1. Catalogs
  2. ABB Oy Distribution Automation
  3. PRODUCT GUIDE RET615 Transformer protection and control
video corpo

PRODUCT GUIDE RET615 Transformer protection and control

PRODUCT GUIDE RET615 Transformer protection and control
1 / 56 PagesView full catalog

PRODUCT GUIDE RET615 Transformer protection and control

Product catalog summary
Description
RET615 is a transformer protection and control relay from ABB's Relion® product family, designed for power transformers in utility and industrial power distribution systems. It supports communication protocols like IEC 61850, Modbus®, and DNP3, ensuring interoperability between substation automation devices.
Standard Configurations
RET615 is available in two standard configurations, B and F, customizable via the Protection and Control Relay Manager PCM600. These configurations support various logical elements and protection functions tailored to specific application needs.
Protection Functions
The relay offers multi-slope stabilized transformer differential protection, instantaneous stage protection, and sensitive restricted ground-fault protection. It includes thermal overload protection and multiple stages of short circuit, phase overcurrent, negative-sequence, and ground-fault backup protection. Optional arc fault protection is available for enhanced safety.
Application
RET615 provides main protection for two-winding power transformers and power generator-transformer blocks. It supports configurations for transformers with solidly grounded LV side neutral or with a neutral grounding resistor, and includes phase-voltage protection and measurement functions.
Supported Solutions
The 615 series protection relays, along with the Substation Management Unit COM600F, offer comprehensive solutions for substation automation and management.
Specifications
The 615 series relays support IEC 61850 Edition 2, including GOOSE messaging and process bus capabilities, offering interoperability and flexibility for power system protection.
System Integration
ABB relays come with connectivity packages for easy configuration using PCM600 and integration with COM600F or MicroSCADA Pro, enhancing substation functionality with a web-based HMI.
Control and Measurements
RET615 relays provide control for circuit breakers and other devices, with configurable binary inputs and outputs, and options for additional analog signal measurements.
Data Recording and Analysis
The relays feature disturbance recorders, event logs, and fault records for detailed analysis, supporting extensive reporting and analysis through COM600F.
Condition Monitoring and Supervision
The relays monitor circuit breaker performance and include trip-circuit and fuse failure supervision, with a self-supervision system to alert operators of faults.
Communication Protocols
The relays support multiple communication protocols, including IEC 61850, Modbus, and DNP3, focusing on interoperability and modern substation applications.
Network Redundancy
The relay offers redundant Ethernet communication with options for optical or galvanic interfaces, supporting high-availability seamless redundancy (HSR) and parallel redundancy protocol (PRP).
Communication Interfaces
The relay supports various communication protocols, including Modbus (RTU, ASCII, TCP) and DNP3 (serial, TCP), allowing simultaneous operation with IEC 61850.
Time Synchronization
The relay supports SNTP, IRIG-B, and IEEE 1588 for time synchronization, with a time-stamping resolution of 1 ms and 4 μs for process bus applications.
Technical Data
Includes detailed tables on power supply, energizing inputs, binary inputs, RTD/mA measurement, signal outputs, and environmental conditions.
Environmental and Compatibility Tests
The relay is tested for electromagnetic compatibility, including burst disturbance, electrostatic discharge, and radio frequency interference, ensuring robust performance.
Protection Functions
Detailed settings and operation characteristics for various protection functions such as overcurrent, ground-fault, and overvoltage protection are provided.
Frequency Protection (FRPFRQ)
Involves parameters such as start value, df/dt, start time, reset time, and operate time accuracy.
Three-phase Thermal Overload Protection (T2PTTR)
Characterized by operation accuracy based on current frequency, with settings including temperature rise and maximum temperature.
Overexcitation Protection (OEPVPH)
Defined by operation accuracy, start time for frequency and voltage changes, reset time, and retardation time.
Stabilized and Instantaneous Differential Protection (TR2PTDF)
Includes operation accuracy, start time, reset time, and harmonic suppression.
Restricted Ground-fault Protection (LREFPNDF)
Characterized by operation accuracy and start time, with settings for operate value and minimum operate time.
Circuit Breaker Failure Protection (CCBRBRF)
Includes operation accuracy, operate time accuracy, reset time, and retardation time.
Arc Protection (ARCSARC)
Defined by operation accuracy and start time, with settings for phase and ground start values.
Multipurpose Protection (MAPGAPC)
Features operation accuracy and settings for start value and operate delay time.
Measurement Functions
Includes three-phase current, sequence current, residual current, and voltage measurements.
Local HMI
The relay features a large display for user interface functionality, including a configurable single line diagram.
Mounting Methods
Relays can be mounted using various methods including flush, semi-flush, and rack mounting.
Relay Case and Plug-in Unit
Relay cases are designed for specific plug-in units with safety features like automatic contacts for short-circuiting CT secondary circuits.
Selection and Ordering Data
ABB Library and Product Selection Tool (PST) are available for generating order numbers and accessing the latest product information.
Accessories and Ordering Data
Tables list order numbers for optical sensors and mounting accessories.
Tools
The protection relay is preconfigured, with parameter settings adjustable via local HMI, Web HMI, or PCM600.
Supported Functions
Tables outline functions supported by Web HMI and PCM600, including relay parameter setting and signal monitoring.
Cyber Security
Features include role-based user authentication, audit trail event storage, and TLS encryption for data protection.
Certificates
IEC 61850 Edition 1 and 2 certificates have been issued for the Relion® 615 series.
Functions, Codes, and Symbols
Detailed tables list protection, control, monitoring, and measurement functions with corresponding IEC 61850 and ANSI codes.
Document Revision History
The document includes a revision history table noting the first release date and product version.
See more

