Catalog excerpts

DESIGN ♦ MANUFACTURE ♦CONSULTANCY TM ABBEY electronic controls Abbey House 19-21 Fleet Street Pemberton Wigan WN5 ODU England MO 21V MODULATING PUMP CONTROLLER FOR HEATING SYSTEM CONTROL (OEM COPY) This document may be updated at any time without notification. It is therefore advised that a check is made to see if there is a later release copy.
Open the catalog to page 1
INTRODUCTION 1.1. The M021P is a modulating temperature controller. Its function is to regulate the final flow temperature out of a heat exchanger by regulating the flow rate through the primary of the same heat exchanger. It does this by modulating the voltage applied to the pump which circulates water through the primary of the heat exchanger. The general principle is illustrated in the appendix. 1.2. Consequently, the M021P is not a "Safety Control" but is nonetheless designed and approved to the prevalent standard of EN 60730-1 which includes electromagnetic compatibility (EMC). 1.3. In...
Open the catalog to page 2
2.1 The M021P is equipped with two blocks of screw terminals; one for high voltage (mains) interface and the other for low voltage isolated interface. 2.2 The following detail the connections which have to be made to the M021P. 2.3.1 Pins 1&2 are the contacts of an on-board change-over relay. The common pin is connected internally to permanent live and is not available externally. Thus pin 1 (normally closed) is live in the relay's normal state. When the external flow switch connection to the board is closed the relay gets powered and changes over to the energised state making pin 2 live...
Open the catalog to page 3
There is also an optional pin header, TB3. Normally, temperature range is preset with an on-board preset potentiometer, RV2. When the OEM requires it, a 3 way pin header is inserted in place of RV2 thus allowing temperature range control via a remotely mounted potentiometer.
Open the catalog to page 4
(No condensation) Power Consumption:- (Excluding all peripherals) Maximum 2 Temperature Range:-OEM Specifiable. Default 40 - 60 ±3 Earthing should be suitably provided on the appliance by the OEM. The control itself does not need an earth. The whole board is protected with a 20 mm fuse, FS2. The value is marked on as T2A and is factory fitted as T2A. The relay contacts and tracks are rated for a 3A current. Therefore, if the OEM requires it, it is recommended that the fuse rating may be changed to an appropriate value no greater than T3A. In this case, the new value must be printed...
Open the catalog to page 5
Flow Switch:- Volt-free, normally open. Closed for flow. Mechanical Details:- Holes Pitch Rectangle 110x70
Open the catalog to page 6
To ensure that the pump is never run at an r.p.m. which is likely to result in stalling the OEM must ensure that a minimum voltage is set as follows.
Open the catalog to page 7
I declare that the information provided above is true and that all the tests have either been carried out by myself or under my supervision. The control has been tested and certified to comply with relevant sections of EN60335. Third party certificates of independent tests will be supplied on request.
Open the catalog to page 8
2. TYPICAL PERFORMANCE CURVES
Open the catalog to page 9
CONFIDENTIAL INFORMATION TYPICAL HYDRAULIC SYSTEM FOR MQ21P MODULATING PUMP CONTROLLER NO M021-HS ALL RESISTORS 0.25U 5X FILL ZENERS 0.5U ALL DlflENTIONS IN nn DIM'S TO 1DP= ±0. 1 en DIM'S TO 2DP= ±0.02 nm ANGLES TO ±0.3° SCALE = 100X UNLESS STATED OTHERUISE
Open the catalog to page 10
TITLE:- WIRING DIAGRAM FOR M021P ORTE:- ALL RESISTORS 0.25U 5J4 ALL ZENERS 0.5U ALL DIMENTIONS IN mn DIM'S TO 1DP= ±0.1 nia DIM'S TO 2DP= ±0.02 nu ANGLES TO ±0.5° SCALE = 100X UNLESS STATED OTHERUISE
Open the catalog to page 14
CONFIDENTIAL INFORMATION THE ART OF CONTROLS AMP CONNECTOR-FEMALE ---> 280590 CRIMPS —> 182198-1 ELECTRICAL SPECIFICATION _l LOlu a my t—i cr Q£ O' £ LU CD*? £ cr z imn it iis V) -Z I ks>qq.cl\X O hqq +S> i—un>—x-cn s IOQJZ ox-W.UUUOOI-inzcn-i- ii LJLiJt—* in acNouiuniiui _l *-<ZO UJ GQ O 02 o a. in in Q£ CE O O' t- m in t— Q 3E *-H DC 3 LU O x in
Open the catalog to page 16All Abbey Electronic Controls catalogs and technical brochures
-
AEC
1 Pages
-
WSX53
4 Pages
-
WSX53G06 PRECIPITATION
4 Pages
-
FX37SPT IGNITION CONTROL BOX
1 Pages
-
WSX53B WEATHER SENSOR
4 Pages
-
FX37FSA
1 Pages
-
WSX53A48 PRECIPITATION
4 Pages
-
FX37-P16
1 Pages
-
WSX53A24 PRECIPITATION
4 Pages
-
WSX53A12 PRECIPITATION
4 Pages
-
WSX53A06 PRECIPITATION
4 Pages
-
FQ37SPT IGNITION CONTROL BOX
1 Pages
-
MPC34A DUAL MODE
2 Pages
-
WSX53