video corpo

UX/UZ

UX/UZ

UX/UZ

Product catalog summary
Overview: The document provides technical specifications and guidelines for the installation and operation of the UX/UZ Ultrasonic Flow Meters, designed for fuel gas management. These meters are suitable for various gases including city gas, butane, propane, nitrogen, and argon.
Specifications: The flow meters are available in models UX40, UX50, UZ40, and UZ50, with connection diameters of 40A and 50A. They support a wide range of flow rates from 1.6 to 150 m3/h, depending on the model. The meters can operate under pressures up to 500kPa and temperatures ranging from -10℃ to +60℃.
Conversion and Accuracy: The document details the conversion of actual flow to normal flow using specific equations that account for atmospheric pressure and temperature. The accuracy of the flow meters is specified as ±1.5%RD at 23℃ and 100kPa.
Installation Guidelines: The flow meters can be installed directly after bends in piping without requiring a straight pipe section. However, they must be placed at least 10D away from a governor to ensure accurate measurements. The meters are designed for both indoor and outdoor use, with an IP64 protection rating.
Power Supply and Display: The meters offer multiple power supply options, including 100VAC, 24VDC, and an exclusive lithium battery. The display orientation can be adjusted on-site, and the meters provide outputs for pulse, alarm, and 4-20mA signals.
Maintenance and Durability: The flow meters are designed for easy maintenance, with replaceable batteries that do not require removal of the meter from the piping. They are robust against dust and have high durability, making them suitable for outdoor applications.
Additional Features: The document highlights the ability to measure small flow ranges accurately and the compatibility with various gas types. It also emphasizes the importance of using a sunshade to prevent high temperatures from affecting the electronic components.
See more

Catalog excerpts

UX/UZ-1

Specifications of Ultrasonic Flow Meter UX/UZ for Fuel Gas Management Model Maximum working pressure Gas type ※1 City gas (13A), butane (butane = 70%, propane = 30%), propane (propane = 98%, butane 2%), nitrogen and argon Battery ※2 Power/ AC power consumption DC power Flow range City gas, nitrogen and argon (Actual flow) Butane and propane Ultrasonic Flowmeter Temperature and pressure compensation ※4 Conversion accuracy ±4%RD (for a range of 10% to 100% of the max flow) ±0.5%FS (for a range of 2% to 10% of the max flow) Pipe connection Yes/No (Normal/Standard conversion) ±1.5%RD(@23℃ and 100kPa) Developed jointly by Tokyo Gas Co., Ltd. and our company Accumulated flow (actual flow: 8-digit integer + 2 decimal places, converted flow: 8-digit integer + one decimal place, accumulated flow of trip function) Main display Alarm indication (for ultrasonic sensor, temperature sensor, pressure sensor, external memory and power voltage (for battery operation only)) (For 100VAC or 24VDC only) 4-20mADC (load resistance = max 400Ω): choose among options of instantaneous flow, temperature and pressure (default = instantaneous flow) Output 1 (accumulated flow volume pulse): standard = 1000L/P (choose 10, 100, 1000 or 10000 L/P): duty = 20 ‒ 80% Instantaneous flow: 5 digits; temperature: 3 digits; and pressure: 5 digits Nch open-drain output (maximum load 24VDC, 50mA) Output 2 (alarms): upper & lower limits, or upper limits of accumulated flow (for 100VAC or 24VDC drive); low voltage, or upper & lower limits (for battery drive) Fluid temperatur Ambient working temperature and humidity Protective structure Mass -10℃ to +60℃, under unfrozen condition -10℃ to +60℃, max 90%RH, no condensation permissible Indoor and outdoor use *6, IP64 (JIS C 0920) About 6.3kg *1 Gas type (composition) can be changed on site among those specified here with little degradation in measuring accuracy. *2 Replaceable without removing the meter from the piping *3 In case a distance from an elbow of minimum 10D in the upstream side and 5D in the downstream side of the meter can be secured: ±2%RD (for a range of 10% to 100% of the max. flow) and ±0.5%FS (for a range of 2% to 10% of the max. flow). The distance to a governor should be greater than 10D for both the upstream and downstream sides of the meter. Failing to meet this condition may lead to naccurate measurements. For other conditions for installation, please contact us. *4 Normal flow: Conversion of measurement into a flow at 0℃ and1atm. Standard flow = conversion of measurement into a flow at the reference temperature and 1 atom *5 For communication specifications, see our company's website to download it. *6 High temperatures can cause the electronic circuit board to be deteriorated and the batteries to be consumed. To avoid unnecessary rise in temperature, the product is recommended to be fitted with a sunshade. Conversion into Normal flow: example (at fluid temperature of 15℃) ○ Diameter of 40A Actual flow ○ Diameter of 50A Actual flow Atmospheric Gauge pressure pressure + (101.325kPa) (kPa) Atmospheric pressure (101.325kPa) Absolute temperature scale value of 0℃ (273.15K) Gauge Atmospheric pressure + pressure (kPa) (101.325kPa) × × = Atmospheric Reference pressure flow pressure + for conversion (101.325kPa) (kPa) Standard flow Gauge pressure Normal flow Gauge pressure Absolute temperature scale value of 0℃ (273.15K) Absolute temperature Reference temperature scale value of 0℃ + for conversion (273.15K) (℃) Absolute temperature scale value of 0℃ (273.15K) Terminal stands and connection RS485 PULSE ALARM OUTPUT OUTPUT (+) (+) PULSE OUTPUT ALARM OUTPUT 4-20mA OUTPUT PULSE ALARM OUTPUT OUTPUT (+) (+) PULSE OUTPUT ALARM OUTPUT 4-20mA OUTPUT PULSE ALARM OUTPUT OUTPUT (+) (+) PULSE OUTPUT ALARM OUTPUT section required for installation Technical specifications in this catalog are up-to-date as of June 2020 Aichi tokei denki co.,ltd. URL:https://www.aichitokei.net/ 1-2-70 Chitose, Atsuta-ku, Nagoya, 456-8691, Japan For inquires, please contact us. Overseas Business Division TEL +81-(0)52-661-5150 Please understand that product specifications may be changed without notice in order to improve performance.

 Open the catalog to page 1
UX/UZ-2

Needl Customer wants to install a flow meter immediately after a bend part in the piping Need3 Customer wants to replace batteries No straight pipe section required for installation It is possible to connect the flow meter directly to a bend such as an elbow piece and a flexible pipe. Easy to replace batteries You can choose one of the three power supply options: The flow meter has to be located 10D or more distant from a governor irrespective whether it is placed upstream or downstream of the governor. Falling to meet this condition may lead to inaccurate measurements. (D = pipe diameter) Users...

 Open the catalog to page 2

All Aichi Tokei Denki Co.,Ltd catalogs and technical brochures

  1. UX15

    2  Pages

  2. VNS

    2  Pages

  3. TRX/TRZ

    1  Page

  4. OF

    2  Pages

  5. UW

    4  Pages

  6. CX

    4  Pages

  7. AS-W

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.