VAMP 57
1 / 16ページ

{{requestButtons}}

カタログの抜粋

VAMP 57 - 1

VAMP 57 Multipurpose feeder and motor protection relay The VAMP 57 feeder manager has been developed to cover basic protection needs for OEMs, utilities and industrial applications. Thanks to its cost-effective and flexible design, the VAMP 57 provides an excellent alternative for various protection applications. User-friendliness has always been a feature of VAMP products, and the VAMP 57 is no exception. The rapid setting and download/upload is achieved with the unique VAMPSET setting software which dramatically improves usability

カタログの1ページ目を開く
VAMP 57 - 2

VAMP RANGE // VAMP 57 PROTECTION RELAY www.schneider-electric.com/vamp-protection 2 VAMP RANGE // VAMP 57 PROTECTION RELAY www.schneider-electric.com/vamp-protection 2 VAMP 57 at a glance- Robust hardware • User selectable Ethernet, RS485 or RS232 based communication interface • Designed for demanding industrial conditions Common technology for cost efficiency • Powerful CPU supporting IEC 61850 • Thanks to four setting groups adaptation to various protection schemes is convenient User-friendly and high functionality • Common firmware platform with other VAMP range protection...

カタログの2ページ目を開く
VAMP 57 - 4

VAMP RANGE // VAMP 57 PROTECTION RELAY User friendly HMI interface Ease of use A great deal of effort has gone into the design of the operational aspects of the new products. Unicode support allows the menu text and settings to be translated by user into various international languages including for example Russian and Chinese. The informative human machine interface shows all of the required information for the user with support of customised legend texts. The VAMP 57 protection relay concept has been extended with a number of features that make installation and testing of the relays even...

カタログの4ページ目を開く
VAMP 57 - 5

VAMP RANGE // VAMP 57 PROTECTION RELAY www.schneider-electric.com/vamp-protection 5 VAMP is an expert in communication with vast experience in interfacing different system integrators, SCADA, RTUs, PLCs and gateways using a large number of supported protocols. Flexible adaptation of the communication protocols together with powerful and easy to use software tools are the key to successful integration. IEC 61850 The IEC 61850 protocol can be used to read or write static data or to receive events sent spontaneously from the relay. In addition, the interface allows peer-to-peer communication...

カタログの5ページ目を開く
VAMP 57 - 6

VAMP RANGE // VAMP 57 PROTECTION RELAY www.schneider-electric.com/vamp-protection 6 VAMPSET is a user-friendly, free-of-charge relay management software for setting parameters and configuring VAMP relays. Via the VAMPSET software, relay parameters, configurations and recorded data can be exchanged between PC and VAMP relays. Supporting the COMTRADE format, VAMPSET also incorporates tools for analysing relay events, waveforms and trends from data recorded by the relays, e.g. during a network fault situation. Relay's setting views are organised to several folders in the VAMPSET setting...

カタログの6ページ目を開く
VAMP 57 - 7

VAMP RANGE // VAMP 57 PROTECTION RELAY The VAMP 57 offers a complete set of measurement functions to replace the conventional metering functions of switchgear and controlgear installations. The measurement functions cover phase, line and residual currents, current imbalance, system frequency and harmonics from phase currents. Condition monitoring continuously monitors trip circuits, breaker wear and current transformers.

カタログの7ページ目を開く
VAMP 57 - 8

VAMP RANGE // VAMP 57 PROTECTION RELAY

カタログの8ページ目を開く
VAMP 57 - 9

VAMP RANGE // VAMP 57 PROTECTION RELAY Programmable stages There are now eight stages available to use with various applications. Each stage can monitor any analogue (measured or calculated) signal and issue start and trip signals. Programmable stages extend the protection functionality of the manager series to a new level. For example, if four stages of frequency are not enough, with programmable stages, the maximum of 12 can be reached. Other examples are using the stages to issue an alarm when there are a lot of harmonics (THD) or indicating reverse power condition. Programmable logic:...

