High Performance Power and Energy Meter
18Pages

{{requestButtons}}

Catalog excerpts

High Performance Power and Energy Meter - 1

High Performance Meters Real Time Metering Waveform Capture Data Logging Revenue Grade with Data Logging Waveform Capture Modbus, BACnet, SNMP DNP3.0 Level 2 Free Cloud Metering Data Storage + Analytics

Open the catalog to page 1
High Performance Power and Energy Meter - 2

Acuvim II Series High Performance Meters 100ms Refresh 0.2 Class 400 Parameters DNP 3.0 BACnet 16 MB Memory NEMA 3 5 Year Warranty DESCRIPTION The Acuvim II series are high-end multifunction power and energy meters manufactured by Accuenergy. They are the ideal choice for the monitoring and controlling of power distribution systems. The Acuvim II series may be used as data gathering devices for intelligent power distribution systems or plant automation systems. All monitored data is available via a digital RS485 communication port running Modbus RTU and DNP 3.0 protocols, additional...

Open the catalog to page 2
High Performance Power and Energy Meter - 3

Top quality components are meticulously engineered into a line of products offering best-in-class capability that exceeds the toughest standards and ratings. • 100ms Refresh, True-RMS Measuring Parameter • ANSI C12.20 (0.2 Class) and IEC 62053-22 (0.2S Class) • 16 MB Onboard Memory • Power Quality Analysis • Over/Under Limit Alarm • Multiple Communication Ports (E.g: Ethernet, RS485) • Supports Modbus RTU, DNP 3.0, BACnet IP, BACnet MS/TP • Web Server and Email Sending, SNTP • Switch Status Monitoring • Waveform Capture • Measure Individual Harmonics from 2nd to 63rd • Physical...

Open the catalog to page 3
High Performance Power and Energy Meter - 4

Metering • Voltage V1, V2, V3, Vlnavg, V12, V23, V31, Vllavg • Current I1,I2,I3, In, lavg • Power P1, P2, P3, Psum • Reactive Power Q1, Q2, Q3, Qsum • Apparent Power S1, S2, S3, Ssum • Frequency F • Power Factor PF1, PF2, PF3, PF • Energy Ep_imp, Ep_exp, Ep_total, Ep_net, Epa_imp, Epa_exp, Epb_imp_Epb_exp, Epc_imp, Epc_exp • Reactive Energy Eq_imp, Eq_exp, Eq_total, Eq_net, Eqa_imp, Eqa_exp, Eqb_imp, Eqb_exp, Eqc_imp, Eqc_exp • Apparent Energy Es, Esa, Esb, Esc • Demand Dmd_P, Dmd_Q, Dmd_S, Dmd_I1, Dmd_I2, Dmd_I3 • Load Features • Four Quadrant Powers Monitoring • Power Quality • Voltage...

Open the catalog to page 4
High Performance Power and Energy Meter - 5

Data Logging Acuvim IIR/IIE/IIW offers 3 assignable historical logs where the majority of the metering parameters can be recorded. The onboard memory is up to 8 MB and each log size is adjustable. A real time clock allows for any logged events to be accurately time stamped. Flexible Current Input Compatible with different current transformers such as 5A, 1A, 80mA, 100mA, 200mA, 333mV output CT and Rogowski coil all available from Accuenergy. Time of Use Users can assign up to 4 different tariffs (sharp, peak, valley and normal) to different time periods within a day according to the billing...

Open the catalog to page 5
High Performance Power and Energy Meter - 6

• Function; ® Option; Blank NA

Open the catalog to page 6
High Performance Power and Energy Meter - 7

6x digital inputs 24Vdc power for digital inputs 2x relay outputs 4x digital inputs 2x digital outputs 2x analog outputs 4x digital inputs 2x relay outputs 2x analog inputs Communications Protocols A standard RS-485 port and our AXM line of plug-in expansions modules support a wide array of protocols. Standard

Open the catalog to page 7
High Performance Power and Energy Meter - 9

INPUT Current Inputs (Each Channel) Nominal Current ①0~10A, ②0~2A, ③0~1.2A,④0~1.2A, ⑤0~1.2A Metering Range ①5mA, ②1mA, ③5mA, ④5mA, ⑤5mA, Pickup Current 20Arms Continuous, 0.1% of Nominal Withstand                  100Arms for 1 second, Non-Recurring    Burden             0.05VA (Typical) @ 5Arms Accuracy         0.2% Full Scale Voltage Inputs (Each Channel) Nominal Full Scale Withstand Input Impedance Metering Frequency Pickup Voltage Accuracy Energy Accuracy Active Reactive   400Vac L-N, 690Vac L-L (+20%) 1500Vac Continuous 2500Vac, 50/60Hz for 1 Minute 2Mohm per Phase 45Hz~65Hz, 300Hz ~...

