Low maintenance high performance batteries ADVANCED SOLUTIONS ENGINEERING EXCELLENCE
Open the catalog to page 1Low maintenance, high performance Ni-Cd batteries Powerful assurance for critical applications depend upon XHP where vital UPS, engine starting and emergency back-up duties need guaranteed power in an instant. The built-in reliability of sintered/pbe technology and alkaline electrolyte provides up to 20+ years of cost-effective trouble-free service, requiring virtually no maintenance. Future-proof construction Best for engines – perfect for UPS XHP’s steel superstructure and tough polypropylene casing hold sintered and plastic-bonded electrodes with copious amounts of alkaline electrolyte....
Open the catalog to page 2Bayonet flamearrester vent plug Large electrolyte reserve with visible levels Plastic-bonded negative electrode Separator Sintered positive electrode Rapid charging characteristics ( + 20 ˚ C ± 5 ˚ C /+ 68 ˚ F ± 9 ˚ F) XHP can be charged by all normal methods: With boost The rated capacity(C 5 ) of a cell is the capacity available in ampere-hours (Ah) at the 5 hour discharge rate to an end voltage of 1.00 V/cell. Maintenance float voltage: 1.40 ± 0.01 V Boost voltage range: 1.45 V ± 0.01 V Constant current Nominal discharge voltage Without boost Constant voltage The nominal discharge voltage...
Open the catalog to page 3Capacity and dimensions XHP Capacity Length per cell Width per cell Overall height type at the H H H Approx. weight per cell Alcad XHP batteries fulfil all requirements specified by IEC publication 60623 Flame retardant (F) option available. Please add 1.5% to dimensions.
Open the catalog to page 4Data for stationary applicationsPerformance after prolonged float charge of fully charged cells Available amperes at + 20°C ± 5°C/+68°F ± 9°F Final voltage: 1.00 V/cell Final voltage: 1.05 V/cell
Open the catalog to page 5XHPData for stationary applicationsPerformance after prolonged float charge of fully charged cellsAvailable amperes at +200C ± 5°C/+68°F ± 90F Final voltage: 1.10 V/cell Available amperes at +20°C ± 5°C/+68°F ± 9°F Final voltage: 1.14 V/cell
Open the catalog to page 6Data for engine starting applicationsPerformance for fully charged cells by a constant current charge according to IEC 60623 standard Available amperes at + 20°C ± 5°C/+68°F ± 9°F Final voltage: 0.65 V/cell XHP type Available amperes at +20>C ± 5°C/+68°F ± 90F Final voltage: 0.85 V/cell XHP type
Open the catalog to page 7Alcad Limited Headquarters United Kingdom Document X3.0.E.0117 - Edition: January 2017 - Finedesign - Photo credits: Alcad, Fotolia © Alcad Alcad Sales Offices
Open the catalog to page 8All ALCAD Ltd catalogs and technical brochures
-
AT10.1 SERIES
8 Pages
-
Rack Range Ni-Cd batteries
8 Pages
-
New Vantex
2 Pages
-
Vantage Rang
8 Pages
-
Alcad Services
8 Pages
-
Alcad Corporate Brochure
8 Pages
-
Alcad Single Cell Range
32 Pages
-
Vantex New Generation
12 Pages
-
Solar Range
8 Pages
-
HC P Range
27 Pages
Archived catalogs
-
Pocket Plate Range Data
27 Pages