1. Catalogs
  2. AMBOSO
  3. REMOVAL OF VOLATILE ORGAN COMPOUNDS (VOC) THROUGH FILTRATION, CONCENTRATION AND COMBUSTION WITH REGENERATIVE HEAT RECOVERY

REMOVAL OF VOLATILE ORGAN COMPOUNDS (VOC) THROUGH FILTRATION, CONCENTRATION AND COMBUSTION WITH REGENERATIVE HEAT RECOVERY

REMOVAL OF VOLATILE ORGAN COMPOUNDS (VOC) THROUGH FILTRATION, CONCENTRATION AND COMBUSTION WITH REGENERATIVE HEAT RECOVERY

REMOVAL OF VOLATILE ORGAN COMPOUNDS (VOC) THROUGH FILTRATION, CONCENTRATION AND COMBUSTION WITH REGENERATIVE HEAT RECOVERY

Product catalog summary
Overview: This document outlines the process for removing volatile organic compounds (VOCs) from air emissions at the Sestriere Vernici paint production facility in Nichelino, Italy. The process involves filtration, concentration, and combustion with regenerative heat recovery.
Concentration Section:
  • Air Flow: 15,000 Nm3/h
  • Temperature: Ambient
  • Pollutants: Toluene, Xylene, Acetate, MEK
  • Max Concentration of VOCs: 466 mg/Nm3
  • Max Load of VOCs: 7 kg/h
  • Adsorption Material: Active Carbon
Incinerator Section:
  • Air Flow from Regeneration Phase: 2,000 Nm3/h
  • Inlet Temperature: 80 – 100 °C
  • Operating Hours: 8 hours per day
  • Lowest Combustion Chamber Temperature: 750 °C
  • Minimum Residence Time in Combustion Chamber: 0.6 seconds
Emission Details:
  • Air Flow: 17,000 Nm3/h
  • Temperature: 40 – 45 °C
  • Max Concentration of Total Organic Carbon (TOC): <20 mg/Nm3
  • Max Concentration of CO: <10 mg/Nm3
  • Max Concentration of NOx: <25 mg/Nm3
See more

Catalog excerpts

REMOVAL OF VOLATILE ORGAN COMPOUNDS (VOC) THROUGH FILTRATION, CONCENTRATION AND COMBUSTION WITH REGENERATIVE HEAT RECOVERY-1

REMOVAL OF VOLATILE ORGAN COMPOUNDS (VOC) THROUGH FILTRATION, CONCENTRATION AND COMBUSTION WITH REGENERATIVE HEAT RECOVERY Customer: SESTRIERE VERNICI – stabilimento di Nichelino (TO) - Italy Product sector: paint production CONCENTRATION SECTION Air flow: 15000 Nm3/h Temperature air: ambiente S.O.V. Pollutants: toluol, xilolo, acetate, MEK Max concetration S.O.V.: 466 mg/Nm3 Max load S.O.V.: 7 kg/h Adsorbtion material: active carbon INCENERATOR SECTION Highest air flow to burn originates from rigeneration phase: 2000 Nm3/h Inlet middle temperature: 80 – 100 °C Houres of functionary: 8 hours par day Lowest temperature in combustion chamber: 750 °C Lowest standing time in combustion chamber: 0,6 sec 20035 Lissone – via Adamello, 9 – tel (0039) 039.48.34.98 – 24.56.105 – fax (0039) 039.46.12.86 e-mail: [email protected] – sito web: www.ventilazioneindustriale.it Reg. Soc. Trib. Monza 54794 - R.E.A. Milano N.1444463 – C.F. e P.I. 02404270965

 Open the catalog to page 1
REMOVAL OF VOLATILE ORGAN COMPOUNDS (VOC) THROUGH FILTRATION, CONCENTRATION AND COMBUSTION WITH REGENERATIVE HEAT RECOVERY-2

EMISSION Air flow: 17000 Nm3/h Temperature: 40 – 45 °C Concentration max C.O.T.: <20 mg/Nm3 Concentration max CO : <10 mg/Nm3 Concentration max NOx: <25 mg/Nm3 20035 Lissone – via Adamello, 9 – tel (0039) 039.48.34.98 – 24.56.105 – fax (0039) 039.46.12.86 e-mail: [email protected] – sito web: www.ventilazioneindustriale.it Reg. Soc. Trib. Monza 54794 - R.E.A. Milano N.1444463 – C.F. e P.I. 02404270965

 Open the catalog to page 2

All AMBOSO catalogs and technical brochures

  1. ReCol System

    5  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.