40-XP

40-XP

40-XP

Product catalog summary
Applications
  • Energy savings through intermittent operation of ventilation equipment in enclosed areas.
  • Suitable for commercial or industrial locations where a sudden build-up of combustible gases may occur.
  • Applicable in underground parking, boiler rooms, landfills, storage rooms, etc.
  • Can be used as a stand-alone unit with standard analog outputs for direct connection to existing Building Management Systems (BMS) or DDCS.
Features
  • High-accuracy Catalytic Bead (Pellistor) explosion-proof sensor.
  • Explosion-proof enclosure.
  • Available outputs: 4-20mA analog output or optional 0-1V DC, 0-5V DC, or 0-10V DC analog outputs.
  • Remote sensor-transmitter on an RS-485 communication network compatible with Acme’s CEL-Series centralized multipoint/multigas detection and control systems.
Product Overview

The Acme 40-XP Series Combustible Gas Sensors-Transmitters are designed for the detection of Methane (CH4), Propane (C3H8), Butane (C4H10), Hydrogen (H2), and other combustible gases. The sensor-transmitter measures the concentration of target gases in enclosed areas and produces a proportional analog output signal. It features a diffusion-type catalytic bead sensor for broad-range gas detection, ensuring instantaneous detection and long-term reliability.

The 40-ST series is designed to act as fixed in-situ safety monitors, automatically operating mechanical ventilation systems upon detection of combustible gases, thus protecting occupants and sensitive goods. It meets code requirements economically using commercial-grade gas detection equipment.

Specifications
  • Gases Detected: Methane, Propane, Hydrogen, etc.
  • Sensor Technology: Catalytic Bead (Pellistor) type.
  • Sensing Method: Diffusion.
  • Power Requirements: 24V AC 50/60Hz.
  • Outputs Available: 4-20mA, 0-1V DC, 0-5V DC, 0-10V DC, RS-485.
  • Operating Temperature: -4ºF to 120ºF (-20ºC to +50ºC), with extended range available.
  • Humidity Range: 10-95% RH.
  • Accuracy: +/- 5% of calibrated value.
  • Repeatability: 2% of signal.
  • Response Time (T90%): < 30 seconds.
  • Expected Lifetime: 3 years.
  • Enclosure: Explosion Proof - Class 1.
  • Dimensions: 11” (L)x Φ4”(D)x 3”(D) (279mm x 101mm x 75mm).
Model Numbers and Gas Detection Range
  • CH4-ST-XP-X*: Methane 0-40% LEL
  • C3H8-ST-XP-X*: Propane 0-40% LEL
  • H2-ST-XP-X*: Hydrogen 0-40% LEL
  • C4H10-ST-XP-X*: Butane 0-40% LEL
  • CH4O-ST-XP-X*: Methanol 0-40% LEL
Output Signal and Options

Output signals include 4-20mA, 0-1V DC, 0-5V DC, 0-10V DC, and RS-485 for CEL systems only. Installation and maintenance instructions must be closely followed.

Contact Information

In Canada: Acme Engineering Prod. Ltd., Montreal, Quebec. Tel: (514) 342-5656. Email: [email protected]

In the USA: Acme Engineering Prod. Inc., Mooers, N.Y. Tel: (518) 236-5659.

See more

Catalog excerpts

40-XP-1

For detection of Methane (CH 4 ), Propane (C 3 H 8 ), Butane (C 4 H 10 ), Hydrogen (H 2 ) and other Combustible Gases Features • igh-accuracy Catalytic Bead H (Pellistor) explosion proof sensor. • Explosion Proof enclosure • -20mA analog output or 4 optional 0-1V DC, 0-5V DC or 0- 10V DC analog outputs. • emote sensor-transmitter R on a RS-485 comunication network compatible with Acme’s popular CEL-Series centralized multipoint/multigas detection and control systems. • nergy savings through the E intermittent operation of ventilation equipment in enclosed areas. • ommercial or industrial locations C where a sudden build-up of combustible gases may occur. • nderground parking, boiler rooms, U landfills, storage rooms, etc. • tand-alone with standard analog S outputs for direct connection to the existing Building Management System (BMS) or DDCS. he Acme Combustible gas sensor-transmitter measures the concentration of the target gas in an enclosed area and produces a proportional analog output signal. The Acme 40-ST Combustible Gas sensor is explosin proof. The enclosure of the sensor-transmitter is a explosion proof enclosure. The 40-ST series employs a diffusiontype catalytic bead (pellistor) sensor capable of detecting a broad range of combustible gases. It provides instantaneous detection of these coumponds and has long term reliability and trouble free operation. With the increased use of gas detection in maintenance and industrial facilities, the 40-ST allows installers and users to meet code requirements in an economical fashion using commercial-grade gas detection equipment. Designed to act as fixed in-situ safety monitors, the 40-ST sensor-transmitter automatically operates the mechanical ventilation system of a facility upon detection of combustible gases, thereby protecting occupants, personnel and gas-sensitive goods and products. The 40-ST contains all the wellknown standard features of ACME’s gas detection line; a robust enclosure, the latest sensor technology and state-of-the-art electronics. For more versatile gas detection options, consult the ACME b

 Open the catalog to page 1
40-XP-2

Ordering Information Standard unit specifications Gases detected: Methane, Propane, Hydrogen, etc. MODEL NUMBER Sensor Technology: Catalytic Bead (Pellistor) type. Sensing Method: Diffusion. P ower Requirements: 24V AC 50/60Hz. Outputs Available: Operating Temp.: -4ºF to 120ºF (-20ºC to +50ºC)* Humidity Range: 10-95% RH Accuracy: +/- 5% of calibrated value Repeatability: 2% of signal Response Time (T90%): < 30 seconds Expected Lifetime: 3 years Enclosure: Explosion Proof - Class 1 Output Signal and other Options *X OUTPUT SIGNAL * Extended temperature range available. Explosion Proof mounting...

 Open the catalog to page 2

All Acme Engineering Products Ltd. catalogs and technical brochures

  1. Y Strainers

    5  Pages

  2. FB1 SERIES

    2  Pages

  3. WGH-TS

    4  Pages

  4. CEJW

    8  Pages

  5. GS

    4  Pages

  6. TW-ECH

    2  Pages

  7. COV-2

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.