1. Catalogs
  2. ABB Smart Power
  3. PMAFIX Pro - NKIS-M - Fitting

PMAFIX Pro - NKIS-M - Fitting

PMAFIX Pro - NKIS-M - Fitting

PMAFIX Pro - NKIS-M - Fitting

Product catalog summary
Overview: The PMAFIX Pro - NKIS-M is a straight, female metric metal thread fitting designed for flexible non-metallic conduits. It is suitable for applications requiring high technical standards under demanding environmental conditions.
Features & Benefits:
  • High impact resistance, even at low temperatures.
  • Strong connection to conduit and mating parts.
  • Easy push-in assembly ensures correct installation.
  • Requires a screwdriver for dismantling, preventing unauthorized access.
  • Space-saving design with no extra room needed for dismantling.
  • Compatible with both fine (T) and coarse (G) conduit profiles.
Ingress Protection: Rated IP66, IP68, and IP69 according to EN/IEC 60529, even with continuous motion.
Materials:
  • Fitting body: High-grade polyamide 6.
  • Locking and sealing element: Polyamide 6 and crosslinked polyester elastomer.
  • Thread: Nickel-plated brass.
Compatibility: Compatible with PMAFLEX Pro, Multilayer, and Smart Line Conduits.
Standards & Compliance:
  • Conforms to EN 45545-2 HL3, NFPA 130, UL 94 (V0), and UL 1696.
  • RoHS and REACH compliant.
Weathering & Chemical Properties: Excellent UV resistance and weathering characteristics. Free from halogens and cadmium.
Mechanical Properties:
  • Tensile modulus: 1,200 - 3,700 N/mm² (ISO 527).
  • Tensile strength: 45 - 65 N/mm² (ISO 527).
  • Notched bar impact test: 4 - 20 kJ/m² (ISO 180/1C).
Thermal Properties:
  • Continuous application temperature: -50 to +105°C.
  • Upper application temperature: +120°C for 20,000 hours.
  • Short-term temperature: +160°C for 168 hours.
Fire Safety Properties:
  • Non flame-propagating (IEC EN 61386).
  • Flame class V0 (UL 94).
  • Fire hazard level HL3 (EN 45545-2).
  • Oxygen index > 32% (EN ISO 4589-2).
  • Smoke density < 150 Ds max. (EN ISO 5659-2).
  • Toxicity < 0.75 CITNLP (NF X 70-100-1/-2).
Product Selection: Various part numbers available with different thread and conduit sizes, dimensions, and weights.
Assembly Instructions: Refer to www.pma.ch for detailed assembly instructions and data sheet No. 26990 for the KNH2 locking and sealing element.
Contact Information: ABB Switzerland Ltd, PMA Cable Protection, Aathalstrasse 90, 8610 Uster, Switzerland. Phone: +41 58 585 00 11, Email: [email protected], Website: www.pma.ch
See more

Catalog excerpts

PMAFIX Pro - NKIS-M - Fitting-1

TECHNICAL DATA SHEET PMAFIX Pro - NKIS-M - Fitting Straight, female metric metal thread IP68 & IP69, two piece metal thread fitting for flexible non-metallic conduit Features & Benefits: • Very high impact resistance - even at very low temperatures • High connection strength - to conduit and mating parts on thread side • Easy push-in assembly - guarantees correct installation • Screwdriver required for dismantling - impeding unauthorized or accidental opening • Space-saving construction - no additional room required for dismantling • Universal - fits both conduit profiles - fine (T) and coarse (G) Ingress protection: • IP66, IP68 & IP69 (EN/IEC 60529) Even when the conduit connection is continually in motion Materials: • Fitting body: high-grade, specially formulated polyamide 6 • Locking and sealing element: made from specially formulated, polyamide 6 and crosslinked polyester elastomer • Thread : nickel-plated brass Compatible with: • PMAFLEX Pro Conduits • PMAFLEX Multilayer Conduits • PMAFLEX Conduits • PMA Smart Line Conduits Conforms to: • EN 45545-2 HL3 (R22 & R23) • NFPA 130 • UL 94 (V0) • UL 1696 (UL file E80294) Weathering resistance: • Very good UV resistance and weathering characteristics Colour: • Black Chemical properties: • Please refer to www.pma.ch (Technical Information / Chemical Resistance) Environmental properties: • Free from halogens and cadmium • RoHS and REACH compliant Applications: • For applications with the highest technical requirements un

 Open the catalog to page 1
PMAFIX Pro - NKIS-M - Fitting-2

Product selection: Part no. Thread size Conduit size Packing unit Our customer service dept. or local distribution partner will be pleased to help you concerning product availability and lead time

 Open the catalog to page 2
PMAFIX Pro - NKIS-M - Fitting-3

Mechanical Properties: Test parameters: Tensile modulus Tensile strength Notched bar impact test Vibration and shock standard Thermal properties: Test parameters: Test method: Continuous application temperature Upper application temperature Test parameters: Test method: Fire safety properties: Fire performance Flame class Fire hazard level Oxygen index Smoke density Fire hazard level Oxygen index Smoke density Fire performance NFPA 130: - Smoke density Heat and visible smoke Smoke emission toxicity Smoke emission toxicity Content of delivery: • Female Fitting body • Locking and sealing element...

 Open the catalog to page 3

All ABB Smart Power catalogs and technical brochures

  1. Bus couplers

    3  Pages

  2. SlimLine XR

    52  Pages

  3. SACE Emax 2

    277  Pages

  4. TruOne

    68  Pages

  5. OFAM/ OFAA

    2  Pages

  6. SACE Tmax XT

    8  Pages

  7. ABB Division

    17  Pages

  8. V400

    2  Pages

  9. V16

    2  Pages

  10. P42E

    2  Pages

  11. Nightstar

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.