Specifications
  • Input: Compatible with resistance thermometers (Pt100, Ni, Cu), various thermocouples, resistance-type transmitters, and voltage inputs.
  • Output: Provides a configurable 4-20 mA HART signal with a measurement deviation of 0.1 K.
  • Safety and Approvals: Certified for device safety per NE 53, SIL2 according to IEC 61508, and explosion protection approvals including ATEX, IECEx, FM, and CSA.
General Information
  • Electrical Isolation: 3.5 kV DC between input and output.
  • MTBF: 28 years at 60°C ambient temperature.
  • Environmental Conditions: Operates between -40 to 85°C, with vibration resistance up to 5 g and shock resistance up to 30 gn.
Communication and Configuration
  • HART Protocol: Configurable via DTM and EDD.
Electrical Connections
  • Power Supply: Two-wire technology with supply voltage from 11 to 42 V DC for non-ex applications and 11 to 30 V DC for ex applications.
Mechanical Design
  • Dimensions and Weight: Compact design, weighing 180 g, suitable for 35 mm rail mounting.
Measuring Accuracy
  • Accuracy: Includes linearity deviation and reproducibility, with digital accuracy using a 24-bit A/D converter.
Ex Relevant Specifications
  • Details on intrinsic safety and non-sparking specifications for ATEX, IECEx, FM, and CSA standards.
Operating Influences
The document describes the minimal influence of supply voltage and load on performance, with common-mode interference having no effect up to 100 Veff or 50 V DC. Ambient temperature influences are specified for different sensor types.
Communication
The TTR200 supports HART communication, with configuration options for measurement type, sensor type, error signaling, and more. It supports point-to-point, multidrop, and burst modes, with diagnostic signaling per NE 43.
Electrical Connections
Includes diagrams for connecting various sensor types, such as RTDs and thermocouples, and explains the function of LEDs and DIP switches for power and error signaling.
Dimensions
Physical dimensions are provided in millimeters and inches.
Ordering Information
Lists options for explosion protection, communication protocols, configuration, calibration certificates, and documentation languages, with specific order numbers for different configurations and certifications.
Ex Relevant Specifications
Complies with ATEX and IECEx standards for intrinsic safety, with specifications for temperature classes and permissible ambient temperatures. Covers non-sparking ATEX and FM/CSA certifications for different zones and divisions.
Order Form Configuration
Details customer-specific configurations, including sensor types, measurement ranges, and output behaviors, highlighting ABB's global sales and support network.
See more

Catalog excerpts

TTR200 - Rail mounted Temperature Transmitter, HART, Pt100 (RTD), thermocouples, electrical isolation-1

Data Sheet DS/TTR200-EN Rail mounted Temperature Transmitter TTR200 HART, Pt100 (RTD), thermocouples, Electrical isolation Input - Resistance thermometer - Thermocouples - Resistance-type transmitters - Voltages, mV voltages Output - 4 ... 20 mA, HART Measurement deviation - 0.1 K Sensor error adjustment Continuous sensor monitoring and selfmonitoring - Two function LEDs - Supply voltage monitoring - Wire break and corrosion monitoring in accordance with NE 89 Device safety in accordance with NE 53 SIL2 acc. to IEC 61508 Approvals for explosion protection - ATEX, IECEx, Zone 0 - FM / CSA Configuration - DTM - EDD Contents

 Open the catalog to page 1
TTR200 - Rail mounted Temperature Transmitter, HART, Pt100 (RTD), thermocouples, electrical isolation-3

Rail mounted Temperature Transmitter TTR200 DS/TTR200-EN HART, Pt100 (RTD), thermocouples, Electrical isolation 3 1 Specifications Change from one to two columns 1.1 Input 1.1.1 Resistance thermometers/Resistors Resistance thermometer Pt100 in accordance with IEC 60751, JIS C1604-81, MIL-T- 24388, Ni in accordance with DIN 43760, Cu Resistance measurement 0 … 500 Ù 0 … 5000 Ù Sensor connection type Two-, three-, four-wire circuit Connecting cable Maximum sensor line resistance (RW) for each line 50 Ù according to NE 89 (January 2009) Three-wire circuit: symmetrical sensor line resistances Two-wire...

