Power Capacitor Units for improved power quality
Open the catalog to page 1
Applications for capacitors Reactive power compensation Most of the apparatus and loads connected to the electrical power system consume both active and reactive (inductive) power. Some examples of such components are transformers, transmission and distribution lines, induction motors, rectifiers, induction furnaces, etc. The most economical method of reducing reactive power consumption in electrical power systems is by installing capacitor banks. This method is called reactive power compensation. The capacitor injects reactive power into the system, thus reducing the load in the entire...
Open the catalog to page 2
Fusing technologies Impregnated capacitor unit — CHD The CHD type is a single-phase power capacitor of the all-film type, with low dielectric losses and long service life. The capacitors are impregnated with Faradol, a bio-degradable product with high insulation strength. The edges of the electrode foils are folded, enabling higher electrical stress. The ABB capacitor units have an extremely low failure rate and high reliability. The CHD capacitor unit is made up of a number of elements, each consisting of very thin layers of dielectric materials and thin foils of aluminum as electrodes....
Open the catalog to page 3
Product information Capacitor unit The ABB capacitor unit is designed for heavy duty operation in shunt, harmonic filter, series capacitor, SVC and HVDC applications in all climatic conditions. Design features − − The single-phase power capacitor is a all-film type, with low dielectric losses and long service life. The capacitors are impregnated with a hydrocarbon fluid with high insulation strength. − − The edges of the electrode foils are folded, enabling higher electrical stress. − − The capacitor units have an extremely low failure rate and high reliability. − − The capacitor units are...
Open the catalog to page 4
Technical data Unit type_CHDB_CHDE_CHDF_ Fusing type Internally fused Fuseless unit with all elements Fuseless unit with separate connected directly in parallel parallel element strings (often referred to as externally fused units) Dielectric material Polypropylene film Polypropylene film Polypropylene film Impregnant Synthetic impregnation fluid. Faradol Synthetic impregnation fluid. Faradol Synthetic impregnation fluid. Faradol Discharge resistor Built-in type Built-in type Built-in type Location Indoor/outdoor Indoor/outdoor Indoor/outdoor Capacitor container_ Material Ferritic stainless...
Open the catalog to page 5
Inquiry specification sheet General information Other information Rating plate bird caps Photo of the rating plate is required Technical information Other standard Temperature class Fusing type Rated voltage Rated output Rated capacitance Rated current Discharge time/voltage Mounting brackets Upper bracket position 2) Pollution level (SCD) according to IEC 60815-1 Very heavy □ 31 mm/kV Special requirement 11 ABB standard S-type bushings 21 Distance from the base of can (capacitor unit container) 6 Power Capacitor Units | Brochure
Open the catalog to page 6
Testing equipment Portable capacitance meter, CB-2000 The CB-2000 is an advanced measurement instrument characterized by its compact design and low weight, which makes it easy to carry when conducting measurements. No disconnections in the capacitor bank or mains connection are required. The collected measurement values can be easily transferred to a PC for storage and analysis. The stored values from the PC can just as easily be transferred to the meter so that they are available when new measurements are made. Measuring capacitance is an important part of the regular maintenance of...
Open the catalog to page 7
ABB AB High Voltage Products ©Copyright 2014 ABB. All rights reserved NOTE: ABB AB is working continuously to improve its products. We therefore reserve the right to change designs, dimensions and data without prior notice. Publication 1HSM 9543 31-03en, Edition 1, 2014-02, Power Capacitor Unit for improved power quality, Brochure, Photo: Hasse Eriksson
Open the catalog to page 8All ABB AG catalogs and technical brochures
-
PASS – Plug And Switch System
12 Pages
-
Transportation
11 Pages
-
MFM - Multi Functional Modules
16 Pages
-
Capacitor Bank Controller CQ900
10 Pages
-
HMC operating mechanism
4 Pages
Archived catalogs
-
High Voltage Surge Arresters
116 Pages
-
Gas-insulated Switchgear ENK
8 Pages
-
Gas-insulated Switchgear ELK-04
32 Pages
-
PASS M00, PASS M0, PASS M0S
24 Pages
-
ABB Composite Insulators
24 Pages
-
Live tank circuit breaker
136 Pages
-
COMPASS
20 Pages
-
Disconnecting circuit breakers
12 Pages