IEEE-519 Harmonic standard This article is quoted from the harmonic standard "IEEE Std—2014 Recommended Practices and Requirements for Harmonic Control of Power Systems" revised in 2014 by the Institute of Power Electronics Engineers. If there are copyright issues, please contact to delete. The United States IEEE Std. 519-2014 on the harmonic standards of power grids is a relatively authoritative standard in the world, produced by the United States IEEE Power and Energy Society, it is used as a reference standard by many countries and regions around the world. Current distortion limits for systems rated 120 V through 69 kV The limits in this subclause apply to users connected to systems where the rated voltage at the PCC is 120 V to 69 kV. At the PCC, users should limit their harmonic currents as follows: Maximum harmonic current distortion in percent of IL Individual harmonic order (odd harmonics)a, b ISC/IL Definitions: Isc = maximum short-circuit current at PCC IL = maximum demand load current (fundamental frequency component) at the PCC under normal load operating conditions PCC (point of common coupling): Point on a public power supply system, electrically nearest to a

カタログの1ページ目を開く
IEEE 519 - 2

particular load, at which other loads are, or could be, connected. The PCC is a point located upstream of the considered installation a Even harmonics are limited to 25% of the odd harmonic limits above. Current distortions that result in a dc offset, e.g., half-wave converters, are not allowed. All power generation equipment is limited to these values of current distortion, regardless of actual Isc/IL. TDD (total demand distortion): The ratio of the root mean square of the harmonic content, considering harmonic components up to the 50th order and specifically excluding interharmonics,...

カタログの2ページ目を開く

Sinexcel Electricのすべてのカタログと技術パンフレット

  1. SER100040K3B

    2 ページ

  2. SER

    8 ページ

  3. SEC 40-80kW

    3 ページ