Catalog excerpts

PRODUCT GUIDE RET615 Transformer protection and control-1

PRODUCT GUIDE RET615 Transformer protection and control

 Open the catalog to page 1
PRODUCT GUIDE RET615 Transformer protection and control-2

Description Standard configurations Protection funtions Application Supported ABB solutions Control Measurements Disturbance recorder Event log Recorded data Condition monitoring Trip-circuit supervision Self-supervision Fuse failure supervision Access control

 Open the catalog to page 2
PRODUCT GUIDE RET615 Transformer protection and control-3

016 Inputs and outputs 017  – 021 Station communication 022– 042 Technical data 045 Local HMI 046 Mounting methods 046 Relay case and plug-in unit 046 Selection and ordering data 047 Accesories and ordering data 048 Tools 049 Cyber security 050-051 Terminal diagrams 052 Certificates 052 References 053– 054 Functions, codes, and symbols 054 Document rev

 Open the catalog to page 3
PRODUCT GUIDE RET615 Transformer protection and control-4

— RET615 Transformer protection and control 1. Description RET615 is a dedicated transformer protection and control relay for power transformers, unit and step-up transformers including power generatortransformer blocks in utility and industry power distribution systems. RET615 is a member of ABB’s Relion® product family and part of its 615 protection and control product series. The 615 series relays are characterized by their compactness and withdrawable-unit design. Re-engineered from the ground up, the 615 series has been designed to unleash the full potential of the IEC 61850 standard for...

 Open the catalog to page 4
PRODUCT GUIDE RET615 Transformer protection and control-5

Figure 1. Functionality overview for standard configuration B RET615 V5.0 FP1 ANSI Func Appl B Available with Arc Flash Detection (AFD) option Available with RTD option

 Open the catalog to page 5
PRODUCT GUIDE RET615 Transformer protection and control-6

Figure 2. Functionality overview for standard configuration F RET615 V5.0 FP1 ANSI Func Appl F 382 Available with Arc Flash Detection (AFD) option Available with RTD option — Table 1. Standard configurations Description Transformer differential with low imp. restricted EF on MV side Transformer differential with voltage protection & measurements and low imp. restricted EF on MV side, overexcitation, directional ground protection, and sync-check

 Open the catalog to page 6
PRODUCT GUIDE RET615 Transformer protection and control-7

