CS,HS,SS,PS SERIES
12Pages

{{requestButtons}}

Catalog excerpts

CS,HS,SS,PS SERIES - 1

ENTED TYPE STATIONARY LEAD-AC IDBATTE RY_

Open the catalog to page 1
CS,HS,SS,PS SERIES - 3

CS Series outline drawings with terminal position

Open the catalog to page 3
CS,HS,SS,PS SERIES - 4

CS Series Charge Specification CS Series Discharge and Final Voltage * The average voltage must not be less than 1.2V for each cell for the engine starting applications. CS Series Discharge Characteristics Constant current discharge curves at 25°C(77°F) Discharge Time (Hour) * The above-mentioned graph becomes the characteristic of CS-900 or smaller size. * If you need these characteristic of CS-1000 or bigger, please contact us. * The graph is one example and not guaranteed values.

Open the catalog to page 4
CS,HS,SS,PS SERIES - 5

Capacity (%) CS Series Relationship between battery temperature and capacity Battery Temperature(℃) The above-mentioned graph becomes the characteristic of CS-900 or smaller. If you need these characteristic of CS-1000 or bigger, please contact us. The graph is one example and not guaranteed values. CS Series Constant voltage charge characteristics Recovering charge at 2.30V/cell, 0.1C 10 A current limit at 25℃ from 100% DOD Amount of Charge(%) Terminal Voltage(V/cell) 140 120 100 80 60 40 Amount Charge (%) Terminal Voltage (V/cell) Charging Current (CA) Battery temperature:25℃(77°F)...

Open the catalog to page 5
CS,HS,SS,PS SERIES - 7

HS Series outline drawings with terminal position

Open the catalog to page 7
CS,HS,SS,PS SERIES - 8

HS Series Charge Specification Item Charge Specification Purpose Floating charge Charge Type Remarks Equalizing charge Recovering charge Refreshing charge Please do the equalizing charge once every six months at least. Constant voltage charge Charge Voltage 2.18V/cell 2.30V/cell ー ー ー ー Approx.24 hours Charge Time charging with 0.1C 10 A from 100% Discharge HS Series Discharge and Final Voltage Discharge Current CA Average final Voltage (V/each) 2V Battery 6V Battery V/cell Less than 0.1C 10 A or Intermittent discharge 1.90 5.70 1.90 0.1C 10 A or close current 1.80 5.40 1.80 0.16C 10 A or...

Open the catalog to page 8
CS,HS,SS,PS SERIES - 9

HS Series Relationship between battery Battery Temperature(°C) * The graph is one example and not guaranteed values. HS Series Constant voltage charge characteristics Recovering charge at 2.30V/cell, 0.1C 10 A current limit at 25°C from 100% DOD Charging Time (Hour) * The graph is one example and not guaranteed values.

Open the catalog to page 9
CS,HS,SS,PS SERIES - 10

• Service life of 5 to 7 years can expected. •The specific gravity can be confirmed at any time with specific gravity indicator in the electrolyte. * The Above nominal capacity ; 25°C (77°F) Discharge at O.IC10A (1 xho) to 1.80V/cell (1.80Vpc) Note : SS-200, PS5-6S, PS7-6S and PS9-6S batteries have the vent plug instead of explosion resistant plug. Outline drawings with terminal position ■ Communication for marine purpose ■ Lighting for marine purpose ■ Emergency power for marine purpose

Open the catalog to page 10
CS,HS,SS,PS SERIES - 11

■ Safety precautions ■ ▲ Be sure to read through the instruction manual before using the battery. ▲ Keep the instruction manual near at hand future reference. Danger ● The battery may generate hydrogen gas, thus causing a risk of ignition or explosion. Be sure to ventilate the chamber where the battery is used so that the hydrogen gas concentration is kept at 0.8% or lower. ● Do not install the storage battery in a sealed, gas-tight enclosure, near a fire or source of sparks. Violation of this rule may results in the generation of hydrogen gas from the storage battery, causing a risk of...

Open the catalog to page 11
CS,HS,SS,PS SERIES - 12

Request of Cooperation of Recycling Used lead-acid storage batteries can be recycled. Do not scrap used storage batteries with general waste, but bring them to a place specified by government law. Please contact our local sales company for the details. When returning storage batteries, insulate terminals with adhesive tapes. Electric energy still remains in used storage batteries, insufficient insulation of terminals may result in explosion or fire. ● Please read the manual of the product concerned when you use it. ● The design and the specification might be changed without a previous...

Open the catalog to page 12