1. Catalogs
  2. Algodue Elettronica
  3. Current transformers

Current transformers

Current transformers
1 / 13 PagesView full catalog

Current transformers

Product catalog summary
General Characteristics
The document details the specifications and applications of current transformers (C.T.), which reduce line current to secondary values of 5A or 1A. For electronic card applications, secondary values can be in A.C. current (50mA - 200mA), A.C. voltage (2V - 10V), or D.C. voltage (10V). These transformers, made with iron cores, are available in toroidal or rectangular shapes and use thermoplastic materials for insulation. They are tested with S.I.T. certified equipment and come in two primary types: wound primary for low current and primary passing for higher current. All models support DIN rail fixing.
Technical Characteristics
The transformers have an ABS self-extinguishing case and operate at a frequency of 40-60Hz. They can withstand a dynamic nominal current of short circuit up to 2.5 times the nominal current for 1 second and a thermal nominal current of short circuit ranging from 40-80 times the nominal current for 1 second. With a safety factor of N < 5, they offer high instrument protection. Operating temperatures range from -25°C to +50°C, with storage temperatures between -40°C and +80°C. The insulation is E class, and the protection degree is IP30. Construction complies with standards like CEI 38-1 and IEC 185.
Usage Examples
The document illustrates how the number of loops in the primary cable affects the current value without changing technical features or precision class. For example, a 300/5A transformer with two loops results in a 150/5A output.
Power Consumption Table
A table shows the power consumption (VA) between the current transformer and the reading instrument cables, recommending the use of current transducers for high voltage drops.
Product Variants
Various models of passing cable current transformers (TABV series) are listed with specifications such as primary current, burden, and order codes. UTF certified versions are available upon request.
Warnings and Recommendations
It is recommended to contact sales representatives for codes, availability, and quotes for specific models. Additionally, the height of linearized transformers or transducers is noted to be 20 mm higher than indicated in the drawings.
See more

Catalog excerpts

Current transformers-1

CATALOGO - CATALOGUE TRASFORMATORI di CORRENTE Current transformers

 Open the catalog to page 1
Current transformers-2

Trasformatori di corrente - Current transformers Sommario - Index Tipo Type Caratteristiche generali General characteristics Caratteristiche tecniche Technical characteristics Trasformatori di corrente apribili Openable current transformers La Società si riserva il diritto di modificare le specifiche in qualsiasi momento senza alcun obbligo di notifica. The Company can modify the specification at any time without having to give notice.

 Open the catalog to page 2
Current transformers-3

Trasformatori di corrente Current transformers CARATTERISTICHE GENERALI I trasformatori di corrente (T.A.) vengono utilizzati per ridurre la corrente di linea ad un valore secondario di 5A oppure a 1A. Per applicazioni su schede elettroniche vengono costruiti T.A. con valori di secondario:  in corrente c.a., 50mA - 60mA - 100mA - 200mA  in tensione c.a., 2V - 5V - 10V  in tensione c.c., 10V I T.A. sono composti da nuclei di ferro a grani orientati e possono essere toroidali o rettangolari, il numero di spire è calcolato in funzione della corrente secondaria. L’isolamento tra nucleo e avvolgimento...

 Open the catalog to page 3
Current transformers-4

Trasformatori di corrente Current transformers CARATTERISTICHE TECNICHE • Contenitore: in ABS autoestinguente • Corrente: al secondario 5A (1A)* • Frequenza di funzionamento: 40÷60Hz • Corrente nominale dinamica di corto circuito (Idin): 2,5 I.ter per 1 sec. Massimo valore di picco che il T.A. può sopportare con il secon ario in corto circuito d • Corrente nominale termica di corto circuito (Iter): 40-80 IpN per 1 sec. Massimo valore efficace con secondario in corto circuito • Sovracorrente permanente: 1,2 In • Tensione di riferimento per l’isolamento: 0,72 KV (1,2 KV)* massimo valore di tensione...

 Open the catalog to page 4
Current transformers-5

Trasformatori di corrente a barra passante Passing cable current transformers TABV 0 Codice d’ordine Order code Corrente primaria Primary current OPZIONE disponibile solo a richiesta: versione con certificato UTF - OPTIONS available only on request: UTF certified version TABV 1 Codice d’ordine Order code Corrente primaria Primary current OPZIONE disponibile solo a richiesta: versione con certificato UTF - OPTIONS available only on request: UTF certified version TABV 2 Codice d’ordine Order code Corrente primaria Primary current Prestazione - Burden OPZIONE disponibile solo a richiesta: versione...

 Open the catalog to page 5
Current transformers-6

Trasformatori di corrente a barra passante Passing cable current transformers TABV 3 Codice d’ordine Order code Corrente primaria Primary current A/5 OPZIONE disponibile solo a richiesta: versione con certificato UTF - OPTIONS available only on request: UTF certified version TABV 4 Codice d’ordine Order code Corrente primaria Primary current OPZIONE disponibile solo a richiesta: versione con certificato UTF - OPTIONS available only on request: UTF certified version TABV 5 Codice d’ordine Order code Corrente primaria Primary current OPZIONE disponibile solo a richiesta: versione con certificato...