Table 2. Supported functions

 Open the catalog to page 7
PRODUCT GUIDE RET615 Transformer protection and control-8

Table 2. Supported functions, continued () = optional 1) lo selectable by parameter, lo calculated as default 2) lo calculated is always used 3) IoB calculated and 3IB are always used 4) Uo selectable by parameter, Uo measured as default 5) Uo measured is always used 6) IoB measured and 3IB are always used 7) IoB selectable by parameter, IoB measured as default 8) Must be added with ACT to be available in SMT and in Relay. 9) Master Trip included and connected to corresponding HSO in the configuration only when BIO0007 module is used. If additionally the ARC option is selected, then ARCSARC is...

 Open the catalog to page 8
PRODUCT GUIDE RET615 Transformer protection and control-9

3. Protection functions The relay features three-phase, multi-slope stabilized (biased) stage transformer differential protection and an instantaneous stage to provide fast and selective protection for phase-to-phase short circuit, winding interturn fault and bushing flashover protection. Besides second harmonic restraint, an advanced waveform-based blocking algorithm ensures stability at transformer energization and a fifth harmonic restraint function ensures good protection stability at moderate overexcitation of power transformers. Sensitive restricted ground-fault protection completes the...

 Open the catalog to page 9
PRODUCT GUIDE RET615 Transformer protection and control-10

4. Application RET615 provides main protection for two-winding power transformers and power generatortransformer blocks. The standard configurations offer comprehensive protection functions for detection and elimination of operational disturbance conditions and power transformer faults. Furthermore, the RTD/mA inputs can be used for measuring the ambient air temperature. The RTD inputs also offer thermal protection of dry-type power transformers fitted with Pt-100 temperature sensors. Temperature measurement over the RTD/ mA inputs extends the function of the three-phase thermal overload protection...

 Open the catalog to page 10
PRODUCT GUIDE RET615 Transformer protection and control-11

Figure 3. Illustrates the protection of a two winding power transformer with configuration B. The main protection used in this application example is transformer differential protection. Additionally, Figure 4. Protection of two-winding power transformers feeding a single busbar switchgear arranged into two bus sections separated with bus coupler. restricted ground fault protection with numerical low impedance principal is applied on the transformer’s LV side. Figure 4 Illustrates the protection of the two winding power transformers feeding a double ended substation. In this case configuration...

 Open the catalog to page 11
PRODUCT GUIDE RET615 Transformer protection and control-12

5. Supported solutions The 615 series protection relays together with the Substation Management Unit COM600F constitute a genuine IEC 61850 solution for reliable power distribution in utility and industrial power systems. To facilitate the system engineering, ABB's relays are supplied with connectivity packages. The connectivity packages include a compilation of software and relay-specific information, including single-line diagram templates and a full relay data model. The data model includes event and parameter lists. With the connectivity packages, the relays can be readily configured using...

 Open the catalog to page 12
PRODUCT GUIDE RET615 Transformer protection and control-13

Figure 5. ABB power system example using Relion relays, COM600F and MicroSCADA Pro/ System 800xA Ethernet switch Analog and binary horizontal GOOSE communication 6. Control RET615 integrates functionality for the control of a circuit breaker via the front panel HMI or by means of remote controls. In addition to the circuitbreaker control the relay features two control blocks which are intended for motor-operated control of disconnectors or circuit breaker truck and for their position indications. Further, the relay offers one control block which is intended for motor-operated control of one grounding...

 Open the catalog to page 13
PRODUCT GUIDE RET615 Transformer protection and control-14

7. Measurements The relay continuously measures the high voltage (HV) side and the low voltage (LV) side phase currents and the neutral current of the protected transformer. In addition, the relay calculates the symmetrical components of the currents and voltages, maximum current demand value over a user-selectable pre-set time frame, the active and reactive power, the power factor, and the active and reactive energy values. Calculated values are also obtained from the protection and condition monitoring functions of the relay. Depending on the standard configuration, the relay also measures...

 Open the catalog to page 14