Catalog excerpts
HAcrelAEW100 wireless measurement meter Overview AEW 100 wireless measurement module is mainly used for metering three phase active energy on low voltage network. There are functions like RS485 communication and wireless communication on 470MHz in order to help customers check, get and manage the value of energy consumption. This kind of production can be installed in distribution box flexibly, achieving the different demand of measurement and statistics of distribution on different areas and different loadings. -Empty:Normal wiring;CG:Taking voltage from magnetic steel -Empty:No Temperature Measurement;TN:Temperature Measurement -Empty:Rod antenna;X:Sucker antenna -Empty:Piercing(except D15);W:No piercing -D15\D20\D36:Mutual inductor aperture 15mm/20mm/36mm Wireless metrology module Note: 1. Choose W before choosing CG; 2. There is a mobile antenna lay outside can be chosen, and the length of wire is 2 meters. Version number -Empty:No Temperature Measurement; TN:Temperature Measurement Aperture Low pressure open type Mutual inductor Chart 1 Mutual inductor specification Installation and operation instruction
Open the catalog to page 1rzIAcrel Voltage Installation and operation instruction
Open the catalog to page 2'iJAcrelDimension and installing description (Unit: mm) ■ Dimension drawings (Unit: mm) Chart 5 Dimension of mutual inductor 54 50 Metering module Fig 2 Dimension of mutual inductor AKH-0.66/K-20 Fig 3 Dimension of mutual inductor AKH-0.66/K-36 Installation and operation instruction
Open the catalog to page 3Fig 4 Dimension of mutual inductor HCT16K-FJ Fig 5 Dimension of mutual inductor HCT20K-TN Fig 6 Dimension of mutual inductor HCT36K-TN ■ Installing and Wiring description 17 ① Installing description of normal type with piercing L1, L2, L3 prick in to A, B, C phase respectively, and especially the A phase and N terminal powered for the AEW100. And A, B, C phase transmits the voltage and current to AEW100 by mutual inductor, and then the AEW100 transmits the single to PC via RS485. First step: Loosing the needle screw and loosing the wire bezel to the top (show as above). (The current flow...
Open the catalog to page 4Second step: Open the mutual inductor and rotate the wire bezel to vertical (show as above). (The current flow towards the left shown as above) Third step: Installing the mutual inductor correctly refers to the current flow (The current flow towards downward as above). (The current flow towards the right shown as above) Fourth step: Close the mutual inductor and put down the wire bezel, and make the wire beside the pricking needle hole, then rotate tightly the screw arbor (show as above) Fifth step: Rotating the pricking needle screw arbor, and then tight the screw arbor, making cross...
Open the catalog to page 5AEW100 ■ Installing description of W type without piercing L1, L2, L3 place on A, B, C phase respectively. A、B、C three-phase voltage signal lines are connected to UA, UB, UC terminals respectively, neutral line is connected to the N terminal. And especially the A phase and N terminal powered for the AEW100. And A, B, C phase transmits the voltage and current to AEW100 by mutual inductor, and then the AEW100 transmits the single to PC via RS485. Note: CG is optional after selecting W, which means taking voltage from magnetic steel. Blue Yellow Blue Yellow
Open the catalog to page 6Dimension of magnet steel Operating and display There are 6 LED lights on the surface of the meter represent for L1, L2, L3, pulse, communication, wireless respectively. L1 light on means L1 phase powered; L2 light on means L2 phase powered; L3 light on means L3 phase powered; Pulse light on each time means one electric pulse output; Communication light will flash while communicating via RS485; Wireless light will flash while communicating via wireless module. Installation and operation instruction