Ni 100, thermocouples, resistance and potentiometer. • Process input (TM2F/TN2F 11): ±100mV, ±1V, ±10V, ±300V , ±20mA. • Temperature input (TM2F/TN2F 12): Pt100 3 wire, Ni100, thermocouples • Pt100 input (TM2F/TN2F 13): Pt100 3 wire • Thermocouple input (TM2F/TN2F 14): thermocouples J,K,B,R,S,T,E,N,L,W,W3,WRE5 • Power supply: powered by the output loop • Analog output: passive 4-20mA isolated Detection of the sensor break. Isolation between input / output Self-zero and self-diagnosis Easy programming via the output terminals or via the front face DIN plug using the interface TP2F/yC2F. Self-extinguishing case of black UL 94VO ABS. Mounting in switchbox: latching on symmetrical DIN rail. Rack version: consult Plug-off connectors for screwed connections (2.5mm2, flexible or rigid) Weight: 200g (with packaging) The interface TP2F/|jC2F includes a jconsole with graphical rear-lit LCD, and a USB 2.0 connection. The user can configure the TM2F/TN2F either with the jconsole, or with a PC via the software SuperVISION / MCvision. In the case of a programming via the DIN plug on front face (connected to the tP2F/jC2F), the output loop will not be disturbed. ♦ C€ a; DIN plug for ' connecting the interface TP2F/jC2F ♦ Disturbance immunity according to the standard IEC 61000-6-2 (IEC 61000-4-3 level 3, IEC 61000-4-4 level 4, IEC 61000-4-6 level 3) ♦ Limits of the emitted disturbances according to the standard EN55011 class A ♦ Vibration withstanding according to the standard EN60068-2-6 +/-150jm from 10 to 57Hz and +/-2g peak from 57 to 500Hz

 Open the catalog to page 1
TM2F-TN2F-com-EN-2

(1) Line resistance <25Q (2) Total accuracy = basic accuracy +/- 0.1% EEC. (at 23°C) (3) Other features: consult ± A 12 pA pulsed current allows the detection of line or sensor rupture. * Cut off: the display of the console and the output of the TM2F/TN2F remain at down scale for an input signal < than the cut off value, programmable from 0% to 100% of the input scale. ♦ CJC efficiency: ±0.03°C/°C ±0.5°C MR Measure range EEC Configured scale span e-mail : [email protected] http : //www.ardetem.com Route de Brindas Parc d'activite d'Arbora N°2 69510 SOUCIEU EN JARREST - FRANCE -Tel. : 33 (0)4...

 Open the catalog to page 2

All ARDETEM SFERE catalogs and technical brochures

  1. TPIv10

    2  Pages

  2. µCv 10

    2  Pages

  3. EVAN3000

    2  Pages

  4. EVA3000

    2  Pages

  5. TPI 41K

    2  Pages

  6. TAIv60

    2  Pages

  7. Series µCs

    4  Pages

  8. Series TPls

    4  Pages

  9. TPIv 20I

    2  Pages

  10. TPIv 10I

    2  Pages

  11. ATIS H

    2  Pages

  12. TMvL3

    2  Pages

  13. TMvL2

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.