Product catalog summary
Overview
The Field Mounted Temperature Transmitter TTF300 is designed for use with HART communication, Pt100 (RTD), thermocouples, and features galvanic isolation. It supports various input types including resistance thermometers, thermocouples, and voltage measurements.
Input Specifications
- Supports 1 or 2 sensors with options for sensor backup and redundancy.
- Resistance measurement ranges from 0 to 5000 Ω.
- Supports multiple thermocouple types and voltage measurement ranges from -125 mV to 1100 mV.
Output Specifications
- Utilizes a 2-wire technique with a 4 to 20 mA temperature linear output.
- HART signal for communication and configurable error current signal.
Measurement Accuracy
- Measurement error is 0.1 K with specific linearization options.
Safety and Approvals
- Complies with NE 53 and NE 79 safety standards.
- Explosion protection approvals include ATEX EEx ia (Zone 0), FM, CSA, and others.
Configuration and Monitoring
- Features continuous sensor and self-monitoring.
- Configuration options include a display with TTF300 configuration function, FDT/DTM, SMART VISION DSV401, and EDD.
Environmental and Mechanical Design
- Ambient temperature range from -40 to 85 °C.
- Protection includes IP66 and IP67; NEMA 4X, ENCL 4X.
- Vibration and shock resistance as per IEC standards.
Communication and Power Supply
- HART communication with specific ripple and load requirements.
- Power supply ranges from 11 to 42 V DC for non-ignition-proof applications.
Additional Features
- Galvanic isolation between input and output.
- MTBF time of 28 years at 60 °C ambient temperature.
- Various diagnostic and monitoring features for enhanced reliability.
Specifications
The document outlines the specifications for the TTF300, detailing digital and D/A measuring accuracies, with examples for Pt100 and thermocouple type K.
Procedures
Examples illustrate the calculation of total accuracy and the influence of ambient temperature on measurements. A block diagram explains the measurement process components.
Operating Conditions
The transmitter operates within specified voltage and load limits, supporting various RTD types and resistance measurements.
Mechanical Design
The transmitter is housed in an aluminum die-cast enclosure with IP66 and IP67 protection, supporting multiple installation positions.
Communication
The TTF300 supports HART protocol version 5, with multiple operating modes and configuration options through various tools.
Explosion Protection
Details explosion protection ratings for different models, including intrinsically safe and non-incendive designs.
Approvals
Complies with CE, NAMUR, ATEX, FM, and CSA standards, with optional SIL Level 2 functional safety certification.
LCD Display
Features a configurable LCD display for process data, electrical measurements, and diagnostic information.
Terminal Connection Diagrams
Diagrams for connecting RTD resistance sensors and thermocouples, illustrating various circuit configurations.
Dimensions and Installation
Includes dimensioned drawings for housing and mounting types, detailing electrical connections and installation options.
Ordering Information
Various protection types and housing options are available, compliant with ATEX, FM, and CSA standards.
Additional Options
Customer-specific configurations, calibration certificates, and mounting brackets are available, along with surge and lightning protection accessories.
Configuration Details
Customers can specify sensor numbers, measurement types, and ranges, as well as failure signalization and damping settings.
Contact Information
Lists contact details for ABB offices in the UK, USA, and Germany, emphasizing their global sales and customer support network.
See more

Catalog excerpts

TTF300 - Field mounted Temperature Transmitter, HART, Pt 100 (RTD), thermocouples, electrical isolation-1

Input - Resistance thermometers - Thermocouples - Resistance-remote signalling unit (0 ... 5000 ) - Voltages, mV transmitter (-125 ... 1100 mV) Input functionality - 1 or 2 sensors (e.g. 2 x Pt100 3-L) - Sensor backup/redundancy - Sensor drift monitoring Output - 2-wire technique - 4 ... 20 mA temperature linear - HART signal Measurement error - 0,1 K Specific linearization - Callendar van Dusen coefficients - Customer specific curve / 32 tie points Continuous sensor and self-monitoring - Supply voltage monitoring - Wire break and corrosion monitoring (NE 89) - Extended diagnostics (NE 107) Device safety in accordance with NE 53, NE 79 Approvals for explosion protection - intrinsically safe: ATEX EEx ia (Zone 0), FM, CSA - non-incendive: ATEX EEx n A - Dust-ignition proof: ATEX / Zone 20 - air tight: ATEX / Zone 1, FM, CSA Configuration > - Display with TTF300 configuration function - FDT/DTM - SMART VISION DSV401 - EDD > Contents size="-2">

