XHP Range

XHP Range

XHP Range

Product catalog summary
Overview: The document discusses XHP Ni-Cd batteries, emphasizing their low maintenance, high performance, and suitability for critical applications like UPS, engine starting, and emergency backup. These batteries are designed for long-term reliability and cost-effectiveness, with a lifespan exceeding 20 years and minimal maintenance needs.
Specifications: XHP batteries are constructed with a steel superstructure and polypropylene casing, containing sintered and plastic-bonded electrodes with an alkaline electrolyte. They surpass lead-acid batteries in longevity, requiring topping-up only every 10 years. They operate efficiently between -20°C and +50°C and can endure extremes from -50°C to +70°C for short durations.
Performance and Reliability: XHP batteries are dependable in various conditions, suitable for both onshore and offshore use. They resist electrical abuses such as AC ripple and overcharging, making them ideal for UPS systems. They deliver high power within a narrow voltage window and provide high currents even when partially discharged.
Charging and Maintenance: XHP batteries support various charging methods, including taper, constant current, constant voltage, and pulse. They perform satisfactorily in any state of charge. The maintenance float voltage is 1.40 ± 0.01 V, with a boost voltage range of 1.45 V ± 0.01 V.
Battery Sizing and Standards: The document provides detailed sizing information for different XHP battery types, including capacity, dimensions, and weight. XHP batteries comply with major electrical industry standards and are approved for use on ships and offshore installations. Alcad, the manufacturer, also offers recycling services for old batteries.
Data Tables: Extensive tables in the document detail the performance of various XHP battery types across different discharge rates and conditions, offering critical data for engineers to select the appropriate battery for specific applications.
See more

Catalog excerpts

XHP Range-1

Low maintenance high performance batteries ADVANCED SOLUTIONS ENGINEERING EXCELLENCE

 Open the catalog to page 1
XHP Range-2

Low maintenance, high performance Ni-Cd batteries Powerful assurance for critical applications depend upon XHP where vital UPS, engine starting and emergency back-up duties need guaranteed power in an instant. The built-in reliability of sintered/pbe technology and alkaline electrolyte provides up to 20+ years of cost-effective trouble-free service, requiring virtually no maintenance. Future-proof construction Best for engines – perfect for UPS XHP’s steel superstructure and tough polypropylene casing hold sintered and plastic-bonded electrodes with copious amounts of alkaline electrolyte. As...

 Open the catalog to page 2
XHP Range-3

Bayonet flamearrester vent plug Large electrolyte reserve with visible levels Plastic-bonded negative electrode Separator Sintered positive electrode Rapid charging characteristics ( + 20 ˚ C ± 5 ˚ C /+ 68 ˚ F ± 9 ˚ F) XHP can be charged by all normal methods: With boost The rated capacity(C 5 ) of a cell is the capacity available in ampere-hours (Ah) at the 5 hour discharge rate to an end voltage of 1.00 V/cell. Maintenance float voltage: 1.40 ± 0.01 V Boost voltage range: 1.45 V ± 0.01 V Constant current Nominal discharge voltage Without boost Constant voltage The nominal discharge voltage is...

 Open the catalog to page 3
XHP Range-4

Capacity and dimensions XHP Capacity Length per cell Width per cell Overall height type at the H H H Approx. weight per cell Alcad XHP batteries fulfil all requirements specified by IEC publication 60623 Flame retardant (F) option available. Please add 1.5% to dimensions.

 Open the catalog to page 4
XHP Range-5

Data for stationary applicationsPerformance after prolonged float charge of fully charged cells Available amperes at + 20°C ± 5°C/+68°F ± 9°F Final voltage: 1.00 V/cell Final voltage: 1.05 V/cell

 Open the catalog to page 5
XHP Range-6

XHPData for stationary applicationsPerformance after prolonged float charge of fully charged cellsAvailable amperes at +200C ± 5°C/+68°F ± 90F Final voltage: 1.10 V/cell Available amperes at +20°C ± 5°C/+68°F ± 9°F Final voltage: 1.14 V/cell

 Open the catalog to page 6
XHP Range-7

Data for engine starting applicationsPerformance for fully charged cells by a constant current charge according to IEC 60623 standard Available amperes at + 20°C ± 5°C/+68°F ± 9°F Final voltage: 0.65 V/cell XHP type Available amperes at +20>C ± 5°C/+68°F ± 90F Final voltage: 0.85 V/cell XHP type

 Open the catalog to page 7
XHP Range-8

Alcad Limited Headquarters United Kingdom Document X3.0.E.0117 - Edition: January 2017 - Finedesign - Photo credits: Alcad, Fotolia © Alcad Alcad Sales Offices

 Open the catalog to page 8
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.