 Open the catalog to page 6
Current transformers-7

Trasformatori di corrente a barra passante Passing cable current transformers TABV 6 Corrente primaria Primary current Codice d’ordine Order code OPZIONE disponibile solo a richiesta: versione con certificato UTF - OPTIONS available only on request: UTF certified version Trasformatori di corrente a barra passante Bus bar current transformers TABV 11-12 Codice d’ordine Order code Corrente Current CARATTERISTICHE MECCANICHE / MECHANICAL CHARACTERISTICS TIPO/TYPE OPZIONE disponibile solo a richiesta: versione con certificato UTF - OPTIONS available only on request: UTF certified versi

 Open the catalog to page 7
Current transformers-8

Trasformatori di corrente a barra passante Passing cable current transformers TABV 13 Codice d’ordine Order code Corrente primaria Primary current OPZIONE disponibile solo a richiesta: versione con certificato UTF - OPTIONS available only on request: UTF certified version TABV 14 Codice d’ordine Order code Corrente primaria Primary current OPZIONE disponibile solo a richiesta: versione con certificato UTF - OPTIONS available only on request: UTF certified version TABV 15 Codice d’ordine Order code Corrente primaria Primary current OPZIONE disponibile solo a richiesta: versione con certificato...

 Open the catalog to page 8
Current transformers-9

Trasformatori di corrente a primario avvolto Wound primary current transformers TAPV 1 Codice d’ordine Order code poli poles Corrente Prestazione - Burden Current cl. 0,5 cl. 1 A/5 OPZIONE disponibile solo a richiesta: versione con certificato UTF - OPTIONS available only on request: UTF certified version

 Open the catalog to page 9
Current transformers-10

Trasformatori di corrente a barra passante Passing cable current transformers TAFV 1 Codice d’ordine Order code Corrente primaria Primary current OPZIONE disponibile solo a richiesta: versione con certificato UTF - OPTIONS available only on request: UTF certified version TAFV 2 Codice d’ordine Order code Corrente primaria Primary current OPZIONE disponibile solo a richiesta: versione con certificato UTF - OPTIONS available only on request: UTF certified version TAFV 3 Codice d’ordine Order code Corrente primaria Primary current OPZIONE disponibile solo a richiesta: versione con certificato UTF...

 Open the catalog to page 10
Current transformers-11

Trasformatori di corrente linearizzati - uscita in ca/cc Linear current transformers - output in AC/DC Caratteristiche generali / Main characteristics Tipo / Type Alimentazione Power supply Autoalimentato Self powered Autoalimentato Self powered Autoalimentato Self powered Modelli Models Corrente primaria Primary current Uscita Output Carico minimo Minimum load Carico massimo Maximum load Programmazione Setup Precisione Accuracy * dal 10% al 100% del TA - from 10% to 100% of the CT Attenzione: l’altezza dei trasformatori linearizzati o trasduttori è superiore di 20 mm rispetto al valore indicato...

 Open the catalog to page 11
Current transformers-12

Trasformatori di corrente apribili Split core current transformers TAPRV 10 Codice d’ordine Order code Tipo Type Dimensioni / Size mm Foro hole OPZIONE disponibile solo a richiesta: versione con certificato UTF - OPTIONS available only on request: UTF certified version TAPRV 11-15 Codice d’ordine Order code Tipo Type Foro hole OPZIONE disponibile solo a richiesta: versione con certificato UTF - OPTIONS available only on request: UTF certified version

 Open the catalog to page 12

All Algodue Elettronica catalogs and technical brochures

  1. UEM2L, UEM4L

    7  Pages

  2. MFC190

    3  Pages

  3. MFC150 SERIES

    4  Pages

  4. RPS51

    3  Pages

  5. MFC140 SERIES

    4  Pages

  6. RPS50

    3  Pages

  7. UEM80-2D

    4  Pages

  8. UEC80-D

    4  Pages

  9. UEM80

    4  Pages

  10. UPA20

    5  Pages

  11. UEM6C

    4  Pages

  12. UPM209RGW

    5  Pages

  13. UPM309RGW

    5  Pages

  14. UEC1P5-D

    4  Pages

  15. UEM40-2C R70

    4  Pages

  16. UEM63-4D R70

    4  Pages

  17. UPA30 / UPA41

    5  Pages

  18. UEM1P5

    4  Pages

  19. UEC80-2D

    4  Pages

  20. FCA3000

    3  Pages

  21. UEC40 UEM40

    4  Pages

  22. UPM309

    5  Pages

  23. UPM SERIES

    9  Pages

  24. UPA SERIES

    8  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.