1. Catalogs
  2. Arcteq Relays Ltd
  3. AQ02 COMBINED ARC FLASH AND PRESSURE POINT SENSOR
video corpo

AQ02 COMBINED ARC FLASH AND PRESSURE POINT SENSOR

AQ02 COMBINED ARC FLASH AND PRESSURE POINT SENSOR

Product catalog summary
Technical Specification Overview
Product: AQ02 Combined Arc Flash and Pressure Point Sensor
Features:
  • Arc light sensing and ambient pressure detection capabilities.
  • Supports up to three sensors in a daisy chain configuration.
  • Designed for easy and quick installation and wiring.
  • Equipped with 100% self-supervision functionality.
  • One sensor is required per compartment.
Specifications:
  • Supply Voltage: 24Vdc
  • Supply Current (Standby): 2mA
  • Light Intensity Thresholds:
    • 8Klux - Ordering Code: AQ02-A
    • 25Klux - Ordering Code: AQ02-B
    • 50Klux - Ordering Code: AQ02-C
  • Pressure Threshold Setting: Fixed at 0.2 bar above ambient pressure
  • Pick Up Time: Less than 1ms
  • Pressure Measuring Accuracy: ±1.8 %FS (full scale)
  • Sensor Cable Specification: Shield twisted pair, Size: 0.5 ~ 0.75mm², AWG: 18 ~ 20, Cable cover: Ø 4.5 ~ 6.0 mm
  • Max. Sensor Cable Length per Sensor Channel: 200 meters
  • Operating Temperature: -20˚C to 85˚C
  • Storage Temperature: -20˚C to 85˚C
  • Mechanical Protection:
    • Photodiode Element: IP60
    • Pressure Element: IP40
  • Mounting: Screw or pop rivet, e.g., Phillips Pan-head sheet metal screw, Diameter: M3, Length: 20mm
  • Dimensions (W x H x D): 90.0 x 27.5 x 32.5 mm
  • Weight: 20 g
Notes:
  • Factory default threshold setting is tested under light wavelength 650nm.
  • Standard atmospheric pressure is 1 bar.
  • Activation time is measured after exceeding the set threshold pressure.
See more

Catalog excerpts

AQ02 COMBINED ARC FLASH AND PRESSURE POINT SENSOR-1

T ECHNICAL SPECIFICATION - AQ02 COMBINED ARC FLASH AND PRESSURE POINT SENSOR • Available with arc light sensing and ambient pressure detection. • Maximum 3 sensors in line (daisy chained) • Easy and quick installation and wiring • 100% self-supervision 1 : Factory default threshold setting is tested under light wave length 650nm. 2 : A standard atmospheric pressure is 1 bar. 3 : Time for activation after exceeding the set threshold pressure.

 Open the catalog to page 1
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.