DIO 122

DIO 122

Product catalog summary
Overview: The DIO 122 Series is a dual-output DC-DC converter designed for high isolation voltage applications, such as high power gate drives, medical equipment, and transportation. It features a 20kVac isolation input/output and is corona-free at 12kVac.
Specifications:
  • Input Voltage: Options include 24Vdc, 48Vdc, and 125Vdc. Other inputs available upon consultation.
  • Isolation: 1.5kVdc input to chassis, 20kVac input to output, and 20kVac output to chassis.
  • Output Voltages: Two independent outputs ranging from 12V to 24V, up to 3A each.
  • Efficiency: Minimum 80% at full load.
  • Operating Temperature: 0ºC to 50ºC without derating.
Protection and Standards:
  • Input Protection: Includes inrush current limiting, varistor, reverse polarity protection, and internal safety fuse.
  • Overload Protection: Features rectangular current limiting with short circuit protection.
  • Standards Compliance: Designed to meet EN60950-1 and related UL & CSA standards.
Environmental and Physical Characteristics:
  • Cooling: Convection cooled, no fan required.
  • Environmental Protection: Basic ruggedizing and partial encapsulation with thermally conductive silicon potting compound.
  • Dimensions and Weight: Open board dimensions are 102 x 305mm with a component height of 70mm, weighing 1.1kg.
Additional Information: ABSOPULSE power supplies are customizable to meet specific customer requirements. The company has been designing and manufacturing quality converters and related systems since 1982.
See more

Catalog excerpts

DIO 122-1

120W, Corona-free, 20kV Isolation Voltage, Dual Output DC-DC Converter DIO 122 Series • • • • • • 20kVac isolation input/output, output/chassis Corona free at 12kVac Rugged, industrial quality Convection cooled - no fan Dual output – 60W each Full electronic protection This series of dual-output DC-DC converters was developed for very high operating isolation voltage. Typical applications are high power gate drives, medical equipment, transportation and similar areas. The unit is designed and tested for corona (partial discharge) extinction at a minimum of 12kVac and Hi-POT tested for 20kVrms isolation. The typical operating voltage potential between primary and secondary is 6.5 – 10kVac, with the same isolation provided between the two outputs. Both outputs are highly regulated and have individual current limiting and short circuit protection. Isolation design features include encapsulating the output regulators in two separate insulation chambers, and the use of transformers engineered with ABSOPULSE’s field-proven proprietary technology. Output Voltages Two independent outputs: Any voltage in the range of 12V to 24V and up to 3A on each output. Consult factory for other voltages Input Protection Inrush current limiting Varistor Reverse polarity protection by crowbar diode Internal safety fuse Lower voltage than the specified minimum will not damage the unit Redundancy diode None Available as option Isolation 1.5kVdc input to chassis, 20kVac input to output, 20kVac output to chassis 20kVac output 1 to output 2 Corona extinction 12kVac minimum for the transformer Dynamic Response Max 5% voltage deviation for 10% to 50% load step, with better than 1msec recovery time Standards Designed to meet EN60950-1 and related UL & CSA standards EMI EN 55032 Class A with margins Switching Frequency: 100kHz ±5kHz 50kHz ±5kHz (for 24V input) Line/Load Regulation ±1% combined from zero load to full load including output separation diode Output Ripple/Noise Better than 200mV peak to peak or 40mVrms (20MHZ BW) Overload Protection Rectangular current limiting with short circuit protection. Current Limit set to: 3.5A ±0.4A Output Over-voltage Protection 30V transzorb on output Efficiency Min 80% at full load Operating Temperature 0ºC to 50ºC for full specification without derating Temperature Drift 0.03% per oC over operating temperature range Cooling By convection Environmental Protection Basic ruggedizing and partial encapsulation in the chambers with thermally conductive silicon potting compound with UL94V-0 flammability rating. Indicators Green “Output ON” LED in each chamber Control Input None Alarm Output None Package Dimensions Open board: 102 x 305mm (4” x 12”) Component height: 70mm (2.75”) Weight 1.1kg (2.4lb) Connections Input: 3-pole barrier-type terminal block with 3/8” spacing Outputs: 2-pole barrier type terminal block inside the chamber RoHS Compliance Compliant MTBF 150,000 hours at 45oC per internal module Demonstrated MTBF is significantly higher. Warranty Two years subject to application within good engineering practice Please note that ABSOPULSE power supplies are designed and built to customer specifications. The specifications on this data sheet are generic and will vary depending on input/output configuration and other customer requirements. Generic specifications are subject to change Designer and manufacturer of quality converters, inverters, UPS systems, complete rack mount systems and DC-input fluorescent lamp inverters since 1982. Custom or standard. ABSOPULSE is a BABT-approved Facility ABSOPULSE ELECTRONICS LTD 110 Walgreen Road, Ottawa. Ontario | K0A 1L0 | CANADA Tel: +1-613-836-3511 | Fax: +1-613-836-7488 https://absopulse.com/contact | http://www.absopulse.com Copyright: This document is the property of ABSOPULSE Electronics Ltd Its content is proprietary and may not be reproduced in html text or any other format. Proprietary notices may not be deleted from data sheets or from other materials downloaded from https://absopulse.com/

 Open the catalog to page 1

Archived catalogs

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.
About DirectIndustry
DirectIndustry is a marketplace that offers B2B players a complete experience, from product sourcing to purchase. DirectIndustry is an entity of VirtualExpo Group.