 Open the catalog to page 1
TTF300 - Field mounted Temperature Transmitter, HART, Pt 100 (RTD), thermocouples, electrical isolation-3

Wechsel ein-auf zweispaltig Sensor matching via Callendar van Dusen coefficients via table of 32 sampling points via single point (offset adjustment) via two point adjustment > RTD resistance thermometer Input functionality Pt100 in acc. with DIN IEC 60751, JIS, MIL, Ni in acc. with DIN 43760, Cu (for additional information, see the section "Measuring accuracy") 1 Sensor 2 Sensors: mean measurement Differential measurement: Zero point where Ia = 4 mA Differential measurement: Zero point where Ia = 12 mA Sensor redundancy Resistance measurement 0 500 0 Ņ 5000 Sensor connections 2-, 3-, 4-wire...

 Open the catalog to page 3
TTF300 - Field mounted Temperature Transmitter, HART, Pt 100 (RTD), thermocouples, electrical isolation-4

Wechsel ein-auf zweispaltig Supply voltage (2-wire technique; power lines = signal lines) Supply voltage Galvanic isolation (input/output) 3.5 kV AC (approx. 2.5 KV DC) 60 s Non ignition-proof application with or without LCD-display: U MTBF time 28 years at 60 C ambient temperature > S = 11 ... 42 V DC Ignition-proof applications with or without LCD-display: U Input filter 50 / 60 Hz Switch-on delay < 10 s (I > a 3.6 mA during starting cycle) > S = 11 ... 30 V DC Max. permissible residual ripple for supply voltage Warm-up time 5 min. Max. permissible ripple for supply voltage during communication...

 Open the catalog to page 4
TTF300 - Field mounted Temperature Transmitter, HART, Pt 100 (RTD), thermocouples, electrical isolation-5

Includes linearity deviation, reproducibility/hysteresis at 23 C б 5 K and 20 V supply voltage Information on measuring accuracy corresponds to 3 (Gaussian distribution) Input element -200 ... 850 C / -328 ... 1562 аF Minimum span Digital measuring D/A Standard Sensor -200 ... 850 C / -328 ... 1562 аF -200 ... 850 C / -328 ... 1562 аF -200 ... 850 C / -328 ... 1562 аF 10 C / 18 аF 10 C / 18 аF 10 C / 18 аF 10 C / 18 аF 10 C / 18 аF 10 C / 18 аF 0,80 ѰC / 1,44 ѰF 0,16 ѰC / 0,29 ѰF 0,08 ѰC / 0,14 ѰF 0,24 ѰC / 0,43 ѰF 0,16 ѰC / 0,29 ѰF 0,08 ѰC / 0,14 ѰF 0,05 % ѱ 0,05 % 0,05 % ѱ 0,05 % 0,05 % ѱ 0,05...

 Open the catalog to page 5
TTF300 - Field mounted Temperature Transmitter, HART, Pt 100 (RTD), thermocouples, electrical isolation-6

Sensor Power supply Fig. 1 1 24-bit A/D converter 6 Load (observe voltage drop, refer to the section "Terminal 2 Microcontroller connection diagrams") 3 LCD-display with TTF300 configuration options 7 Digital accuracy 4 16-bit D/A converter 8 D/A accuracy 5 HART signal 9 Overall accuracy >

 Open the catalog to page 6
TTF300 - Field mounted Temperature Transmitter, HART, Pt 100 (RTD), thermocouples, electrical isolation-7

The percentages refer to the configured measuring span. Supply voltage influence/load influence: within the specified limits for the voltage/load the total influence is less than 0.001% per volt Common-mode interference no influence up to 100 V Veff (50 Hz) or 50 VDC Ambient temperature influence: based on 23 C / 73.4 аF (ambient temperature range: -40 ... 85 C / -40 аF ... 185 F) Sensor Ambient temperature influence Ambient temperature influence > 1) For 1 аC / 1.8 F dev. to 23 аC / 73,4 F For 1 аC / 1.8 F dev. to 23 аC / 73,4 F for digital readings for D/A converter 2-, 3-, 4-wire circuit RTD...

