Product Overview: The document provides technical specifications for the A.C. Voltage Sensor Model S190-108 by American Aerospace Controls Inc. This sensor is designed to measure alternating current (AC) voltage and output a direct current (DC) voltage signal.
Specifications:- Input Voltage Ranges: The sensor is available in different models with varying input voltage ranges: 0-130 Vac, 0-150 Vac, 0-270 Vac, 0-300 Vac, and 0-600 Vac. Each model has a specified overvoltage limit.
- Output Voltage: The sensor outputs a voltage of 0 to 10 Vdc.
- AC Input Current Drain: Maximum of 3mA.
- Output Impedance: Maximum of 10K-Ohms.
- Frequency Range: 47 to 63 Hz.
- Output Ripple: Maximum of 3% Full Scale (F.S.) RMS.
- Accuracy: ±2% F.S.
- Repeatability: ½% F.S.
- Response Time: Maximum of 200 milliseconds.
- Operating Temperature: 0°C to +60°C.
- Storage Temperature: -25°C to +85°C.
- Temperature Coefficient: ±0.05% F.S./°C.
- Weight: 10 oz.
Terminal Identification:- 1. AC INPUT (HI)
- 2. AC INPUT (RTN)
- 3. DC OUTPUT (HI)
- 4. DC OUTPUT (RTN)
Physical Dimensions: Dimensions are provided in inches with specified tolerances.