Liquid Turbine Flow Meter User Manual ' Warning When the flow meter is installed at explosion hazard field, DON'T remove the COVERPLATE when the meter is powered. Please make parameter settng at safe filed prior to installation. > Special Notices Pictures & Descriptions are for your information only, please refer to the actual product. Parameters are subjected to changes without notice. GENERAL INFORMATION This manual will assist you in installing, using and maintaining your turbine flow meter. It is your responsibility to make that all operators have access to adequate instructions about...
カタログの2ページ目を開く
Shelok SPECIFICATIONSPerformance Measurable Flow Rate Range and Pres Level: (See table 1) Table 1. Measurable Flow Rage Range and Pressure Rating Standard - 304 Stainless Steel Optional - 316 Stainless Steel Tungsten Carbide Standard - 2Cr13 Stainless Steel (Optional Alloy CD4Mcu) 316 Stainless Steel Power Supply: Sensor: Transmitter: Field Display Type B: Field Display Type C: Accuracy: Standard: ±1% of reading; Housing: Bearings and Shaft: Rotor: Retaining Rings: Output Signal: (Where applicable) Sensor: Pulse signal (Low Level: <0.8V; High Level: >8V) Transmitter: 4 to 20 mA DC current...
カタログの3ページ目を開く
CAUTIONS FOR INSTALLATION Mounting Positions Turbine flow meters should be installed at the place in compliance with the requirements below: •Easy maintenance •No vibration •No electromagnetic interface •Away from heat source Mounting Orientation All turbine flow meters are designed to measure flow in only one direction. The direction is indicated by the arrow on the body. Required Lengths of Straight Runs Flow altering device such as elbows, valves and reducers can affect accuracy. See diagram 1 for typical flow meter system installation. Diagram 1. Typical Flow Meter System Installation...
カタログの4ページ目を開く
See diagram 2 for straight pipe length requirement when there is altering device. Diagram 2. Number of Pipe Diameter (D=Diameter) Warning:Precaution for direct sunshine and rain when the meter is installed outside. Cavitation can be caused by entrained air, and it can seriously damage the rotor on a turbine flow meter. An amount higher than about 100 mg/l of entrained air or gas can produce error. In addition, cavitations can be caused by too little back pres on the flow meter. For turbine flow meters, you should provide a back pres (downstream pres) of at least 1.25 times the vapor pres,...
カタログの5ページ目を開く
Notice: The straight section is included for DN4-DN10, but not DN15-DN Flange connection Wafer Connection
カタログの6ページ目を開く
Sanitary Connection
カタログの7ページ目を開く
Main Power Description of the symbols: + Default Function O Optional • 2. Pulse with Explosion Proof: Notice: l.The pulse means the signal which is in direct proportion to the impeller speed. 2.The scaled Pulse means the signal when the flow rate reach ONE unit volume( m3, L, 0.01L...) 3.The batter model is ER34615 4.The battery model is ER26500 Notice: (1) High level amplitude >22V (2)Low level amplitude<0.8V (3)Load capacity>1100Q (4)Pulse frequency<3000Hz •3. 4-20mA Output with Explosion Proof Type Notice: Load resistor is <
カタログの8ページ目を開く
Pulse / Scaled Pulse output
カタログの9ページ目を開く
Pulse / Scaled Pulse output
カタログの10ページ目を開く
Parameter set There are four keys: "Enter", "^", "t", "Esc". Description of Password Grade
カタログの11ページ目を開く
Parameter set METER CONSTRUCTION Symptom Measurement is not accurate Probable Cause Solution 1. Turbine operated below minimum rate. Increase flow rate. Refer to Section 3.0 Operation Conditions Materials of Housing Stainless Steel 304 • Others available on request) Magnetic Pickup End Fittings: For hazardous areas, pickup colls supplied with explosion proof boss. Carbide Steel (Others available on request) 2. Turbine partially clogged with dried liquid Remove turbine. Clean carefully. Make rotor spins freely. 3. Installed too close to fiffings. Install correctly. Refer to Section 5.0...
カタログの12ページ目を開く
METER CONSTRUCTION Hereby provides a limited warranty against defects in materials and workmanship. This product includes a one-year warranty. The warranty period shall begin on the date of the original new equipment purchase. Warrantor's obligation hereunder shall be limited to repairing defective workmanship or replacing or repairing any defective parts. In the event Purchaser believes the product is defective, the product must be returned to, transportation prepaid by Purchaser, within the appropriate warranty period relative to the product. If 's inspection determines the workmanship or...
カタログの13ページ目を開くXi'an Yunyi Instrument Co.のすべてのカタログと技術パンフレット
-
K series
3 ページ
-
YX-2006B
2 ページ
-
XY-2002
1 ページ
-
YFM4800E
14 ページ
-
YD32
2 ページ
-
Deadweight tester JY
2 ページ
-
Mass flow meter Coriolis
14 ページ
-
Orifice flow meter
6 ページ
-
Mass flow meter
3 ページ
-
Vortex flow meter YFV
20 ページ
-
Mass flow meter YFV300
20 ページ
-
Mass flow meter YFT300D
13 ページ
-
Turbine flow meter
13 ページ
-
Liquids level gauge
3 ページ
-
Radar level sensor
12 ページ
-
YD31 series
4 ページ