Reyrolle 7SR10 Platform Protecting grid with confidence Catalog Reyrolle 7SR10 · Edition 8
1 /
48ページ
カタログの抜粋

Catalog Reyrolle 7SR10 • Edition 8
カタログの1ページ目を開く
2 Digital Grid ⋅ 7SR10 Platform Catalog ⋅ Siemens Protection Device
カタログの2ページ目を開く
Digital Grid 7SR10 Platform Catalog Introduction Devices and Application Relay Selection Guide Reyrolle 7SR10 Overcurrent Relay Reyrolle 7SR105 Motor Protection Relay System Protection Monitoring, and Data Acquisition and Recording Communications Hardware Construction Technical Documentation Connection Diagrams Dimension Drawings Technical Data Ordering Information Digital Grid ■ 7SR10 Platform Catalog ■ Siemens Protection Devices 3
カタログの3ページ目を開く
Reyrolle – Solutions for Distribution Grids [dw_reyrolle history, 3, en_US] Figure 1/1 History of Reyrolle Reyrolle has been synonymous with electrical protection devices in the sectors of sub-transmission, distribution, and industrial applications for decades. Historically, Reyrolle relays were sold mainly in traditional markets but are now sold worldwide as part of the Siemens protection network. Since its foundation, Reyrolle has been an innovation driver in product development – based on a strong focus on market, customer and technology. Worldwide established brand names such as...
カタログの4ページ目を開く
Digital Grid ■ 7SR10 Platform Catalog ■ Siemens Protection Devices 5
カタログの5ページ目を開く
Devices and ApplicationRelay Selection Guide ANSI Functions o o
カタログの6ページ目を開く
■ Basic • Optional The Reyrolle 7SR10 Platform devices come equipped with numerous protection functions and features. A full list of these can be seen in the table above. Digital Grid ■ 7SR10 Platfo
カタログの7ページ目を開く
Main Function Description The Reyrolle 7SR10 Argus is an overcurrent and earth fault relay intended as a simple protection solution for distribution and industrial applications. It consists of non-directional functions and additional voltage inputs providing directional functions. The conformal coating on device electronic modules increases protection against harmful environmental influences such as extreme moisture, corrosive gases and aggressive dust. Benefits • Circuit-breaker open and close fascia push button • Protection settings can be viewed and edited from the fascia • 9 user...
カタログの8ページ目を開く
Devices and Application Reyrolle 7SR10 Overcurrent Relay • 60CTS CT supervision • 60VTS VT supervision • 74CCS Close-circuit supervision • 74TCS Trip-circuit supervision • 81HBL2 Inrush current detection • 81I_THD Total harmonic distortion supervision Control Functions • 52 CB control • 86 Lockout • 79 Automatic reclosing • User programmable logics Communications • IEC 60870-5-103 • MODBUS RTU • DNP 3.0 Reydisp Software [lo_7SR10 non-directional functional diagram, 3, en_US] Figure 2.2/2 7SR10 Non-Directional Overcurrent Relay Our user friendly PC software tool ensures a smooth installation...
カタログの9ページ目を開く
Digital Grid ■ 7SR10 Platform
カタログの11ページ目を開く
Description 7SR105 relay is a numerical protection relay intended for use in motor protection applications. It provides a highly comprehensive functional software package with a range of integral application functions aimed at reducing installation, wiring, and engineering time. The conformal coating on device electronic modules increases protection against harmful environmental influences such as extreme moisture, corrosive gases and aggressive dust. Benefits • 2 settings groups • Password protection - 2 levels3 • User programmable logic • Self monitoring • Circuit-breaker trip and...
カタログの12ページ目を開く
Devices and Application Reyrolle 7SR105 Motor Protection Relay Applications • Motor protection for industrial applications • Sewage, water treatment plants and pumping station • CHP handling plants • Automotive conveying systems • Typically for current based protection of motors less than 1 MW Application The 7SR105 Rho motor protection relay is a numerical protection relay intended for use in the motor protection applications. It provides a highly comprehensive functional software package with a range of integral application functions aimed at reducing installation, wiring, and engineering...
カタログの13ページ目を開く
ANSI Functions ■ Included as standard 14 Digital Grid ■ 7SR10 Platf
カタログの14ページ目を開く
System Protection Protection and Supervision Functions 14 Locked Rotor Protection Each element has a single definite time overcurrent characteristic with settings for pickup level and definite time lag (DTL) delays. Operation can be controlled from motor stopped or running conditions. 27 Undervoltage Protection – Phase Each element has settings for pickup level, drop-off level and DTL delays. Operation occurs if voltage is below setting for duration of delay. ances on the system or remote earth faults when a delta-star transformer is in circuit. 47NPS Negative Sequence Overvoltage...
カタログの15ページ目を開く
System Protection to bypass the time delays when the circuit-breaker is known to be faulty. 50G Instantaneous Earth Fault – Measured This function directly measures the earth current from an independent CT, or the residual connection of the 3 line CTs. 50G INST/DTL elements provide earth fault protection, each with independent settings for pickup current. 50GLC Line Check Earth Fault – Measured This function prevents a CB being repeatedly manually closed onto a faulted line. It is enabled upon the Manual CB Close output being issued. 3.1 50LC Line Check This function prevents a CB being...
カタログの16ページ目を開く
System Protection method that considers the presence of negative phase sequence current, without an equivalent level of negative phase sequence voltage, for a user set time as a CT failure. Both element types have user operate and delay settings. 60VTS VT Supervision The VT supervision uses a combination of negative phase sequence voltage and negative phase sequence current to detect a VT fuse failure. This condition may be alarmed or used to inhibit voltage dependent functions. Element has user operate and delay settings. 64H Restricted Earth Fault Protection – High-Impedance The measured...
カタログの17ページ目を開く
System Protection Virtual Inputs/Outputs There are 8 virtual inputs/outputs to provide internal logical states to assist in the application of the functions. Each virtual I/O can be assigned in the same way as a physical I/O. Circuit-Breaker Maintenance 2 circuit breaker operations counters are provided to assist with maintenance scheduling. The maintenance counter records the overall number of operations and the delta counter records the number of operations since the last reset. An I2t summation counter provides a measure of the contact wear indicating the total energy interrupted by the...
カタログの18ページ目を開くSIEMENS Energy automation and smart gridのすべてのカタログと技術パンフレット
-
7SR5 Platform
86 ページ
-
Reyrolle 7SR54
2 ページ
-
Reyrolle 7SR51
2 ページ
-
SICAM Q100
2 ページ
-
7SR21 & 7SR22 Argus
2 ページ
-
SIPROTEC 7SA87
2 ページ
-
SIPROTEC 7SA86
2 ページ
-
SIPROTEC 7SA82
2 ページ
-
SICAM A8000 Series
11 ページ
-
SICAM Substation Automation
190 ページ
-
Reyrolle Product Catalogue
346 ページ
-
Reyrolle 5 Platform
52 ページ
-
SIPROTEC Compact
210 ページ
-
Catalog SICAM CMIC
8 ページ
-
7SC80 Brochure
8 ページ
-
Catalog - Bay Controller
32 ページ