Overview
Isolated Power Systems (IG, IT, MED Series) are essential for medical environments, particularly Group 2 rooms, to ensure continuous operation of medical equipment during insulation failures. These systems prevent circuit breakers from tripping, thus avoiding energy interruptions.

Isolated Power Supply Panels (IG Series)
These panels include isolating transformers, insulation monitoring devices, and fault location devices. They monitor insulation levels and trigger alarms if resistance falls below 50 kΩ. Key features include a power range of 3.15 to 10 kVA, a rated voltage of 230 Vac, and communication via Modbus RTU protocol. They are used in hospitals, dental clinics, and similar facilities.

Standards
The systems comply with IEC 60364-7-710, IEC 61558-2-15, and IEC 61557-8/9 standards, ensuring safety and reliability.

Isolating Transformers (IT Series)
These transformers minimize electrical interference and provide reliable power in critical medical areas. They have a power range of 3.15 to 10 kVA, primary/secondary voltage of 230/115 Vac, and include overload protection and temperature monitoring.

Insulation Monitoring Device (IMD 30)
The IMD 30 detects insulation faults and monitors transformer conditions, featuring high measurement resolution and low uncertainty. It communicates with the EDS 30 Fault Location Device.

Fault Location Device (EDS 30)
This device quickly identifies insulation fault locations, supports up to 6 lines, and communicates with the IMD 30.

Changeover Module (CTS 30)
The module ensures seamless power transfer between sources with a transfer time of ≤ 40 ms, preventing interruptions.

Alarm Panels (LAP 70 and RAI 70)
These panels provide visual and auditory alarms for insulation faults, overloads, and overtemperature conditions, supporting event logging and remote monitoring.

Hospital Monitoring Interface (HMI 70)
The HMI 70 allows comprehensive monitoring of the isolated power system, displaying all alarm information on a single screen.

Conclusion
Aktif's Isolated Power Systems provide robust solutions for maintaining uninterrupted power in medical environments, ensuring safety and compliance with international standards.
See more

Catalog excerpts

Isolated Power Systems-1

Isolated Power Systems Medical Solutions IG | IT | MED Series

 Open the catalog to page 1
Isolated Power Systems-2

Isolated Power Supply Panels Isolated power panels are used in Group 2 rooms in medical locations, and they consist of auxiliary devices and test combinations such as isolating transformer, insulation monitoring device and insulation fault location devices. IT system different from TN and TT systems, when an insulation failure occurs, IT system ensures that there is no electrical problem by preventing the circuit breakers from tripping and interrupting the system. The medical equipment continues to function, the fault currents are reduced to non-critical values, and the energy interruption is...

 Open the catalog to page 2
Isolated Power Systems-4

Isolating Transformers IT series medical isolating transformers are manufactured in accordance with IEC 603647-710 and IEC 61558-2-15 standards. IT isolating transformers are used to supply power at Group 2 rooms of medical locations such as operating rooms, intensive care units and as addition they are also used to power laboratory instruments and other sensitive devices. The design of the isolating transformers is aimed at reducing the impact of electrical faults through electrostatic protection. The IT series medical isolating transformers have galvanically isolated windings to minimize electrical...

 Open the catalog to page 4
Isolated Power Systems-5

IMD 30 Insulation Monitoring Device IMD 30 Insulation Monitoring Device is one of the most important equipment of IT grounding systems. It detects insulation fault in the system by constantly checking the insulation resistance level between phases and earth. At the same time, it monitors the load current and the temperature of the isolating transformer in accordance with the IEC 60364-7-710 standard and ensures that the warning system is started when it reaches critical values. The device, which can indicate alarm situations visually and audibly, has the feature of showing insulation fault, overload...

 Open the catalog to page 5
Isolated Power Systems-6

CTS 30 Changeover Module is the equipment that enables to select the convenient one between two different sources supplying the isolated power panel and transfer it to the output. The changeover module, which performs the transfer process within the periods specified by the IEC 60364-7-710 standard, monitors the continuous voltages of the two sources and automatically transfers when the voltage value drops below 0,9xUn and exceeds 1,15xUn. Thus, any power interruption that may occur from the failure of the supply source or from the supply cables is prevented. Advantages • Transfer Time: < 40...

 Open the catalog to page 6
Isolated Power Systems-7

LAP 70 Local Alarm Panel RAI 70 Remote Alam Indicator LAP 70 Local Alarm Panel indicates alarms like insulation fault, overcurrent, transformer over temperature visually and audibly that are detected by the IMD 30 Insulation Monitoring Device and stores each event with their timestamp. Advantages • Automatic adressing thanks to synchronization with IMD 30 • Up to 150 event logs thanks to its internal real time clock. • Remote insulation test and fault contact outputs The RAI 70 Remote Alarm Indicator enables remote monitoring of all data, alarms, and events in the isolated power system through...

 Open the catalog to page 7
Isolated Power Systems-8

HMI 70 Hospital Monitoring Interface , ten* S’* oes«,raCS i____OJ HMI 70 Hospital Monitoring Interface is used to remotely monitor all alarm information detected by the medical isolated power system. HMI 70 Hospital Monitoring Interface communicates with RAI 70 Remote Alarm Panel and IG Series Medical Isolated Power Panel, allowing the technical service personnel in the hospital to monitor transfer alarm, insulation fault, overtemperature fault and overload fault information audibly and visually through a single product. Advantages • Monitoring the entire system on a single screen • Customizible...

 Open the catalog to page 8
Isolated Power Systems-9

Doc. Nr: MED-20240320/Eng Owing to periodical improvements of our products the supplied products may differ in some details from the data stated in the prospectus material. Published by Aktif Data subject to alteration without notice. Design & Creation: Aktif / Photos: Aktif - Stock.xchng & Shutterstock, Published Date: 20.03.2024 Germany Office Bayraktar Bul. Şehit Sk. No: 5 34775 Ümraniye, İstanbul, TR Phone : +90 (216) 314 93 20 Fax : +90 (216) 314 93 60 www.aktif.net - [email protected] Bahnhofstrasse 82-86 35390 Giessen, Germany Phone : +49 176 60940534 www.aktif.net [email protected] Akşemsettin...

 Open the catalog to page 9
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.
About DirectIndustry
DirectIndustry is a marketplace that offers B2B players a complete experience, from product sourcing to purchase. DirectIndustry is an entity of VirtualExpo Group.