AH12-5

AH12-5

Product catalog summary

Certifications and Standards

The battery product complies with multiple international certifications and standards including ISO9001 (Quality Management), ISO14001 (Environmental Management), OHSAS18001 (Occupational Health and Safety), UL (Underwriters Laboratories), CE (Conformity European), and IEC60896-21/22 (Stationary Lead Acid Batteries).

Design Life

The design life of the battery follows the EUROBAT Commercial Standard, with an expected operational life of 3 to 5 years.

Discharge Characteristics

The document provides detailed constant current (Ampere) and constant power (Watt) discharge tables at 25°C (77°F) for various time intervals ranging from 5 minutes to 20 hours. Key points include:

  • Current discharge values (in Amperes) decrease as discharge time increases, e.g., from 18.00 A at 5 minutes to 0.26 A at 20 hours.
  • Corresponding power discharge values (in Watts) also decrease with time, e.g., from 190.80 W at 5 minutes to 2.89 W at 20 hours.
  • Multiple voltage levels are considered for discharge curves, including nominal voltages from 9.60 V to 11.10 V.

Battery Specifications

  • Nominal Voltage: 12 V
  • Rated Capacity: 5.0 Ah (at 20-hour rate)
  • Dimensions: Total Height 106 mm (4.17 in), Height 101 mm (3.98 in), Length 90 mm (3.54 in), Width 70 mm (2.76 in)
  • Weight: Approximately 1.53 kg (3.36 lbs)
  • Terminal Type: Dimensions provided (mm), specifics not detailed

Capacity and Temperature Effects

Capacity varies with temperature and discharge rate:

  • At 25°C (77°F), the rated capacity is 5.0 Ah at 20-hour rate.
  • Capacity decreases at higher discharge rates: 4.60 Ah at 10-hour rate, 4.25 Ah at 5-hour rate, and 3.00 Ah at 1-hour rate.
  • Temperature impacts capacity retention: 102% at 40°C (104°F), 100% at 25°C (77°F), 85% at 0°C (32°F), and 65% at -15°C (5°F).

Self-Discharge and Storage

  • Capacity retention after storage at 25°C (77°F): 91% after 3 months, 82% after 6 months, and 64% after 12 months.

Charging Parameters

  • Initial charging current should be less than 2.0 A.
  • Recommended charging voltages: 14.40-14.70 V for cycle use, 13.50-13.80 V for float charging.

Additional Notes

Discharge curves and performance data are provided for various current levels (0.25 A to 18 A) and voltages, supporting detailed performance analysis. The battery is designed for reliable operation under specified conditions with clear guidelines for charging and storage to maximize lifespan and performance.

See more

Catalog excerpts

AH12-5-1

Specifications Nominal Voltage Rated capacity (20 hour rate) Total Height Weight Approx Characteristics Design Life EUROBAT Commercial Standard 3-5 years 20 hour rate(0.25 A) 10 hour rate(0.46 A) Capacity 5 hour rate(0.85 A) 25 (77 ) 1 hour rate(3.00 A) 1.5 hour discharge to 10.5V Internal Resistance Full charged Battery at 25 (77 ) Capacity 40 (104 ) a ected 25 (77 ) by Temperature 0 (32 ) (20hour rate) -15 (5 ) Self-Discharge at 25 (77 ) Terminal Charge Cycle (constant Voltage) Float Capacity after 3 month storage Capacity after 6 month storage Capacity after 12 month storage T1 Initial Charging Current less than 2.0 A Voltage 14.40-14.70V Voltage 13.50-13.80V Constant Current (Amp) and Constant Power(Wat t ) Discharge Table at 2 5℃( 77℉) Time 9.60V 10.20V 10.50V 10.80V 11.10V