 Open the catalog to page 7
TTF300 - Field mounted Temperature Transmitter, HART, Pt 100 (RTD), thermocouples, electrical isolation-8

Wechsel ein-auf zweispaltig Dimensions: Refer to dimensioned drawings Metal cable fitting: Weight: > Material: 1.25 kg dust-ignition proof, hermetically sealed, explosion-proof max. cable outer diameter 6 ... 7.5 mm, temp. range -20 90 ŰC / -4 194 ŰF Housing: Aluminum die cast, chromized inside/outside, 70 յm epoxide-coated (aluminum with 12 % silicon, magnesium content < 0.3 %, copper-free < 0.05 %) Color: gray RAL9002 Օ Types of protection: IP66 and IP67; NEMA 4X, ENCL 4X Ground screw external 6 mm > 2 2 M5 internal 2 x 2.5 mm M4 Օ Terminals for lines up to 2.5 mm > 2 and hand-held terminal...

 Open the catalog to page 8
TTF300 - Field mounted Temperature Transmitter, HART, Pt 100 (RTD), thermocouples, electrical isolation-9

Wechsel ein-auf zweispaltig The system is registered with the HART Communication Foundation. Driver-independent: HMI indicator type A with configuration function Օ Device management/asset management tools FDT/DTM technology Օ DSV401 (SMART VISION) via TTX300-DTM driver EDD Driver-dependent: > Օ Sensor type, connection type Fault signaling Օ Measuring range General information, e.g., TAG number Օ Damping Warning and alarm limits Օ Signal simulation of output See " Measurement type Fig. 2 * if necessary 1 DHH691 (691HT), STT04, HC275, FC375 2 Ground connection (optional) 4 Order form configuration...

 Open the catalog to page 9
TTF300 - Field mounted Temperature Transmitter, HART, Pt 100 (RTD), thermocouples, electrical isolation-10

Approved for use in zone 0. Designation: ŕ II 1G EEx ia IIC T6 (Zone 0) II 2 (1) G EEx [ia] ib IIC T6 (zone 1 [0]) Օ II 2 G (1D) Ex [iaD] ib IIC T6 (zone 1 [20]) Note The Ex or ignition-proof designation is provided on the name plate. EC prototype test certificate: Refer to PTB 05 ATEX2017 X. > Temperature Permissible ambient temperature range class Device category 1 Device category 2 use use T6 -50 44 ŰC -50 56 ŰC T5 -50 56 ŰC -50 71 ŰC T4 -50 84 ŰC -50 85 ŰC > Wechsel ein-auf zweispaltig Intrinsically safe EEx ia IIC explosion protection Supply circuit Measurement current Measurement current...

 Open the catalog to page 10
TTF300 - Field mounted Temperature Transmitter, HART, Pt 100 (RTD), thermocouples, electrical isolation-11

Wechsel ein-auf zweispaltig The TTF300 meets requirements for ATEX, FM and CSA. For additional information, refer to the section "Explosion-protection relevant information"). > The TTF300 meets all requirements for the CE mark in accordance with IEC 61326 (2002). > acc. to IEC 61508. Device with certificate of conformity for use in safety-relevant applications, including SIL Level 2. For additional information, refer to the safety manual for the TTH300/TTF300. The TTF300 complies with NAMUR NE 21 (02/2004). > Wechsel ein-auf zweispaltig

 Open the catalog to page 11

All ABB Measurement & Analytics catalogs and technical brochures

  1. ProKiln GAC400

    24  Pages

  2. AV1 and AV2

    24  Pages

  3. SCK

    20  Pages

  4. INDI-BOY DSP

    8  Pages

  5. 9QGPS4500

    8  Pages

  6. 9QGPS3100P

    12  Pages

  7. 9QGPS2960

    12  Pages

  8. 9QGPS2625

    8  Pages

  9. MB3600-HP10

    5  Pages

  10. MB3600-CH10

    8  Pages

  11. ACF5000

    16  Pages

  12. Magnos28

    10  Pages

  13. EL3060

    8  Pages

  14. HP30

    4  Pages

  15. Aztec ATS430

    12  Pages

  16. LMS200

    12  Pages

  17. PGC5000

    8  Pages

  18. LGR-ICOS 927S

    4  Pages

  19. MR Series

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.