— PowerLine DPA 20 – 120 kVA Full power for industrial applications PowerLine DPA 20 – 120 kVA Full power for industrial applica
Open the catalog to page 1— Smooth power in rough places — 01 In DPA, each UPS module has all the hardware and software it needs for autonomous operation. For many industries, the consequences of electrical power loss can be disastrous: Production lines may have to go through a complex and costly restart; expensive product may be ruined; valuable production time can be lost; process equipment can be damaged; and safety issues may arise. Because a reliable supply of clean power usually cannot be guaranteed by the grid, ABB’s PowerLine DPA UPS (uninterruptible power supplies) makes sure that the operation of industrial...
Open the catalog to page 2High serviceability One major advantage of DPA is that the modules can be swapped online, ie, removed or inserted without the need to power down or transfer to raw mains supply and without risk to the critical load. This unique aspect of modularity directly addresses continuous uptime requirements, significantly reduces MTTR (mean time to repair), reduces inventory levels of specialist spare parts and simplifies system upgrades. Modularity pays off too when it comes to serviceability: local service personnel do not need special skills, visiting service engineers spend less time on site, and any...
Open the catalog to page 3— PowerLine DPA Product features At the heart: the module • Featuring ABB’s exclusive DPA • IGBT rectifier and inverter • Online swap capability, MTTR <30 min • Service panel for maintenance and operation of each individual module • Monitored fans • Redundant fans (optional) • Tropicalization and anti-corrosion (optional) Superior electrical performance* • Efficiency up to 96% (3ph); up to 94% (1ph) • Input power factor 0.99 • Input THDi <4% • 2.7 x Inom (3ph); 2.4 x Inom (1ph) • Output THDv <2% • 100% unbalanced load capability • All phases regulated independently Wide suite of interfaces &...
Open the catalog to page 4Power and redundancy for demanding industrial applications • 3-ph: 20-120 kVA with N and N+N configurations • 1-ph: 20-80 kVA with N and N+1 configurations • Possibility to run frames in parallel (up to 30 modules max.) Full range of electrical and functional options • Cold/black start (optional) • Synchronization kit (optional) • Battery temperature sensor (optional) • Battery-wrong polarity diode* (optional) Total onboard protection • Rectifier and bypass input breakers • Rectifier input switch • Output switch • Integrated manual bypass switch Optional transformers • Providing galvanic separation...
Open the catalog to page 5With its modular architecture, the PowerLine DPA uninterruptible power supply makes it easy and cost-effective to support all your 3ph and 1ph industrial applications.
Open the catalog to page 6— Tough meets rough — 01 Rail control & signaling system — 02 Paging & Information system — 03 Control & Automation system — 04 Lighting system — 05 Instrumentation/ sensor and valves — 06 Telcom system — 07 Security systems — 08 Industrial Infrastructure A UPS for rough conditions The guarantee of a continuous supply of clean power for their critical operations has become an essential prerequisite for the success of many enterprises. The PowerLine DPA UPS, designed to withstand the rigors of rough industrial environments, can provide this guarantee. PowerLine DPA’s modular architecture makes...
Open the catalog to page 8Remote monitoring In a power fail situation, it is important for all relevant personnel to be quickly and fully informed of the system status. For this reason, the PowerLine DPA UPS can be supplied with relay boards and a network management card that provide connection to a DCS (distributed control system) or SCADA (supervisory control and data acquisition) system via SNMP, Modbus TCP, Modbus RS 485 or Profibus. These interfaces allow: • Environmental monitoring • Extensive alarm handling and dispatching • Redundant UPS monitoring • Integration of PowerLine DPA into multivendor and multiplatform...
Open the catalog to page 9— PowerLine DPA Technical specification General data System power range Nominal power / frame Number of UPS modules Output power factor Topology UPS configuration UPS type Input Nominal input voltage Voltage tolerance (referred to 3 × 400 / 230 V) Input distortion THDi Frequency Power factor Output Rated output voltage Voltage distortion (referred to 3 × 400/230 V) Frequency Overload capability Output short capability Unbalanced load Crest factor Efficiency Overall efficiency / transformerless In eco-mode configuration Environment Storage temperature Operating temperature Humidity Altitude configuration...
Open the catalog to page 10— Available models (three-phase and single-phase) Cabinet type Weight in kg (without transformers) — Available models (1ph / N+1 configuration) Cabinet type Weight in kg (without transformers) UPS standard configuration • 3ph or 1ph online double conversion UPS • Decentralized Parallel Architecture • Housed in an industrial metal enclosure, IP31, RAL 7035, bottom cable entry • Halogen free cable • Forced ventilation with monitored fans • Input, bypass and battery protection • Manual bypass switch • Integrated back-feed protection • HMI interface with graphical display, control push keys, UPS...
Open the catalog to page 11© Copyright 2017 ABB. All rights reserved. Specifications subject to change without notice. © Copyright ABB. All rights reserved. Specifications subject to change without notice.
Open the catalog to page 126 Pages
6 Pages
6 Pages
60 Pages
6 Pages