カタログの9ページ目を開く
VAMP 57 - 10

VAMP RANGE // VAMP 57 PROTECTION RELAY Voltage scaling mode Inputs / Outputs The VAMP 57 hosts various optional modules in order to upgrade the relay functionality from basic to more advanced applications.

カタログの10ページ目を開く
VAMP 57 - 11

VAMP RANGE // VAMP 57 PROTECTION RELAY Dimensional drawings Panel mounting VAMP 57 PANEL MOUNTING VAMP 57

カタログの11ページ目を開く
VAMP 57 - 12

VAMP RANGE // VAMP 57 PROTECTION RELAY Phase currents & voltage input, X1 3 Earth-fault current input , X1 A Nominal Supply Voltage [V] , X2 A Power A 48 - 230 V (range: 40 - 265 V ac / dc) Conformal coating Note: For exact DI, DO and AI amount see table on page 10 Accessories Order code USB programming cable (Vampset) V57 Panel Seal Cover V57 (RS232) - Remote / Extension / IRIG-B (3xD9) V57 (RS232) - VPA 3CG Profibus adapter cable Fiber optic module (plastic - plastic) Fiber optic module (glass - glass) Profibus DP fieldbus optio

カタログの12ページ目を開く
VAMP 57 - 13

VAMP RANGE // VAMP 57 PROTECTION RELAY Main technical data Auxiliary voltage Voltage range Measuring circuit Rated phase current IN Current measuring range Rated neutral current I0N Current measuring range Thermal withstand Voltage measuring range Continuous voltage withstand Digital inputs Digital inputs (external voltage max 265 V) Nominal operation voltage DI1 – DI16 1: 24 - 230 V ac / dc (max. 265 V ac / dc) 2: 110 - 230 V ac / dc (max. 265 V ac / dc) 3: 220 - 230 V ac / dc (max. 265 V ac / dc) Typical switching treshold 1: 12 V ac / dc 2: 75 V ac / dc 3: 155 V ac / dc Outputs Rated volta

カタログの13ページ目を開く
VAMP 57 - 14

VAMP RANGE // VAMP 57 PROTECTION RELAY Test value 5 kV, 1.2/50 ms, 0.5 J, communication 1 kV 2 kV, 50 Hz, communication 0,5 kV Electrical safety tests Impulse voltage withstand Dielectric test Insulation resistance Protective bonding resistance Power supply burden Standard & Test class / level IEC/EN 60255-27 & EN 60255-5, Class III IEC/EN 60255-27 & EN 60255-5, Class III IEC/EN 60255-27 & EN 60255-5 IEC/EN 60255-27 IEC/EN 60255-1 Disturbance tests

カタログの14ページ目を開く

Vampのすべてのカタログと技術パンフレット

  1. vamp 265

    2 ページ

  2. VAMP 11V

    16 ページ

  3. VAMP 1 1 F

    16 ページ

  4. VAMP 50 series

    20 ページ

  5. VAMP 96 and VAMP 260

    12 ページ

  6. VAMP 259

    12 ページ

  7. VAMP 125

    1 ページ

  8. VAMP 120 & 121

    8 ページ

  9. VAMP 11V

    16 ページ

  10. VAMP 321

    12 ページ

  11. VAMP 59

    12 ページ

  12. VAMP 55

    190 ページ

  13. VAMP 120

    8 ページ

  14. VAMP 40

    24 ページ

  15. VAMP 50

    20 ページ

  16. VAMP 230

    16 ページ

  17. VAMP 210

    2 ページ

  18. VAMP 135

    8 ページ

カタログアーカイブ

  1. VAMP 221_2013

    16 ページ

  2. VAMP 221_2011

    16 ページ

  3. VAMP 96

    16 ページ

  4. ARC Protection

    20 ページ

  5. Customer

    28 ページ

  6. Selection table

    1 ページ