Technical Specification Overview
Product: AQ02 Combined Arc Flash and Pressure Point Sensor
Features:- Arc light sensing and ambient pressure detection capabilities.
- Supports up to three sensors in a daisy chain configuration.
- Designed for easy and quick installation and wiring.
- Equipped with 100% self-supervision functionality.
- One sensor is required per compartment.
Specifications:- Supply Voltage: 24Vdc
- Supply Current (Standby): 2mA
- Light Intensity Thresholds:
- 8Klux - Ordering Code: AQ02-A
- 25Klux - Ordering Code: AQ02-B
- 50Klux - Ordering Code: AQ02-C
- Pressure Threshold Setting: Fixed at 0.2 bar above ambient pressure
- Pick Up Time: Less than 1ms
- Pressure Measuring Accuracy: ±1.8 %FS (full scale)
- Sensor Cable Specification: Shield twisted pair, Size: 0.5 ~ 0.75mm², AWG: 18 ~ 20, Cable cover: Ø 4.5 ~ 6.0 mm
- Max. Sensor Cable Length per Sensor Channel: 200 meters
- Operating Temperature: -20˚C to 85˚C
- Storage Temperature: -20˚C to 85˚C
- Mechanical Protection:
- Photodiode Element: IP60
- Pressure Element: IP40
- Mounting: Screw or pop rivet, e.g., Phillips Pan-head sheet metal screw, Diameter: M3, Length: 20mm
- Dimensions (W x H x D): 90.0 x 27.5 x 32.5 mm
- Weight: 20 g
Notes:- Factory default threshold setting is tested under light wavelength 650nm.
- Standard atmospheric pressure is 1 bar.
- Activation time is measured after exceeding the set threshold pressure.
See more