s114

s114

Product catalog summary
Specifications:
- Inputs: Supports 2 sensors with a 3-wire connection cable and a wire cross-section greater than 0.5 mm². Maximum distance between control unit and sensor is 150 meters.
- Alarm Threshold: Permanently set at 20% LEL for gases, with alarm memory.
- Display: Includes a green LED for operation and a red LED for fault (flashing) or alarm (steady on).
- Audible Alarm: Features a piezo buzzer at approximately 70 dB(A), which can be acknowledged.
- Switching Outputs: Equipped with a relay contact that is voltage-free, rated at AC 250 V, 2 A.
- Supply Voltage: Operates on AC 230 V with a power input of 15 VA.
- Operating Temperature: Suitable for ambient temperatures between 0 and 40°C.
- Housing: Made of impact-resistant plastic (ABS) for wall mounting, with dimensions 100 x 188 x 65 mm and a weight of 0.55 kg. Degree of protection is IP 40 according to EN 60529.
Application:
The GRM gas and smoke detector is designed for continuous monitoring of explosive gases, vapors, and smoke, generating alarms in conjunction with appropriate sensors. It is suitable for use in heating rooms, basements, storage areas, offices, residential buildings, and public facilities to enhance safety. However, it is not suitable for hazardous areas (EX areas).
Functionality:
The unit features an alarm threshold and a relay contact. When the threshold is exceeded, it triggers an alarm, lighting up the red LED, sounding the audible alarm, and switching the alarm relay. The audible alarm can be muted with an Acknowledge button, which also clears the visual alarm once the alarm condition is resolved. The relay contact allows for the integration of additional external signaling equipment.
Sensor Combinations:
The GRM can be configured with various sensor combinations, including:
1. One gas sensor and one smoke sensor
2. Two gas sensors
3. Two smoke sensors
4. One gas sensor
5. One smoke sensor
See more

Catalog excerpts

s114-1

Building technology For natural gas and liquid gas (gas detector) For early detection of smoke (smoke detector) Audible and visual alarms; Acknowledge button and relay output Self-monitoring for line interruption, short circuit and sensor defect A 5 Application For continuous monitoring of explosive gases, vapours and smoke and for generating alarms in conjunction with the appropriate sensors. GRM is installed in heating rooms and basements, storage, office and residential buildings as well as public facilities to increase safety. Not suitable for installation in hazardous areas (EX areas). Description Alarm unit in a wall mounting housing with audible and visual alarms. GRM features an alarm threshold and is equipped with a relay contact. If the threshold value is exceeded, the unit generates an alarm. The red LED lights up, the audible alarm goes on and the alarm relay switches. The audible alarm can be muted with the Acknowledge button. When the alarm condition no longer exists, you press the Acknowledge button again to clear the visual alarm (alarm memory). The alarm can only be cleared with the Acknowledge button if the reason for the alarm has been removed. If the concentration still exceeds the alarm threshold, pressing the Acknowledge button does not clear the alarm. The voltagefree relay contact allows you to switch additional external signalling equipment such as the event reporting system EMS, horns, lamps, fans or fan controllers in the case of alarm or fault conditions. GRM is suitable for panel mounting with a mounting frame. A sealing kit (IP 54) is available for rough application conditions. The following sensor combinations are possible with GRM: 1. 1 gas sensor and 1 smoke sensor 2. 2 gas sensors 3. 2 smoke sensors 4. 1 gas sensor 5. 1 smoke sensor Technical specifications Inputs 2 sensors Connection cable 3 wires Wire cross section > 0.5 mm2 Distance control unit – sensor Max. 150 m Alarm threshold 1 permanently installed alarm threshold for alarm at 20 % LEL (for gases) with alarm memory Display 1 green LED: Operation 1 red LED: Flashing: fault Steady on: alarm Audible alarm Piezo buzzer approx. 70 dB(A), can be acknowledged Switching outputs Relay contacts: voltage-free changeover contact 1 Contact rating: AC 250 V, 2 A Supply voltage AC 230 V Power input 15 VA Operating temperature range Ambient: 0/40 °C Housing Wall mounting housing made of impact-resistant plastic (ABS) W x H x D: 100 x 188 x 65 mm Weight: 0.55 kg Degree of protection: IP 40 (EN 60529) Please order sensors and calibration separately.

 Open the catalog to page 1

All AFRISO-EURO-INDEX catalogs and technical brochures

  1. s022

    1  Page

  2. s025

    1  Page

  3. s033

    1  Page

  4. s056

    3  Pages

  5. s058

    2  Pages

  6. s062

    1  Page

  7. s112

    1  Page

  8. s116

    1  Page

  9. s113

    1  Page

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.