INTRINSIC SAFETY BARRIERS - ATEX

Open the catalog to page 1
INTRINSIC SAFETY ATEX BARRIERS - 2

SIL 3 Repeater Power Supply Smart-Hart compatible DIN-Rail Models D1010S, D1010D Manufacturer: Technical Data: General Description: The single and dual channel DIN Rail Repeater Power Supply, D1010S and D1010D, provides a fully floating dc supply for energizing conventional 2 wires 4-20 mA transmitters, or separately powered 3, 4 wires 4-20, 0-20 mA transmitters located in Hazardous Area, and repeats the current in floating circuit to drive a Safe Area load. The circuit allows bi-directional communication signals, for Hart-Smart transmitters. Function: 1 or 2 channels I.S. analog input for...

Open the catalog to page 2
INTRINSIC SAFETY ATEX BARRIERS - 3

Parameters Table: Safety Description Maximum External Parameters Group Cenelec Terminals 14-15, 10-11 Uo/Voc = 26.3 V IIC 0.095 Io/Isc = 91 mA IIB 0.738 Po/Po = 597 mW IIA 2.508 Terminals 15-16, 11-12 Uo/Voc = 1.1 V IIC 100 Io/Isc = 38 mA IIB 1000 Po/Po = 11 mW IIA 1000 NOTE for USA and Canada: IIC equal to Gas Groups A, B, C, D, E, F and G IIB equal to Gas Groups C, D, E, F and G IIA equal to Gas Groups D, E, F and G Function Diagram: HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC, HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D, CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III,...

Open the catalog to page 3
INTRINSIC SAFETY ATEX BARRIERS - 4

Function Diagram: HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC, HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D, CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1, CLASS I, ZONE 0, GROUP IIC SAFE AREA, ZONE 2 GROUP IIC T4, NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2, GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4 Safety Description Terminals 14-11 (with 15-12 shorted) Uo/Voc = 27.4 V Io/Isc = 91 mA Po/Po = 624 mW Group Cenelec IIC IIB IIA Connections for Duplication of 2 wires Transmitter Input Restriction on specifications for 2 wires Transmitter Input:...

Open the catalog to page 4
INTRINSIC SAFETY ATEX BARRIERS - 5

Function Diagram: HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC, HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D, CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1, CLASS I, ZONE 0, GROUP IIC SAFE AREA, ZONE 2 GROUP IIC T4, NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2, GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4 Safety Description Terminals 15-12 (with 16-11 shorted) Uo/Voc = 2.2 V Io/Isc = 38 mA Po/Po = 21 mW Group Cenelec IIC IIB IIA Connections for Duplication of Active Input Signals Restriction on specifications for external powered Transmitter: The...

Open the catalog to page 5
INTRINSIC SAFETY ATEX BARRIERS - 6

Switch/Proximity Detector Repeater Relay Output DIN-Rail Models D1030S, D1030D Manufacturer: Technical Data: General Description: The Switch/Proximity Detector Repeater type D1030 is a DIN Rail unit with one or two independent channels. The unit can be configured for contact or proximity detector, NO or NC and for NE or ND SPDT relay output contact. Each channel enables a Safe Area load to be controlled by a switch, or a proximity detector, located in Hazardous Area. D1030D dual channel type has two independent input channels and actuates the corresponding output relay. Two actuation modes...

Open the catalog to page 6
INTRINSIC SAFETY ATEX BARRIERS - 7

Parameters Table: Safety Description Maximum External Parameters Function Diagram: HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC, HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D, CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1, CLASS I, ZONE 0, GROUP IIC SAFE AREA, ZONE 2 GROUP IIC T4, NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2, GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4 voltage free Contact Proximity voltage free Contact Proximity voltage free Contact Proximity Relay contact shown in de-energized position AECO Sri - Via Giacomo Leopardi 5 I-20065 Inzago...

Open the catalog to page 7
INTRINSIC SAFETY ATEX BARRIERS - 8

Switch/Proximity Detector Repeater Transistor Output DIN-Rail Models D1031D, D1031Q Manufacturer: Technical Data: General Description: The Switch/Proximity Detector Repeater type D1031 is a DIN Rail unit with two or four independent channels. The unit can be configured for contact or proximity detector, NO or NC and for NO or NC optocoupled open collector transistor output. Each channel enables a Safe Area load to be controlled by a switch, or a proximity detector, located in Hazardous Area. D1031Q quad channel type has four independent input channels and actuates the corresponding output...

Open the catalog to page 8
INTRINSIC SAFETY ATEX BARRIERS - 9

Parameters Table: Safety Description Image: Maximum External Parameters Co/Ca (µF) Group Cenelec Terminals 13-14, 15-16 9-10, 11-12 Uo/Voc = 10.7 V 2.23 IIC Io/Isc = 15 mA 15.60 IIB Po/Po = 39 mW 69.00 IIA NOTE for USA and Canada: IIC equal to Gas Groups A, B, C, D, E, F and G IIB equal to Gas Groups C, D, E, F and G IIA equal to Gas Groups D, E, F and G Function Diagram: HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC, HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D, CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1, CLASS I, ZONE 0, GROUP IIC SAFE AREA, ZONE 2 GROUP IIC T4,...

Open the catalog to page 9
INTRINSIC SAFETY ATEX BARRIERS - 10

SIL 2 Switch/Proximity Detector Repeater Relay Output DIN-Rail Models D1032D, D1032Q Manufacturer: Technical Data: General Description: The Switch/Proximity Detector Repeater type D1032 is a DIN Rail unit with two or four independent and isolated channels. The unit can be configured for contact or proximity detector, NO or NC and for NE or ND relay output. Each channel enables a Safe Area load to be controlled by a switch, or a proximity detector, located in Hazardous Area. D1032Q quad channel type has four independent input channels and actuates the corresponding output relay. Two...

Open the catalog to page 10
INTRINSIC SAFETY ATEX BARRIERS - 11

Parameters Table: Safety Description Image: Maximum External Parameters Co/Ca (µF) Group Cenelec Terminals 13-14, 15-16 9-10, 11-12 Uo/Voc = 9.6 V IIC 3.599 Io/Isc = 10 mA 25.999 IIB Po/Po = 24 mW IIA 209.999 NOTE for USA and Canada: IIC equal to Gas Groups A, B, C, D, E, F and G IIB equal to Gas Groups C, D, E, F and G IIA equal to Gas Groups D, E, F and G Function Diagram: HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC, HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D, CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1, CLASS I, ZONE 0, GROUP IIC SAFE AREA, ZONE 2 GROUP IIC...

Open the catalog to page 11