936A

936A

Product catalog summary
Overview: The Arbiter Systems Model 936A Reference Current Transformer is designed for high-accuracy laboratory-grade measurements in a portable and rugged case, suitable for field use. It offers selectable current ratios and is ideal for calibrating other current transformers.
Specifications:
  • Accuracy: 0.02% ratio and 0.01° phase, traceable to NIST.
  • Current Ratios: 1200:5, 1000:5, 800:5, 600:5.
  • Input Range: 1 to 1200 Arms.
  • Output: 5 Arms maximum current, 8.5 Vrms maximum voltage.
  • Power Requirements: 85 to 264 Vac, 47 to 440 Hz, 15 VA max; 110 to 250 Vdc, 15 W max.
  • Safety Standards: Designed to meet UL, CSA, VDE standards.
Design and Functionality: The Model 936A uses an active transformer with a dual core toroid and amplifier-aided second stage to maintain high accuracy. It is primarily used with the Model 935A Current Source and Model 931A Power Systems Analyzer for calibrating current transformers.
Physical and Environmental Characteristics:
  • Case Size: 205 x 305 x 225 mm; shipping size 483 x 483 x 483 mm.
  • Weight: 5.8 kg maximum.
  • Operating Temperature: 0° to +40° C; non-operating: -40° to +85° C.
  • Humidity: Noncondensing.
See more

Catalog excerpts

936A-1

SYNCHRONIZED POWER QUALITY/REVENUE STANDARDS Reference Current Transformer The Arbiter Systems®, Inc. Model 936A Reference Current Transformer provides laboratory grade accuracy in a small, portable, ruggedized case, making it ideal for field use. Multiple ratios of 1200:5, 1000:5, 800:5, 600:5 are selectable via a front panel switch. The guaranteed accuracy over the full input range and operating conditions is 0.02% ratio and 0.01° phase (traceable to NIST), ideal for calibrating other current transformers. The Model 936A uses an active transformer to achieve the high accuracy needed for a primary reference. This design incorporates a dual core toroid with an amplifier aided second stage. The active circuitry reduces the sense transformer core flux to zero and produces an accurate output current independent of burden. The Model 936A was designed primarily for use with the Model 935A Current Source and the Model 931A Power Systems Analyzer to calibrate current transformers used with the Model 1133 Power Sentinel. The Model 936A's multiple ratio selections allow other current transformers to be tested and calibrated across their entire operating range. I/O Configuration Input Input Range 1 to 1200 Arms Current Ratios 1200:5, 1000:5, 800:5, 600:5 Output Current Voltage 5 Arms maximum 8.5 Vrms maximum Power Requirements External Power Range 85 to 264 Vac, 47 to 440 Hz, 15 VA max. 110 to 250 Vdc, 15 W maximum Safety Designed to meet UL, CSA, VDE Standard Inlet IEC-320 with fuse and mating cordset. Specify option P01-P10. General Physical Case Size Weight Sense Transformer 205 x 305 x 225 mm (8 x 12 x 8.75 in.) 483 x 483 x 483 mm (16 x 16 x 16 in.), shipping 5.8 kg (12.8 lbs) maximum 55 mm (2.125 in.) ID Nominal Environmental Temperature Operating: 0° to +40° C Nonoperating: -40° to +85° C Humidity Noncondensing Arbiter Systems, Inc. · 1324 Vendels Circle, Suite 121 · Paso Robles, CA 93446 · USA Tel: +1.805.237.3831 · Fax: +1.805.238.5717 · E-mail: [email protected] · Internet: http://www.arbiter.com

 Open the catalog to page 1
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.