 Open the catalog to page 3
TTR200 - Rail mounted Temperature Transmitter, HART, Pt100 (RTD), thermocouples, electrical isolation-4

Rail mounted Temperature Transmitter TTR200 DS/TTR200-EN HART, Pt100 (RTD), thermocouples, Electrical isolation 4 2 General information Change from one to two columns CE Marking The TTR200 meets all requirements for the CE mark in accordance with IEC 61326 (2006) Electrical isolation 3.5 kV DC (approx. 2.5 kV AC) 60 s, input to output MTBF time 28 years at 60 °C ambient temperature Input filter 50 / 60 Hz Switch-on delay < 10 s (Ia 3.6 mA during starting cycle) Warm-up time 5 minutes Ramp-up time t90 400 … 1000 ms Rate updated 10/s, independent of sensor type and sensor circuit Output filter...

 Open the catalog to page 4
TTR200 - Rail mounted Temperature Transmitter, HART, Pt100 (RTD), thermocouples, electrical isolation-5

Rail mounted Temperature Transmitter TTR200 DS/TTR200-EN HART, Pt100 (RTD), thermocouples, Electrical isolation 5 Change from one to two columns 2.6 Measuring accuracy Includes linearity deviation, reproducibility/hysteresis at 23 °C (73.4 °F) ± 5 K and 20 V supply voltage Information on measuring accuracy corresponds to 3 ó (Gaussian distribution) Input element Standard Sensor Measuring range limits Minimum span Digital measuring accuracy (24-bit A/D converter) D/A measuring accuracy 1) (16-bit DA) Resistance thermometer/resistor IEC 60 751 Pt10 Pt50 Pt100 Pt200 Pt500 Pt1000 (a=0,003850) (a=0,003850)...

 Open the catalog to page 5
TTR200 - Rail mounted Temperature Transmitter, HART, Pt100 (RTD), thermocouples, electrical isolation-6

Rail mounted Temperature Transmitter TTR200 DS/TTR200-EN HART, Pt100 (RTD), thermocouples, Electrical isolation 6 2.7 Operating influences The percentages refer to the configured measuring span. Supply voltage influence/load influence: within the specified limits for the voltage/load, the total influence is less than 0.001 % per volt Common-mode interference: no influence up to 100 Veff (50 Hz) or 50 V DC Ambient temperature influence: based on 23 °C (73.4 °F) for ambient temperature range -40 ... 85 °C (-40 ... 185 °F) Sensor Influence of ambient temperature per 1 °C (1.8 °F) deviation to 23...

 Open the catalog to page 6
TTR200 - Rail mounted Temperature Transmitter, HART, Pt100 (RTD), thermocouples, electrical isolation-7

Rail mounted Temperature Transmitter TTR200 DS/TTR200-EN HART, Pt100 (RTD), thermocouples, Electrical isolation 7 Kommunikation 3 Communication Change from one to two columns 3.1 Configuration parameters Measurement type Sensor type, connection type Error signaling Measurement range General information, e.g., TAG number Damping Signal simulation of output For additional information, see Section 8, "Order form configuration" Write protection Software write protection Diagnostic information in accordance with NE 107 Sensor error (wire break or short circuit) Device error Over/under alarm limits...

 Open the catalog to page 7
TTR200 - Rail mounted Temperature Transmitter, HART, Pt100 (RTD), thermocouples, electrical isolation-8

Rail mounted Temperature Transmitter TTR200 DS/TTR200-EN HART, Pt100 (RTD), thermocouples, Electrical isolation 8 4 Electrical connections Fehler! Verweisquelle konnte nicht gefunden werden. A00203 12 ... 30 / 42 V DC + 11 - 4 ... 20 mA TTR200 + 11 PWR ERR OFF ON 1 2 - 1 2 3 4 5 6 A 4 2 2 2 1 1 1 1 1 1 4 3 3 3 3 3 3 2 1 2 3 4 5 6 + - 7 2 3 + - 8 9 2 3 Fig. 3 1 Potentiometer, four-wire circuit 2 Potentiometer, three-wire circuit 3 Potentiometer, two-wire circuit 4 RTD, four-wire circuit 5 RTD, three-wire circuit 6 RTD, two-wire circuit 7 Voltage measurement 8 Thermocouple 9 Terminal 11: Measurement...

