Temperature Controller VTR-2

Temperature Controller VTR-2

Temperature Controller VTR-2

Product catalog summary
Product Overview:
The VTR-2 Temperature Controller is designed for use with Pt100 or Pt1000 sensors to monitor and control temperatures in food and biopharma applications. It features a compact design, universal power supply, and an LC display for menu guidance.

Specifications:
  • Housing: ABS for rail mounting, dimensions 22.5 x 111 x 120 mm, IP 20 protection class.
  • Temperature Range: Operating 0...+55 °C, Storage -10...+55 °C, Humidity 0...95% non-condensing.
  • Input: Pt100/Pt1000, 3- or 4-wire, sensor current 500 μA, wire compensation max 100 Ω.
  • Output: Analog 0/4...20 mA or 0...10 V, switching contact max 250 V / 3 A AC.
  • Accuracy: ≤ ±0.1% of measurement range, temperature drift ≤ 0.01%/K.
  • Power Supply: 24...255 V AC/DC, power consumption 2.5 W / 4.5 VA.

Features:
  • Menu guidance with LC display.
  • Settable operating point, hysteresis, and delay.
  • Switching function adjustable between normal and inverting.
  • Analog output options and sensor monitoring.
  • Display in °C or °F.

Functionality Test:
  1. Connect the temperature sensor or simulator and auxiliary power supply.
  2. Set unit parameters via the menu.
  3. Check switching function, hysteresis, and sensor monitoring.

Operation and Adjustment:
  1. Enter 'SET' mode by holding the 'set' button for 5 seconds.
  2. Select and adjust parameters using 'up' and 'down' buttons.
  3. Save changes or exit without saving as needed.

Standards and Guidelines:
  • Complies with Electromagnetic Compatibility Directive 2014/30/EU and Low Voltage Directive 2014/35/EU.
  • Not suitable for explosive areas or security-relevant equipment.

Disposal:
  • Devices must be recycled according to national laws and not disposed of with household trash.
See more

Catalog excerpts

Temperature Controller VTR-2-1

SENSORS FOR FOOD AND BIOPHARMA. Application / Specified usage ■ The temperature controller VTR-2 is used in conjunction with the temperature sensor Pt100 or Pt1000 to easily control and monitor temperatures. Features ■ Menu guidance using LC display ■ Settable operating point, hysteresis and operating delay ■ Switching function "min" / "max" can be toggled ■ Can be connected to PT100 or PT1000 ■ 3 or 4-wire-technology ■ Analog output: 0...10 V or 0/4...20 mA (optional) ■ Sensor monitoring ■ Display of the actual value in either °C or °F,as selected ■ Connection via pluggable terminal blocks ■ Narrow design (22.5mm) ■ Universal power supply 24/20...255 V AC/DC

 Open the catalog to page 1
Temperature Controller VTR-2-2

Electrical Connection | Parameter Functionality test 1. Connect temperature sensor or simulator at input (KL 1 to 4). In doing so, take heed of the 3-wire or 4-wire connection (in accordance wit the software configuration). 2. Connect the auxiliary power supply (KL 9/10). 3. Set unit parameters (e.g. setpoint SP to 100 °C) as described above via the menu. 4. Check the switching function by slowly increasing or decreasing the input signal until the setpoint is reached. 5. Check the required hysteresis and operating delay by altering the input signal. 6. Check the sensor monitoring system by disconnecting...

 Open the catalog to page 2
Temperature Controller VTR-2-3

Advice Measured values are not recorded nor are switch outputs changed while the module is in "SET" mode. Should no further buttons be actuated within approx. 30 seconds, the unit returns automatically to operation mode and any alterations made to the parameters up to this point are discarded. The same occurs when the "SET" mode is exited using the menu point "cancel". The unit then operates with the last previously saved values. Exiting the "SET" mode via the menu point "Reset" restores the parameters to their factory default values. OperationAdjustment 1. Actuate the "set" button for at least...

 Open the catalog to page 3
Temperature Controller VTR-2-4

Product Information VTR-2 Switching diagram T > 0° Function maximum limit switch: temperature > 0° ■ Logic: "Direct" Switching diagram T < 0° Function maximum limit switch: temperature < 0° ■ Logic: "Direct" Hysterese — Hysteresis Sollwert Value — eingestellt set to auf 50 °C 50 °C Relals /Relay EIN/ON-- - Hysterese —► Hysteresis AUS/OFF--Xi i i r Sollwert Value eingestellt set to auf -50 “C -50 °C Function minimum limit switch: temperature > 0° ■ Logic: "Invers" Function minimum limit switch: temperature < 0° ■ Logic: "Invers" Value Sollwert set to eingestellt — 50°C auf 50 "C - Hysterese Hysteresis...

 Open the catalog to page 4
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.