DATA SHEET Economical Effective, low-cost material level detection in a wide variety of applications, and a desirable alternative to electromechanical level switches. No expendable parts to buy and stock. No expensive, extra-cost options. Maintenance-Free Unlike paddle wheels, vibrating tines or other mechanical instruments, there are no components to jam, break or wear out. No need for routine maintenance, cleaning or replacing of worn parts. Reliable Operation Cote-Shield™ circuitry allows the Z-tron IV to ignore coatings or build up on the sensing element. There are no false signals from dust or tunneling. Easy-Installation One-piece unit is easily installed through a single 3/4-inch, probe dependent vessel opening. Calibration is quick and simple. Z-tron IV™ Point Level Switch, a reliable low-cost, on/off level switch The low-cost, Drexelbrook Z-tron IV level switch is unaffected by sticky coatings and impervious to corrosive liquids. The all-electronic design means no moving parts to wear, break or fail. Based on field-proven RF technology, the Z-tron IV is a simple and reliable on/off level switch. The compact one-piece unit is inserted through a standard 3/4-inch , probe dependent, NPT opening into the vessel so that the sensing element is positioned at the desired high or low level. (Other connection types and sizes are also available.) When the material level reaches a predetermined point on the sensing element, it causes a change in status at the electronic unit, resulting in actuation of the DPDT relay. The relay can be used to operate alarms, annunciators, valves, or other control or indication devices. Drexelbrook's Exclusive Cote-Shield™ Cote-Shield enables the Z-tron IV to ignore dust pileups, coatings, and sticky buildups on the sensing element.
Open the catalog to page 1Relay Wiring High Level Fail Safe HLFS Switch Up = High Level Fail Safe HLFS Switch Up = High Level Fail Safe HLFS Switch Up = High Level Fail Safe HLFS Switch Up = High Level Fail Safe Low Level Fail Safe LLFS Switch Down = Low Level Fail Safe LLFS Switch Down = Low Level Fail Safe LLFS Switch Down = Low Level Fail Safe LLFS Switch Down = Low Level Fail Safe
Open the catalog to page 2DEPENDENT UPON SENSING ELEMENT
Open the catalog to page 3Z-tronIV™ Z02X-Series Z-tron IV™ Z02X-Series Remote Mounting Dimensions
Open the catalog to page 4Model Numbering Technology Z4 Z-tron IV RF Admittance Level Measurement System Field Selectable Field Selectable (No Cable) w/ Out Cable w/ 5 Ft Gp Cable w/ 10 Ft Gp Cable w/ 15 Ft Gp Cable w/ 20 Ft Gp Cable 6 Remote 7 Remote 8 Remote 9 Remote A Remote B Remote w/ 25 Ft Gp Cable w/ 35 Ft Gp Cable w/ 50 Ft Gp Cable w/ 75 Ft Gp Cable w/ 100 Ft Gp Cable w/ 150 Ft Gp Cable C Remote D Remote E Remote F Remote G Remote H Remote w/ 5 Ft Hi Temp Cable w/ 10 Ft Hi Temp Cable w/ 15 Ft Hi Temp Comp Cable w/ 20 Ft Hi Temp Comp Cable w/ 25 Ft Hi Temp Comp Cable w/ 50 Ft Hi Temp Comp Cable I Remote J Remote K...
Open the catalog to page 5Power Requirements: AC Units - Field Adjustable: 95-145 VAC, 50/60 Hz, 2 Watt 215-265 VAC, 50/60 Hz, 2 Watt DC Units: 24 VDC Unit: 19-29 VDC input, 2 Watt Sensitivity: 0.3pF or less Operating Point Range: 0 - 80 pF (20 Turn Pot / 4 pF per Turn) Extended range with external pad capacitor, Pad ratio 1:1 Load Resistance: Center to Ground, 1500 Ohms Center to Shield, 750 Ohms Shield to Ground, 750 Ohms Failsafe: Field adjustable to either High-Level Fail-Safe (HLFS) or Low-Level Fail-Safe (LLFS) Output: DPDT relay closure Contact Rating: 5A @ 120 Vac non-inductive 2A @ 230 Vac non-inductive Line...
Open the catalog to page 62 Pages
2 Pages
2 Pages
2 Pages
9 Pages
8 Pages
4 Pages
5 Pages
4 Pages
5 Pages
2 Pages
4 Pages
2 Pages
4 Pages
5 Pages
4 Pages
4 Pages
6 Pages
16 Pages
17 Pages
17 Pages
4 Pages
10 Pages
6 Pages
4 Pages
4 Pages
8 Pages
2 Pages
5 Pages
4 Pages
4 Pages
2 Pages
4 Pages
4 Pages
4 Pages