IGA TEST T

IGA TEST T

Product catalog summary
Installation Instructions:
The IGA TEST series protectors must be installed in series with the low voltage line, positioned between the power control circuit breaker (ICP) and the residual current device (ID). Installation should occur without power running through the line. Protective coils are to be placed between the lines connected to the residual current breaker and the neutral. The protectors cut off the power supply upon detecting a permanent overvoltage, safeguarding downstream equipment. To restore the main circuit breaker, the protective coils must be reconnected using the RESET buttons, starting from the most external coil.

Compatibility:
IGA TEST protectors can be used alongside ATSUB-D transient overvoltage protectors.

Specifications:
- Nominal Currents: 6, 10, 16, 20, 25, 32, 40, 50, 63 A
- Nominal Voltage: 230 VAC
- Maximum Overvoltage: 400 VAC
- Actuation Voltage: 265 - 280 VAC
- Actuation Time: 8 - 10 s at 275 VAC, 0.1 - 0.2 s at 400 VAC
- Maximum Short-Circuit Current: 6 kA
- Dimensions: 123 x 81 x 65 mm (7 modules DIN 43880)
- MCB Cable Range: 1.5 / 25 mm²
- Coil Cable Range: 1.5 / 2.5 mm² (single-stranded) or 4 mm² (multi-stranded)

Standards and Certification:
The product is certified according to UNE-EN 50550 and UNE-EN 60898 standards.

Product Description:
The IGA TEST series is a three-phase protector against permanent overvoltages, featuring an integrated miniature circuit breaker (MCB) and protective coils.
See more

Catalog excerpts

IGA TEST T-1

DATA SHEET APLICACIONES TECNOLOGICAS IGA TEST series protectors cut off the power supply when they detect a permanent overvoltage (for example, a fault in the neutral), thus protecting the equipment installed downstream. To restore the main circuit breaker, it is necessary to reconnect the protective coils in advance using the RESET buttons. Reclosing will always be carried out from the most external coil to the one closest to the MCB. IGA TEST permanent overvoltage protectors can be used together with ATSUB-D transient overvoltage protectors. The integrated MCB is available for the most usual nominal currents: 6, 10, 16, 20, 25, 32, 40, 50 and 63 A. > INSTALLATION They must be installed in series with the low voltage line, between the power control circuit breaker (ICP) and the residual current device (ID). Installation should be carried out without power running through the line. The protective coils are to be installed between the lines connected to the residual current breaker and the neutral. The protector is formed by protective coils for permanent overvoltage linked to a miniature circuit breaker (MCB). Aplicaciones Tecnologicas S.A. - Parque Tecnologico de Valencia - Nicolas Copernico, 4 - 46980 Paterna (Valencia), Spain T +34 961 318 250 - F +34 961 318 206 - [email protected] - www.at3w.com