CEJW REVISED AUGUST 2021 ELECTRODE BOILERS FOR LARGE APPLICATIONS HIGH VOLTAGE IMMERSED ELECTRODE HOT WATER BOILERS

Open the catalog to page 1
CEJW - 2

WHY CHOOSE A HIGH VOLTAGE BOILER? OUTPUT MATCHES FUEL BURNING BOILERS Due to considerable advances in High Voltage electric boiler technology for heat or power generation, Immersed Electrode Boilers can match the capacity of large gas or oil-fired boilers (up to 60 MW) while occupying a much smaller footprint. LOWER OPERATING COSTS Immersed Electrode Boilers are simple to operate and maintain with no complex pollution or combustion control equipment required. Users can also take advantage of lower energy rates during daily or seasonal off-peak periods. ECONOMICAL INSTALLATION Operating at...

Open the catalog to page 2
CEJW - 3

ACME IMMERSED ELECTRODE BOILERS FOR EVERY APPLICATION A partial list of possible uses includes: THESE IMMERSED ELECTRODE BOILERS HAVE UNLIMITED APPLICATION POSSIBILITIES WHEREVER A NEED FOR LARGE HOT WATER PROCESS OR SPACE HEATING EXISTS. • Office and apartment buildings • Hospitals, schools, hotels, motels • Food processing Plants • Clothing and textiles plants • Industrial plants • Plastic and chemical plants • Mining Operations • Power plants for District Heating • Car

Open the catalog to page 3
CEJW - 4

CEJW IMMERSED ELECTRODE HOT WATER BOILERS FEATURES: • Capacity range: 2500 to 68,000 KW • Electric Power Supply Voltage : 4160 to 25000 V • Maximum Operating Temperature for Standard Models: 180 °C (360 ° F) • Operating pressure: 3 to 14.5 bar (50 to 200 psi) • Power Feeds (Current Passage) assembled and certified for 42000 V and 16 bar (230 psi) for any operating voltage • Fast Response: 0 to 100 % capacity in: Hot State: 1 minute Cold to Hot state : 15 to 25 minutes (depends on the size) • Economical even for capacities between 2 to 6 MW • Simple controls • Can be added to existing systems...

Open the catalog to page 4
CEJW - 5

SAFER OPERATION There are no combustion hazards because there are no flames, fumes, fuel lines or fuel storage tanks. There is no low water danger since the current cannot flow without water and there are no problems with heat buildup or electrode burnout even if scaling should occur. Thermal shock is eliminated. Electrically safe due to a grounded pressure vessel. A safety enclosure around boiler is not required and expensive isolating piping connections are not required. HOW THE MODEL CEJW WORKS The CEJW operates flooded with water at the selected conductivity. A motorized drive system is...

Open the catalog to page 5
CEJW - 6

STANDARD CEJW HOT WATER BOILER BOILER HEIGHT B mm (Inch) INITIAL CLEARANCE HEIGHT FOR POWER FEED INSERTION mm (Inch) PUMP FLOW RATE m3/hr (gpm)

Open the catalog to page 6
CEJW - 7

CEJW HEATING LOOP COMPONENTS FOR STANDARD MODELS water heats building, plant or storage facilities transferring heating boiler capacity. EXPANSION TANK Expansion tank based on total water content of the loop and its operating pressure. ELECTRICAL • • • • • BOILER • Pressure vessel, ASME (Section I or IV) design, CRN/U stamp pressure vessel registration certificate or CE / PED required • Complete assembled Power feeds tested and certified for 16 bar (230 psi) and 42 KV • Boiler actuator and capacity control system • Large DN 500 (20”) Manhole • Sheet metal jacket and 100 mm (4”) ceramic fiber...

Open the catalog to page 7
CEJW - 8

GUARANTEE All our Immersed Electrode Boilers are guaranteed for one year in operation or 18 months after shipment against defective workmanship and material. Guarantee limited to replacement of defective parts only, when returned, prepaid, to the factory. Copy of guarantee available on request. ACCESSORIES • Isolating valves for boiler, heat-exchanger and centrifugal pump • Piping for the loop • Y strainer, located on the pump suction pipe • Filling water system, connected to the Expansion tank-includes pump, Y strainer, check valve and isolating valves ACCESSORIES FOR CEJW- OUT OF ACME...