 Open the catalog to page 8
TTR200 - Rail mounted Temperature Transmitter, HART, Pt100 (RTD), thermocouples, electrical isolation-9

Rail mounted Temperature Transmitter TTR200 DS/TTR200-EN HART, Pt100 (RTD), thermocouples, Electrical isolation 9 Bestellangaben 6 Ordering information Main order number Add. order no. Version number 1 - 6 7 8 9 10 11 XX TTR200 rail-mounted temperature transmitter, HART, Pt100 (RTD), thermocouples, electrical isolation TTR200 X X X X X XX Explosion protection Without explosion protection Y 0 ATEX intrinsic safety type of protection: Zone 0: II 1 G Ex ia IIC T6, zone 1 (0): II 2 (1) G Ex [ia] ib IIC T6, Zone 1 (20): II 2 G (1D) Ex [iaD] ib IIC T6 E 1 ATEX non-sparking type of protection: Zone...

 Open the catalog to page 9
TTR200 - Rail mounted Temperature Transmitter, HART, Pt100 (RTD), thermocouples, electrical isolation-10

Rail mounted Temperature Transmitter TTR200 DS/TTR200-EN HART, Pt100 (RTD), thermocouples, Electrical isolation 10 7 Ex relevant specifications Change from one to two columns The TTR200 complies with the requirements of ATEX Directive 94/9/EC. 7.1 TTR200-E1, Intrinsic Safety ATEX Explosion protection Approved for use in Zone 0 and 1 Designation II 1G Ex ia IIC T6 (Zone 0) II 2(1)G Ex [ia] ib IIC T6 (Zone 1 [0]) II 2G(1D) Ex [iaD] ib IIC T6 (Zone 1 [20]) EC type-examination test certificate PTB 05 ATEX 2017 X 7.2 TTR200-H1, Intrinsic Safety IECEx Designation Ex ia IIC T6 Ex [ia] ib IIC T6 Ex [iaD]...

 Open the catalog to page 10
TTR200 - Rail mounted Temperature Transmitter, HART, Pt100 (RTD), thermocouples, electrical isolation-12

ABB has Sales & Customer Support expertise in over 100 countries worldwide. www.abb.com/temperature The Company’s policy is one of continuous product improvement and the right is reserved to modify the information contained herein without notice. Printed in the Fed. Rep. of Germany (04.2010) © ABB 2010 3KXT241001R1001 DS/TTR200-EN Rev. B ABB Limited Salterbeck Trading Estate Workington, Cumbria CA14 5DS UK Tel: +44 (0)1946 830 611 Fax: +44 (0)1946 832 661 ABB Inc. 125 E. County Line Road Warminster, PA 18974 USA Tel: +1 215 674 6000 Fax: +1 215 674 7183 ABB Automation Products GmbH Borsigstr....

 Open the catalog to page 12

All ABB Measurement & Analytics catalogs and technical brochures

  1. ProKiln GAC400

    24  Pages

  2. AV1 and AV2

    24  Pages

  3. SCK

    20  Pages

  4. INDI-BOY DSP

    8  Pages

  5. 9QGPS4500

    8  Pages

  6. 9QGPS3100P

    12  Pages

  7. 9QGPS2960

    12  Pages

  8. 9QGPS2625

    8  Pages

  9. MB3600-HP10

    5  Pages

  10. MB3600-CH10

    8  Pages

  11. ACF5000

    16  Pages

  12. Magnos28

    10  Pages

  13. EL3060

    8  Pages

  14. HP30

    4  Pages

  15. Aztec ATS430

    12  Pages

  16. LMS200

    12  Pages

  17. PGC5000

    8  Pages

  18. LGR-ICOS 927S

    4  Pages

  19. MR Series

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.