Model AMT-Ex Dewpoint Transmitter
5Pages

{{requestButtons}}

Catalog excerpts

Model AMT-Ex Dewpoint Transmitter - 1

Intrinsically Safe 4-20 mA Dewpoint Transmitter Features and Benefits Certified Intrinsically Safe to IECEx, ATEX for use in hazardous areas and with potentially explosive atmospheres using specified Signal Isolator in the safe area Ultra-high capacitance aluminium oxide sensor delivers unsurpassed sensitivity, speed of response, accuracy, repeatability, stability, and long service life Unique AutoCal span correction feature Various dewpoint ranges available -110 °C to 20 °C Compact 3 Wire 4-20 mA Intrinsically Safe Dewpoint Transmitter Accuracy ±2 °C dewpoint IP66 / NEMA 4 Weatherproof Protection Optional Sensor Holder/Sample Cell for optimum sampling conditions Supplied with a calibration certificate traceable to National and International Humidity standards AMT-Ex in Transmitter Holder Our AMT-Ex Intrinsically Safe Online Dewpoint Transmitter is used for continuous measurement of trace moisture measurement in process gases or dry compressed air. AMT-Ex dewpoint transmitter can also be factory configured to output a linear 4-20 mA signal for other moisture units e.g. ppm(V), ppm(W), g/m3 and lb/MMSCF etc. The long lasting sensing element offers excellent sensitivity, repeatability and speed of response. Each unit is supplied with a Certificate of Calibration, traceable to International Humidity Standards. AMT-Ex is ATEX certified Intrinsically Safe for hazardous area use when installed with the appropriate isolator and display in the safe area. See Illustrations on pages 2, 3 & 4. This online dew point transmitter also incorporates an Automatic Calibration (AutoCal) feature that allows the user to carry out a field calibration / span check which is operated by two small button switches built within the transmitter enclosure and can withstand 35,000 kPa (350 bar) maximum pressure. By employing a low resistance cable, the AMT-Ex dewpoint transmitter can be located in excess of 1000 metres from the safe area control room. AMT-Ex Dewpoint Transmitter Technical Data Transmitter Type Sensing Element Output Signal Power Supply Dewpoint Ranges Intrinsic Safety Certification Standards ATEX, UKCA and IECEx Markings Electromagnetic Compatibility (EMC) Accuracy Repeatability Operating Temperature (Ambient and Process) Operating Pressure (Process) Operating Humidity (Ambient) Storage Temperature 3 Wire 4-20 mA Intrinsically Safe Dewpoint Transmitter Ultra-High Capacitance – Aluminium Oxide Type Linear 4-20 mA with selectable engineering units and fault indication 12-28 Vdc Reverse Polarity Protected See Page 5 - How to Order IECEx BAS07.0080 BASEEFA 07ATEX0234 BAS21UKEX0805 EN 60079-0:2018 EN 60079-11:2012 Ex II 1GD Ex ia IIC T4Ga Exia IIIC T200 135 °CDA (-20 °C ≤ Ta ≤ +60 °C) Complies with BS EN IEC 61326-1 ± 2 °C dewpoint (UK National Physical Laboratory traceable for range -90 °C to 20 °C) Better than ±0.3 °C dewpoint -20 °C to 60 °C From 1 kPa (0.01 bara) to Maximum 35,000 kPa (350 bara) Maximum 95 %RH

Open the catalog to page 1
Model AMT-Ex Dewpoint Transmitter - 2

Field Calibration AutoCal span check and correction are performed using two buttons on the Transmitter body. Locked in normal operating mode to avoid tamper. We recommend AutoCal is repeated every 2-3 months Supplied with a calibration certificate traceable to National and International Humidity standards. We recommend annual laboratory calibration Flow independent but ideally 2 to 5 litres per minute. Max: 25 litres/min IP66 / NEMA 4X rated, size C, DIN EN 175301 connector at the Transmitter and other end terminated with bootlace ferrules Supplied with 2 m IS (blue) standard cable. Nominal...

Open the catalog to page 2
Model AMT-Ex Dewpoint Transmitter - 3

Application Wiring Diagram Examples Using DS1200 Display AMT-Ex Dewpoint Transmitter Using PR5104BB2A Single Channel Isolator with DS1200 Display HAZARDOUS AREA SAFE AREA AMT-Ex Dewpoint Transmitter Using PR5104BB2B Dual Channel Isolator and DS1200 Display

Open the catalog to page 3
Model AMT-Ex Dewpoint Transmitter - 4

Application Wiring Diagram Examples Using DS4000 Display AMT-Ex Dewpoint Transmitter Using PR5104BB2A Single Channel Isolator with DS4000 Display AMT-Ex Dewpoint Transmitter Using PR5104BB2B Dual Channel Isolator and DS4000 Display Corrosive Gases: The Sensor should not be exposed to corrosive gases (or corrosive contaminants in the gas sample) as these can chemically attack the sensor, impairing calibration accuracy and/or damaging it beyond economic repair. Examples of such gases are mercury (Hg), ammonia (NH3), chlorine (Cl2) etc. Strong oxidising agents such as ozone (O3) should also be...

Open the catalog to page 4
Model AMT-Ex Dewpoint Transmitter - 5

Transmitter Range: The AMT-Ex Transmitter comes complete with 2 metres of connecting cable and connector plug as standard. Example: CAB110-AMT-Ex-[10] for 10 metres. Longer cables are charged at per meter increments up to 1000 metres. • Located in the Safe Area only Part No. PR5104BB2A - Single Channel Part No. PR5104BB2B - Dual Channel NOTE: ppm, ppb, g/m & lbs/MMSCF ranges are stated at atmospheric pressure. AMT-Ex Transmitter can be configured to provide corresponding ranges for operation at other constant pressure. This must be stated at time of order. 3 For a longer cable length with...

Open the catalog to page 5