Open the catalog to page 9
High Performance Power and Energy Meter - 10

TYPICAL WIRING WITH 5A/1A CTs 3 Phase 4 Wire with PT (3LN, 3CT) LINE Terminal Block 3 Phase 3 Wire with PT and 2 CT(2LL, 3CT)* Relay Output Single Phase 3 Wire (1LL, 2CT) Single Phase 2 Wire (1LN, 1CT) Digital Input Power Supply DO Type Relay Control Pulse Output 10K Alarm Output Buzzer Relay Output (RO) Wiring *Note: 2CT configuration is optional only in 3 Phase 3 Wire system. Terminal Block Terminal Block Digital Input Terminal Block Energy Output (DO) Wiring

Open the catalog to page 10
High Performance Power and Energy Meter - 11

TYPICAL WIRING RCT/mV/mA CURRENT INPUT Terminal Block 3 Phase 3 Wire with PT and 3CT(2LL, 3CT)* 3 Phase 4 Wire with PT (3LN, 3CT) Terminal Block Single Phase 3 Wire (1LL, 2CT) Single Phase 2 Wire (1LN, 1CT)

Open the catalog to page 11
High Performance Power and Energy Meter - 12

Multifunction Power Meter Front View Side View DIN Mount Meter Dimensions Note: the 1 display module is connected with the body length of 2 meters, Unit : mm External Displayneed for a longer line, please order statement; (inches) such as the Module Dimensions Multifunction Power Meter Rear View Side View Front View Side View Note: 1. Display module is connected with a six foot 10 pin RJ45 cable, if you need a longer cable please specify that in the ordering statement. 2. Display module opening size and Acuvim II body openings are exactly the same size. Communication Module Dimensions 90.00...

Open the catalog to page 12
High Performance Power and Energy Meter - 13

Acuvim II Series DIN Rail Mounting Adapter Acuvim II Series DIN Rails adapter provide easy installation of panel-mount Acuvim II series meter on DIN rail in all models and IO options. DIMENSIONS 3.54” (90mm)

Open the catalog to page 13
High Performance Power and Energy Meter - 14

Accuenergy's flexible Rogowski coil is designed for use where regular solid or split core current transformers cannot fit, and is ideal for power quality monitoring such as harmonics. Advantages of the Rogowski coil include; high accuracy, wide measurement and frequency range with no additional integrator or power supply needed. Current Input Ranges' Frequency Range Accuracy Lead Polarity Operating Tempreture Temperature Drift Material Dielectric Strength 5A-1200A 12.5A-3000A 25A-6000A 50A-12000A 250A-50000A 20Hz - 5kHz 0.5% White-Positive, Brown-Negative, Bare-Shield; 24AWG Arrow Towards...

Open the catalog to page 14
High Performance Power and Energy Meter - 16

Note: 1. Accuenergy suggests using USB-RS485 converter for configuration, and 3 CTs per three phase circuits. 2. All fields must be completed to create a part number. 3. Add “-S” after power supply for anti-tampering seal option. 4. Contact Accuenergy for 400 Hz frequency option; Acuvim IIW doesn't support this type. Communication Option Module: Remote Display Option: REM-I I-DS2: Compatible with Acuvim II Series "M" (DIN Mount) Models Only I/O Option module: AXM-IO1 AXM-IO2 Logic Module 1 a Logic Module 2 |j2 Logic Module 1 1 Analog Output Type Analog Output Type WEB-PUSH : DNP 3.0 Over...

Open the catalog to page 16

All Accuenergy Canada Inc. catalogs and technical brochures

  1. CATALOGUE

    40 Pages